17.2.3
Group b1: Basic Parameters
Basic running control
Function
Name
code
First
frequency
b1.00
setting
source
Digital set
b1.01
frequency
saving
First RUN
b1.02
command
source
b1.03
Reserved
Digital set
b1.04
frequency
b1.05
Max. frequency 50.00 ~ 400.00 Hz
Upper
b1.06
frequency
Setting range
0: Given by panel potentiom‐
eter
1: Given by panel digital set‐
ting
2: Given by external analog
AIV
3: Given by external analog
AIC
4: Set by external UP/DOWN
terminals
5: Given via communication
6: Given by multi-speed
0: Not saved when powered
off and stopped
1: Not saved when powered
off; saved when stopped
2: Saved when powered off;
not saved when stopped
3: Saved when powered off
and stopped
0: Inputting commands with
panel
1: Inputting commands via
external terminals
2: Inputting commands via
communication
[b1.07] ~ [b1.06]
[b1.07] ~ [b1.05]
Bosch Rexroth AG
Appendix
Min.
Factory
Attribute
unit
default
1
0
1
0
1
0
0.01 Hz 50.00 Hz
0.01 Hz 50.00 Hz
0.01 Hz 50.00 Hz
STOP
STOP
STOP
RUN/
STOP
STOP
RUN/
STOP
199/235