ABB RER620 Technical Manual page 59

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

1MAC309294-MB F
Table 34:
FR Non group settings
Parameter
Values (Range)
Operation
1=Enable
5=Disable
Trig mode
0=Trip or Pickup
1=Trip only
2=Pickup only
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
RER620
Technical Manual
Unit
Step
Table 35:
FR Monitored data
Name
Type
Number
INT32
Time
Timestamp
Max bias current A
FLOAT32
Max bias current B
FLOAT32
Max bias current C
FLOAT32
Max current IA
FLOAT32
Max current IB
FLOAT32
Max current IC
FLOAT32
Current IA
FLOAT32
Current IB
FLOAT32
Current IC
FLOAT32
Max current IG
FLOAT32
Current IG
FLOAT32
Current I2
FLOAT32
Current IN
FLOAT32
Voltage VA
FLOAT32
Voltage VB
FLOAT32
Voltage VC
FLOAT32
Voltage VAB
FLOAT32
Voltage VBC
FLOAT32
Voltage VCA
FLOAT32
Voltage VG
FLOAT32
Voltage V0
FLOAT32
Voltage V1
FLOAT32
Voltage V2
FLOAT32
49 thermal level
FLOAT32
87LOZREF duration
FLOAT32
51P duration
FLOAT32
50P-3 duration
FLOAT32
67/51P duration
FLOAT32
67/50P-1 duration
FLOAT32
Default
Description
1=Enable
Operation Off / On
0=Trip or Pickup
Triggering mode
2=DFT
Selects used measurement mode
Values (Range)
Unit
Description
0...999999
Fault record number
Time of recording
0.000...50.000
Maximum phase A bias current
0.000...50.000
Maximum phase B bias current
0.000...50.000
Maximum phase C bias current
0.000...50.000
xIn
Maximum phase A current
0.000...50.000
xIn
Maximum phase B current
0.000...50.000
xIn
Maximum phase C current
0.000...50.000
xIn
Phase A current
0.000...50.000
xIn
Phase B current
0.000...50.000
xIn
Phase C current
0.000...50.000
xIn
Maximum residual current
0.000...50.000
xIn
Ground current
0.000...50.000
xIn
Negative sequence current
0.000...50.000
xIn
Calculated residual current
0.000...4.000
xVn
Phase A voltage
0.000...4.000
xVn
Phase B voltage
0.000...4.000
xVn
Phase C voltage
0.000...4.000
xVn
Phase A to phase B voltage
0.000...4.000
xVn
Phase B to phase C voltage
0.000...4.000
xVn
Phase C to phase A voltage
0.000...4.000
xVn
Ground voltage
0.000...4.000
xVn
Zero sequence voltage
0.000...4.000
xVn
Positive sequence voltage
0.000...4.000
xVn
Negative sequence voltage
0.00...99.99
49 calculated temperature of the protected
object relative to the operate level
0.00...100.00
%
87LOZREF Pickup duration
0.00...100.00
%
51P Pickup duration
0.00...100.00
%
50P-3 Pickup duration
0.00...100.00
%
67/51P Pickup duration
0.00...100.00
%
67/50P-1 Pickup duration
Section 3
Basic functions
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents