Technical Manual
User-programmable inverse-time characteristics
The user can define curves by entering parameters into the following standard formula:
t[s]
Trip time (in seconds)
set Curve parameter A
A
B
set Curve parameter B
C
set Curve parameter C
set Curve parameter E
E
I
Measured current
set Pickup value
I>
set Time multiplier
k
RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is a
ground-fault specific characteristic.
The RI-type is calculated using the formula
⎛
⎜
k
=
t s
[ ]
⎜
>
I
⎜ ⎜
−
×
0 339 0 236
.
.
⎝
I
The RD-type is calculated using the formula
⎛
I
=
−
×
t s
[ ]
5 8 1 35 In
.
.
⎜
× >
k I
⎝
t[s]
Trip time (in seconds)
set Time multiplier
k
I
Measured current
I>set Pickup value
General function block features
⎞
⎟
⎟
⎟ ⎟
⎠
⎞
⎟
⎠
Section 10
(Equation 59)
(Equation 60)
(Equation 61)