Advertisement

Parameter Description
Value Function
80
Active current > switching level
83
HSP5 bus synchronized
84
Actual value < minimum setpoint
85
Warning, external error input is active
86
Warning HSP5 or operator watchdog
88
Warning overload summary alarm (switching condition 7, 8, 9 , 10 or 11 is active)
No listed values are only for application mode.
CP.35 AN1 Set value selection
The setpoint input (AN1) of the control can be triggered with different signal levels. In order to
correctly evaluate the signal, this parameter must be adapted to the signal source.
Value Set value signal
0
0...10 V DC / Ri = 29 kΩ
1
0...±20 mA DC / Ri = 500 Ω
2
4...20 mA DC / Ri = 500 Ω
CP.36 Select 50/60Hz mode
When units or machines are delivered in the area of application of UL an adaption of the fac-
tory setting to the valid operating data there can be done with this parameter.
Value Default value
0
Current values and limits, motor data, frequencies and speed relate to a 50 Hz
mains with 400 V rated voltage.
1
Current values and limits, motor data, frequencies and speed relate to a 60 Hz
mains with 460 V rated voltage.
CP.37 Response of external overtemperature (only for devices with temperature input)
This parameter determines the response of the drive to the external temperature monitoring.
The function is switched off at factory setting. The power circuit terminals T1/T2 must be
connected to activate the function. Then the response can be adjusted according to the fol-
lowing table. If overheat no longer exists, the message E.ndOH (or A.ndOH) is output. Only
then the error can be reset or the automatic restart can be carried out.
CP.37 Display Response
0
E.dOH Immediate disabling of modulation
1*
A.dOH Quick stopping / disabling of modulation after re-
2*
A.dOH Quick stopping / holding torque at speed 0
3
A.dOH Immediate disabling of modulation
4*
A.dOH Quick stopping / disabling of modulation after re-
5*
A.dOH Quick stopping / holding torque at speed 0
6*
none
7
none
*) If the motor is still too hot after 10 seconds, the error E.dOH is triggered and the modulation
is switched off!
GB - 36
aching speed 0
aching speed 0
No effect on the drive; switching condition "PTC
overtemperature warning" (value 9) is set and can
be used with CP.31/32 to activate an output.
No effect on the drive; Malfunction is not pre-
sent ! Switching condition „External overtempera-
ture" (value 9) is not set.
Restart
Remove fault;
reset
Autoreset, if no
fault is present
inapplicable