DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Minimum immunity requirements for PDSs intended for use in the first environment
Port
Phenomenon
ESD
Radio-frequency electro‐
magnetic field, amplitude
modulated
Fast transient-burst
Surge 1.2/50 μs, 8/20 μs
Conducted radio-frequen‐
cy common mode
Fast transient-burst
Fast transient-burst
Conducted radio-frequen‐
cy common mode
Fig.11-2: Minimum immunity requirements for PDSs intended for use in the first envi‐
ronment
● CD: Contact discharge.
● AD: Air discharge.
● AM: Amplitude modulation.
: Coupling line to line.
c
: Coupling line to earth.
d
Electromagnetic Compatibility (EMC)
Basic
standard
for test
method
4 kV CD or 8 kV AD
IEC
61000-4-2
if CD impossible
80 – 1000 MHz 3 V/m
1.4 – 2.0 GHz 3 V/m
IEC
61000-4-3
2.0 – 2.7 GHz 1 V/m
80% AM (1 kHz)
IEC
1 kV/5 kHz
61000-4-4
IEC
1 kV
a
, 2 kV
61000-4-5
0.15 – 80 MHz 3 V
IEC
61000-4-6
80 % AM (1 kHz)
1 kV/5 kHz
IEC
61000-4-4
Capacitive clamp
0.5 kV/5 kHz
IEC
61000-4-4
Capacitive clamp
0.15 – 80 MHz 3 V
IEC
61000-4-6
80 % AM (1 kHz)
Bosch Rexroth AG
Performance
Level
(acceptance)
criterion
b
B
A
B
B
A
B
B
A
149/235