ABB RER620 Technical Manual page 224

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

Section 4
Protection functions
218
Over/under
frequency
f
detection
df/dt
detection
BLOCK
Figure 100:
Functional module diagram
Freq>/< detection
The frequency detection module includes an overfrequency or underfrequency detection
based on the Operation mode setting.
In the "Freq>" mode, the measured frequency is compared to the set Pickup value Freq>.
If the measured value exceeds the set value of the Start value Freq> setting, the module
reports the exceeding of the value to the operate logic module.
In the "Freq<" mode, the measured frequency is compared to the set Pickup value Freq<.
If the measured value is lower than the set value of the Start value Freq< setting, the
module reports the value to the operate logic module.
df/dt detection
The frequency gradient detection module includes a detection for a positive or negative
rate-of-change (gradient) of frequency based on the set Start value df/dt value. The
negative rate-of-change protection is selected when the set value is negative. The positive
rate-of-change protection is selected when the set value is positive. When the frequency
gradient protection is selected and the gradient exceeds the set Pickup value df/dt value,
the module reports the exceeding of the value to the operate logic module.
The relay does not accept the set value "0.00" for the Pickup value df/dt
setting.
Operate logic
This module is used for combining different protection criteria based on the frequency and
the frequency gradient measurement to achieve a more sophisticated behavior of the
function. The criteria are selected with the Operation mode setting.
df/dt
Trip logic
Blocking
logic
1MAC309294-MB F
TRIP
PICKUP
TRIP_OFRQ
TRIP_UFRQ
PICKUP_OFRQ
PICKUP_UFRQ
TRIP_FRG
PICKUP_FRG
RER620
Technical Manual