Bosch Rexroth EFC 3600 Operating Instructions Manual page 125

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents

Advertisement

DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
H0.03
Local address
Setting range
1 ~ 247
Minimum unit
1
Factory default
1
● In ModBus communication, the maximum number of frequency converters in the net‐
work is 247 (0 is broadcast address).
H0.08
Communication disruption detection time
Setting range
0.0 ~ 60.0s
Minimum unit
0.1s
Factory default
0.0s
H0.09
Communication disruption action
Setting range
0 ~ 1
Minimum unit
1
Factory default
1
When [H0.08]=0.0s, the disruption detection is disabled, otherwise the detection is ena‐
bled.
If the interval between the current communication and the next exceeds the time de‐
fined in [H0.08], a communication error / warning is reported and the action is defined
by [H0.09]:
● 0: The motor freewheels to stop ([b1.40] stopping mode is inactive) after the commu‐
nication timeout.
● 1: The motor continues running at the set frequency. For error / waring message,
see
chapter 9 "Diagnosis" on page
124.
Bosch Rexroth AG
Parameter Settings
123/235