1MAC309294-MB F
Table 155:
50N/G-2 Non group settings
Parameter
Values (Range)
Operation
1=Enable
5=Disable
Minimum trip time
20...60000
Reset delay time
0...60000
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 156:
50N/G-3 Group settings
Parameter
Pickup value
Pickup value mult
Trip delay time
Table 157:
50N/G-3 Non group settings
Parameter
Operation
Reset delay time
RER620
Technical Manual
Unit
ms
ms
Values (Range)
Unit
1.00...40.00
xIn
0.8...10.0
20...200000
ms
Values (Range)
Unit
1=Enable
5=Disable
0...60000
ms
Step
Default
Description
5=Disable
Operation Disable / Enable
1
20
Minimum trip time for IDMT curves
1
20
Reset delay time
2=DFT
Selects used measurement mode
28.2000
Parameter A for customer programmable curve
0.1217
Parameter B for customer programmable curve
2.00
Parameter C for customer programmable curve
29.10
Parameter D for customer programmable curve
1.0
Parameter E for customer programmable curve
Step
Default
Description
0.01
1.00
Pickup value
0.1
1.0
Multiplier for scaling the pickup value
10
20
Trip delay time
Step
Default
5=Disable
1
20
Section 4
Protection functions
Description
Operation Disable / Enable
Reset delay time
135