Bosch Rexroth EFC 3600 Operating Instructions Manual page 37

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents

Advertisement

DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
5.9.2
Recommendation on Cable Dimensioning
1. Depends on the power of a frequency converter.
2. In table column "Nominal Current of Fuse [A]", read corresponding information for
fuse.
1. The cable dimensions for inputs and outputs are based on supply
voltages of 1P 200 VAC / 3P 380 VAC.
2. For torque information, see the table below.
Input side
0.4
10
2.0 / 14
0.75
16
2.0 / 14
1.5
20
2.0 / 14
2.2
25
3.5 / 12
0.4
6
2.0 / 14
0.75
10
2.0 / 14
1.5
10
2.0 / 14
2.2
16
2.0 / 14
4.0
20
2.0 / 14
Fig.5-3: Fuse and cable dimensions
Output
side
Screw torque
for power
cable terminals
[Nm / lb-in]
(screw size)
1-phase 200 VAC class
2.0 / 14
0.8 / 7 (M3)
2.0 / 14
0.8 / 7 (M3)
2.0 / 14
0.8 / 7 (M3)
3.5 / 12
1.2 / 10 (M4)
3-phase 400 VAC class
2.0 / 14
0.8 / 7 (M3)
2.0 / 14
0.8 / 7 (M3)
2.0 / 14
0.8 / 7 (M3)
2.0 / 14
1.2 / 10 (M4)
2.0 / 14
1.2 / 10 (M4)
Bosch Rexroth AG
Mounting and Installation
PE
6 / 8
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
6 / 8
1.2 / 10 (M4)
6 / 8
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
6 / 8
1.2 / 10 (M4)
6 / 8
1.2 / 10 (M4)
35/235