Amax-4820: 4-Channel Analog Output Module - Advantech AMAX-4800 Series User Manual

Industrial ethercat slave modules
Table of Contents

Advertisement

Load/Save Calibration Parameters
Index
Name
2190:01
Load Calibration Parameters
1: Load calibration parameters from a user-configurable area
0: Load calibration parameters from the default area
Index
Name
2190:02
Save Calibration Parameters
1: Save calibration parameters to a user-configurable area
3.5.2

AMAX-4820: 4-Channel Analog Output Module

3.5.2.1
Object Dictionary Configuration
Analog Output Enabled
Index
Name
2180:01
AO 0 Output Enabled
2181:01
AO 1 Output Enabled
2182:01
AO 2 Output Enabled
2183:01
AO 3 Output Enabled
0: Output disabled
1: Output enabled
Analog Output Range
Index
Name
2180:02
AO 0 Range Configuration UINT16
2181:02
AO 1 Range Configuration UINT16
2182:02
AO 2 Range Configuration UINT16
2183:02
AO 3 Range Configuration UINT16
0: 0 ~ 5 V
1: 0 ~ 10 V
2: ±5 V
3: ±10 V
4: 0 ~ 20 mA
5: 4 ~ 20 mA
AMAX-4800 User Manual
Data Type
Flags
UINT16
RW
Data Type
Flags
UINT16
RW
Data Type
Flags
UINT16
RW
UINT16
RW
UINT16
RW
UINT16
RW
Data Type
Flags
RW
RW
RW
RW
38
Default
0x0000 (0dec)
Default
0x0000 (0dec)
Default
0x0000 (0dec)
0x0000 (0dec)
0x0000 (0dec)
0x0000 (0dec)
Default
0x0000 (0dec)
0x0000 (0dec)
0x0000 (0dec)
0x0000 (0dec)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents