Wiring Example - KEB COMBIVERT G6 series Installation Manual

Housing c power 5.5...11kw
Hide thumbs Also See for COMBIVERT G6 series:
Table of Contents

Advertisement

mixed sensor chain
3.2.5

Wiring example

3.2.5.1 Wiring example with extensive fire protection
F
Main fuses
K1 Line contactor with auxiliary contacts
G
KEB COMBIVERT G6
3.2.5.2 Note to the function
In the example above the locking of the line contactor K1 is interrupted in case of overheating
of the braking resistor. The line contactor drops and switches off the mains voltage. The au-
xiliary contacts 13/14 open the error linkage circuit at terminals I1/COM and release an error.
The modulation is switched off. Thus the drive in generatoric operation does not regenerate
further energy into the DC link circuit.
L1
L2
L3
F
1
3
5
K1
2
4
6
L1 L2 L3
++
PE
Power circuit
Connection of the Power Unit
+24VDC
11
12
OH1
RB
OH2
K1
PB
G
Control circuit
S1 Push-bottom switch for switch on
S2 Emergency-off switch
RB Braking resistor with temperature moni-
toring
T1
T2
S2
S1
13
K1
14
I1 COM
GB - 21