ABB RER620 Technical Manual page 570

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

Section 13
Technical data
564
Table 445:
Uninterruptible Power Supply (UPS) tests
Test
Control voltage
(IEEE C37.90-2005)
UPS0001
UPS0002
Control power interruptions
(IEC 60255-11-2008)
UPS0001 and UPS0002
IEEE C37.60 - 2003
UPS0001 and UPS0002
Power consumption
(IEEE C37.90-2005)
UPS0001
UPS0002
Auxiliary Power Supply
Battery Charger
Battery Run Time
Boost Supply
Table 446:
Energizing inputs
Description
Rated frequency
Current inputs
Rated current, I
Thermal withstand capability:
Continuously
For 1 s
Dynamic current withstand:
Half-wave value
Input impedance
Voltage inputs
Rated voltage
Voltage withstand:
Continuous
For 10 s
Burden at rated voltage
1. Ordering option for ground current input
2. Ground current and/or phase current
Type test value
90 to 150 V AC
180 to 280V AC
60 VDC
15 kV, 27 kV, 38 kV reclosers
90 to 150 VAC
180 to 280 VAC
12 VDC & 24 VDC
48 VDC
38 hr
Programmable 61-250 VDC
Value
50/60 Hz ± 5 Hz
1
0.2/1 A
n
4 A
100 A
250 A
<100 mΩ
100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
(Parametrization)
2 x V
(240 V)
n
3 x V
(360 V)
n
<0.05 VA
1MAC309294-MB F
Reference
No influence
No influence
2 seconds (no battery)
No influence
25 W (nominal)/~120 W (max)
20 W (nominal)/~24 W (max)
35 W max
48 VDC 12 amp hr. battery with standard
load (15 W)
80 W max
2
1/5 A
20 A
500 A
1250 A
<20 mΩ
Technical Manual
RER620