Section 2
Modbus data mappings
BitA
RegA
2820
176.04
2821
176.05
2822
176.06
2823
176.07
2834
177.02
2835
177.03
2.3.1.5
Table 8:

CTRL.CBXCBR1 Circuit-breaker control (1)

BitA
RegA
2836
177.04
2837
177.05
2838
177.06
2839
177.07
2.3.1.6
Table 9:

LD0.CCBRBRF1 Circuit breaker failure protection (1)

BitA
RegA
2828
176.12
2829
176.13
2830
176.14
2831
176.15
2832
177.00
2833
177.01
2.3.1.7
Table 10:

LD0.CMMXU1 Three-phase current measurement (1)

BitA
RegA
2752
172.00
2753
172.01
2754
172.02
2755
172.03
2756
172.04
Table continues on next page
14
IEC 61850 name
SA name
< reserved >
< reserved >
.Pos.stSeld
SELECTED
.mcd
.SynItlByps.stVal
ITL_BYPASS
.mcd
CTRL.CBXCBR1 Circuit-breaker control (1)
IEC 61850 name
SA name
CTRL.CBXCBR1
.BlkOpn.stVal
BLK_OPEN
.mcd
.BlkCls.stVal
BLK_CLOSE
.mcd
LD0.CCBRBRF1 Circuit breaker failure protection (1)
IEC 61850 name
SA name
LD0.CCBRBRF1
.Str.general
CB_FAULT_AL
.mcd
.OpEx.general
TRBU
.mcd
.OpIn.general
TRRET
.mcd
LD0.CMMXU1 Three-phase current measurement (1)
IEC 61850 name
SA name
LD0.CMMXU1
.HiAlm.stVal
HIGH_ALARM
.mcd
.HiWrn.stVal
HIGH_WARN
.mcd
.LoWrn.stVal
LOW_WARN
Description
CB selected for control
Interlock bypass
Description
Open blocked
Close blocked
Description
Timer running
Fail, external trip
Internal re-trip
Description
High alarm
High warning
Low warning
1MRS757464 C
Values
1=Selected
1=Bypass
Values
1=Blocked
1=Blocked
Values
1=Running
1=Ext.trip
1=Re-trip
Values
1=Alarm
1=Warning
1=Warning
REM611
Point List Manual