Fig.8-24: Skip frequency and range
● If set frequency is in one range and previous output is above this area, the upper
frequency (the skip frequency + skip range / 2) is output;
● If set frequency is in one range and previous output is below this area, the lower fre‐
quency (the skip frequency - skip range / 2) is output;
● If set frequency is in one range and previous output is within this area, previous out‐
put is output.
● If the set frequency is in the hysteresis range (including the boundaries)
of defined skip frequency, the frequency is set to upper / lower limit of
skip frequency range;
● If the skip frequency range is set to 0.00 Hz, no skip frequency control
is enabled;
● Do not make the 3 frequency ranges overlap or nest in each other.
S3.09
Skip window acceleration factor
Setting range
1 ~ 100
Minimum unit
1
Factory default
1
This parameter makes the acceleration inside the skip-window faster, the range for this
factor is 1 (normal acceleration) to 100 (acceleration is 100 times faster).
The resulting acceleration and deceleration time will be shorter than the
setting value when the factor is above 1.
S3.15
Restarting after power fault
Setting range
0 ~ 1
Minimum unit
1
Factory default
0