DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Function
Name
code
Phase loss
E4.06
protection
E4.07
~
Reserved
E4.14
Fault reset
Function code
Number of fault
E4.15
reset attempts
Interval between
E4.16
reset attempts
E4.17 ~ E4.19 Reserved
Error code memory
Function code
E4.20
Last fault type
E4.21
Second last fault type
E4.22
Third last fault type
E4.23 ~ E4.29 Reserved
● 0: No error
● 1: OC-1, means overcurrent happens when constant speed running
● 2: OC-2, means overcurrent happens when acceleration
● 3: OC-3, means overcurrent happens when deceleration
● 4: OE-1, means overvoltage happens when constant speed running
● 5: OE-2, means overvoltage happens when acceleration
Setting range
0: Both input and output
phase loss protection active
1: Only input phase loss pro‐
tection active
2: Only output phase loss
protection active
3: Both input and output
phase loss protection inactive
Name
Setting range
0 ~ 3
(0: No auto reset)
2 ~ 60s
Name
Min.
unit
1
Min.
unit
1
1s
Setting
Min.
Factory
range
unit
default
1
0 ~ 51
1
1
Bosch Rexroth AG
Appendix
Factory
Attribute
default
RUN/
3
STOP
Factory
Attribute
default
0
STOP
10s
STOP
Attribute
0
read only
0
read only
0
read only