KEB COMBIVERT G6 series Installation Manual page 35

Housing c power 5.5...11kw
Hide thumbs Also See for COMBIVERT G6 series:
Table of Contents

Advertisement

5
DC link voltage CP.07
6
apparent current CP.04
7
active current ru.17
8...10 reserved
11
absolute active current ru.17
12
power stage temperature ru.38
13...21 reserved
22
Analog input before amplification (ru.27)
23
Analog input after amplification (ru.28)
24...25 reserved
26
Active power ru.81
CP.32 Transistor output / function (term. X2A.10)
The switching level of CP.32 is pre-set to 4.00. Value range see CP.33.
CP.33 Relay output 1 / function (terminals X2A.11...13)
The switching level of CP.33 is adjusted by CP.34.
Value Function
0
No function (generally off)
1
Generally on
2
Run signal; also by DC-braking
3
Ready signal (no error)
4
Fault relay
5
Fault relay (without auto-reset)
6
Warning or error message (also at fast stop)
7
Overload pre-warning (OL)
8
Overtemperature pre-warning (OH)
9
External Overtemperature pre-warning (dOH)
10
Motor protection pre-warning (OH2)
11
Interior temperature pre-warning (OHI)
12
Cable breakage 4...20 mA on analog input 1
14
max. constant current (Stall, CP.25) exceeded
15
max. ramp current (LA-Stop, CP.24) exceeded
16
DC-braking active
20
Actual value = set value (CP.3 = Fcon; rcon; not at noP, LS, error, SSF)
21
Accelerate (CP.3=FAcc, rAcc, LAS)
22
Decelerate (CP.3 = FdEc, rdEc, LdS)
23
Real direction of rotation = set direction of rotation
24
Utilization (CP.6) > switching level
25
Active current > switching level
26
Intermediate circuit voltage (CP.7) > switching level
27
Real value (CP.1) > switching level
28
Set value (CP.2) > switching level
31
Absolute set value at AN1 > switching level
34
Set value at AN1 > switching level
40
Hardware current limit activated
41
modulation on
44
Inverter status > switching level
47
Ramp output value > switching level
48
Apparent current (CP.4) > switching level
49
Forward running (not at nOP, LS, abnormal stopping or error)
50
Reverse running (not at nOP, LS, abnormal stopping or error)
63
Absolute ANOUT1 > switching level
65
ANOUT1 > switching level
70
Driver voltage active (safety relay)
73
Absolute active power > switching level
74
Active power > switching level
Parameter Description
0...1000 V
0...2 • rated current
0...2 • ±rated current
0...2 • rated current
0...100 °C
0...100 %
0...400 %
0...±2 • Rated power
further on next side
GB - 35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combivert g6

Table of Contents