Rexroth Frequency Converter EFC 3600
b0.05
Parameter initialization
Setting range
0 ~ 2
Minimum unit
1
Factory default
0
Used to restore parameters to factory defaults. Recent 3 faults and the last fault related
variables are recorded for further fault review. They can be deleted if necessary.
● 0: No action
● 1: Restore to factory defaults.
All parameters except [S2.00] ~ [S2.15] (motor parameters), [E4.20 ]~ [E4.22],
[E4.30] ~ [E4.35] (error messages), [b0.40] (system running time) are restored to
factory defaults.
● 2: Remove error records
Clearing parameters [E4.20] ~ [E4.22], [E4.30] ~ [E4.35].
After the command is executed completely, parameter [b0.05] will be set
to zero automatically.
b0.06
Parameter replication
Setting range
0 ~ 2
Minimum unit
1
Factory default
0
● 0: No action
● 1: Read parameter
All except read-only parameters
rating panel.
● 2: Write parameter
All except read-only parameters
cy converter.
● Read-only parameters
error memory parameters [E4.20] ~ [E4.22] and [E4.30] ~ [E4.35].
● After the command is executed completely, parameter [b0.06] will be
set to zero automatically and "b0.20" will be displayed.
● All operations are invalid during parameter replication.
*
are copied from the frequency converter to the ope‐
*
are copied from the operating panel to the frequen‐
*
: all monitoring parameters [d0.00] ~ [d0.20]; all
Bosch Rexroth AG
Parameter Settings
55/235