Bosch Rexroth AG
Parameter Settings
frequency will accelerate from [b1.07] to the command value according to the accel‐
eration time.
Fig.8-1: [b1.08]=0
Fig.8-2: [b1.08]=1
b1.10
Direction control
Setting range
0 ~ 3
Minimum unit
1
Factory default
0
Used for general settings of direction control. It accepts all the direction control source
(panel, communication and external terminal).
● 0: Both directions
● 1: Forward only. When reverse rotation command is active, the frequency converter
will stop immediately and the error shows up.
● 2: Reverse only. When forward rotation command is active, the frequency converter
will stop immediately and the error shows up.
● 3: Inverse default direction.
An adjustable dead zone time between forward and reverse can be set, please refer to
[S3.30].