DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
This function is used to detect the difference between the output frequency and the set
frequency. The indicative signals are outputted when the difference between the output
frequency and the set frequency is within the range set in [E1.04], as shown in the fig‐
ure below:
Fig.8-37: Frequency arriving at detection width
E1.05
Frequency detection level FDT1
Setting range
0.00 ~ 400.0 Hz
Minimum unit
0.01 Hz
Factory default
50.00 Hz
E1.06
Frequency detection level FDT1 width
Setting range
0.00 ~ [E1.05]
Minimum unit
0.01 Hz
Factory default
1.00 Hz
E1.07
Frequency detection level FDT2
Setting range
0.00 ~ 400.0 Hz
Minimum unit
0.01 Hz
Factory default
25.00 Hz
E1.08
Frequency detection level FDT2 width
Setting range
0.00 ~ [E1.07]
Minimum unit
0.01 Hz
Factory default
1.00 Hz
When the output frequency exceeds the frequency set by [E1.05] or [E1.07], the digital
output "frequency level detection signal 1 or 2 (FDT1 or FDT2)" becomes active before