DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Optional parts
Brake resistor, input choke, output filter, communication cable for cabinet control, etc.
Environment
Power reduction/Maximum in‐
stallation height
Ambient temperature
Relative humidity
Shocking
Allowed pollution degree
Construction
Degrees of protection
Cooling type
Standards and Certifications
CE; UL (in progress)
Mounting mode
Wall mounting
Fig.10-1: General technical data
Up to 1000m above sea level: none
1000 ~ 4000m above sea level: 1 % / 100m
-10 ~ 50 ℃ (Operating)
-20 ~ 60 ℃ (Storage)
< 90 % RH (Without condensation)
1g (< 20 Hz)
6g (20 ~ 50 Hz)
2 (EN 50178)
IP20 (Mounting on the metal wall in control cabinet)
Natural cooling (≤0.75 kW)
Enforced air cooling (>0.75 kW)
Bosch Rexroth AG
Technical Data
143/235