Bosch Rexroth EFC 3600 Operating Instructions Manual page 108

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents

Advertisement

Bosch Rexroth AG
Parameter Settings
Setting range
0.00 ~ 10.00
Minimum unit
0.01
Factory default
1.00
● [E1.30] is used to define the function of analog outputs, as shown below:
[E1.30]=0: Output frequency. 0 ~ 10 V / 2 ~ 10 V, refers to 0 ~ max. frequency
[b1.05]
[E1.30]=1: Setting frequency. 0 ~ 10 V / 2 ~ 10 V, refers to 0 ~ max. frequency
[b1.05]
[E1.30]=2: Output current. 0 ~ 10 V / 2 ~ 10 V, refers to 0 ~ 2 x (rated current)
[E1.30]=3: Reserved
[E1.30]=4: Output voltage. 0 ~ 10 V / 2 ~ 10 V, refers to 0 ~ 1.2 x (rated voltage
[E1.30]=5: Output power. 0 ~ 10 V / 2 ~ 10 V, refers to 0 ~ 1.2 x (rated power)
[E1.30]=6: AIV. 0 ~ 10 V / 2 ~ 10 V, refers to 0 ~ 10 V
[E1.30]=7: AIC. 0 ~ 10 V / 2 ~ 10 V, refers to 4 ~ 20 mA
: Frequency converter rated voltage is defined in parameter [b0.20].
*
● [E1.31] is used to select output signals 0 ~ 10 V or 2 ~ 10 V.
● [E1.32] means the gain applied to analog output voltage.
For example: When the gain value is 0.00, then the analog output voltage will be 0
V. In the case of "FM1 channel mode" [E1.31]=1: 2 ~ 10 V and source value is 0,
– if gain=1.00, the analog output voltage will be 2 V.
– if gain=5.00, the analog output voltage will be 10 V.
106/235
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
)
*

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents