Bosch Rexroth EFC 3600 Operating Instructions Manual page 73

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents

Advertisement

DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Minimum unit
0.1s
Factory default
0.0s
b1.43
Stopping DC braking current
Setting range
0.0 % ~ 150.0 % (Rated frequency converter current)
Minimum unit
0.1 %
Factory default
0.0 %
There are two ways to carry out the stopping DC braking: parameter setting and digital
input. DC-braking will only be activated, when
● a stop command is active, and
● [b1.40]=0, and
● output frequency≤[b1.41], and
● digital input "Stopping DC-braking enabled" is active, or [b1.42]>0.
When [b1.42]>0 and digital input "Stopping DC-braking enabled" (Xn ter‐
minal is set as 13) is active, the frequency converter will keep on DC-brak‐
ing before the digital input goes inactive, even if the time [b1.42] is
elapsed.
Bosch Rexroth AG
Parameter Settings
71/235