User-Programmable Inverse-Time Characteristics; Ri And Rd-Type Inverse-Time Characteristics - ABB RER620 Technical Manual

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

1MAC309294-MB F
10.2.1.3
10.2.1.4
RER620
Technical Manual

User-programmable inverse-time characteristics

The user can define curves by entering parameters into the following standard formula:
t[s]
Trip time (in seconds)
set Curve parameter A
A
B
set Curve parameter B
C
set Curve parameter C
set Curve parameter E
E
I
Measured current
set Pickup value
I>
set Time multiplier
k

RI and RD-type inverse-time characteristics

The RI-type simulates the behavior of electromechanical relays. The RD-type is a
ground-fault specific characteristic.
The RI-type is calculated using the formula
k
=
t s
[ ]
>
I
⎜ ⎜
×
0 339 0 236
.
.
I
The RD-type is calculated using the formula
I
=
×
t s
[ ]
5 8 1 35 In
.
.
× >
k I
t[s]
Trip time (in seconds)
set Time multiplier
k
I
Measured current
I>set Pickup value
General function block features
⎟ ⎟
Section 10
(Equation 59)
(Equation 60)
(Equation 61)
521