Section 6
Condition monitoring functions
370
Figure 203:
Trip Curves for a typical 12 kV, 630 A, 16 kA vacuum interrupter
Nr
the number of closing-opening operations allowed for the circuit breaker
Ia
the current at the time of tripping of the circuit breaker
Calculation of Directional Coefficient
The directional coefficient is calculated according to the formula:
⎛
B
log
⎜
A
⎝
=
Directional Coef
⎛
I
f
log
⎜
I
⎝
r
I
Rated operating current = 630 A
r
I
Rated fault current = 16 kA
f
A
Op number rated = 30000
B
Op number fault = 20
Calculation for estimating the remaining life
The equation shows that there are 30,000 possible operations at the rated operating current
of 630 A and 20 operations at the rated fault current 16 kA. Therefore, if the tripping
⎞
⎟
⎠
= −
. 2 2609
⎞
⎟
⎠
1MAC309294-MB F
(Equation 42)
RER620
Technical Manual