Rexroth Frequency Converter EFC 3600
Both of them have the nature of frequency, the corresponding reference frequency is
related to [E0.10]~[E0.28].
E3.03
Analog digital setting
Setting range
0.00 ~ 10.00 V
Minimum unit
0.01 V
Factory default
0.00 V
E3.04
Rotation speed digital setting
Setting range
0 ~ 30000 rpm
Minimum unit
1 rpm
Factory default
0 rpm
E3.10
P: Proportion gain
Setting range
0.000 ~ 10.000
Minimum unit
0.001
Factory default
1.500
E3.11
Ti: Integral time
Setting range
0.00 ~ 100.00s (0.00 represents no integral)
Minimum unit
0.01s
Factory default
0.00s
E3.12
Td: Derivative time
Setting range
0.00 ~ 100.00s (0.00 represents no integral)
Minimum unit
0.01s
Factory default
0.00s
E3.13
T: Sample period
Setting range
0.01 ~ 100.00s
Minimum unit
0.01s
Factory default
0.50s
● P: Proportion gain
– Decides the gain of deviation.
– Larger P means larger scale and faster response, but too large P leads to oscilla‐
tion.
– P cannot eliminate deviation completely.
● Ti: Integral time
– Used to eliminate the deviation
Smaller Ti means faster response of frequency converter to deviation changes,
but too small Ti leads to oscillation.
– Special case: If Ti=0, I component is disabled.