Installation and Connection
3.3

Connection of Power Circuit

3.3.1 Terminalstrip X1A

Terminal strip X1A / 230 V - class
suitable for
• 180...260 V AC / 1-phase (L1/N)
• 180...260 V AC / 3-phase (L1, L2, L3)
• DC-Supply 250...370 V DC (++, --)

3.3.2 Wiring instructions

Absolutely observe the connecting voltage of the KEB COMBIVERT. A 230V-unit
will be immediately destructed on a 400V-power supply.
Never exchange the mains and motor cables.
Some countries demand that the PE-terminal is directly connected to the terminal
box (not over the mounting plate).
36
• ++, PB
• U, V, W
• T1, T2
Terminal strip X1A / 400 V - Class
suitable for
• 305...500 V AC / 3-phase (L1, L2, L3)
• DC-Supply 420...720 V DC (++, --)
Braking resistor
Motor
Temperature sensor / switch (see chapter 3.3.6)