Parameter Settings
Fig.8-7: S-curve
– Stage ① is defined by [b1.23] with percent of acceleration time.
– Stage ④ is defined by [b1.23] with percent of deceleration time.
– Stage ③ is defined by [b1.24] with percent of acceleration time.
– Stage ⑥ is defined by [b1.24] with percent of deceleration time.
b1.25 ~ b1.29
Reserved
b1.30
Starting mode
Setting range
0 ~ 2
Minimum unit
1
Factory default
0
b1.31
Starting frequency
Setting range
0.00 ~ 50.00 Hz
Minimum unit
0.01 Hz
Factory default
0.05 Hz
b1.32
Starting frequency holding time
Setting range
0.0 ~ 20.0s
Minimum unit
0.1s
Factory default
0.1s
b1.33
Starting DC braking time
Setting range
0.0 ~ 20.0s (0.0 represents no action of starting DC braking)
Minimum unit
0.1s