ABB RER620 Technical Manual page 146

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

Section 4
Protection functions
140
For defining the operation sector, there are five modes available through the Operation
mode setting.
Table 162:
Operation modes
Operation mode
Phase angle
IoSin
IoCos
Phase angle 80
Phase angle 88
The directional operation can be selected with the Directional mode setting. The user can
select either "Non-directional", "Forward" or "Reverse" operation. The operation criterion
is selected with the Operation mode setting. By setting Allow Non Dir to "True",
non-directional operation is allowed when directional information is invalid.
The Characteristic angle setting is used in "Phase angle" mode to adjust the operation
according to the method of neutral point earthing so that in an isolated network the
Characteristic angle (φ
RCA
the characteristic angle can be changed via the control signal RCA_CTL, in which case the
alternatives are -90° and 0°. The operation of RCA_CTL depends on the Characteristic
angle setting.
The Correction angle setting can be used to improve selectivity when there are
inaccuracies due to measurement transformers. The setting decreases the operation sector.
The correction can only be used with the "IoCos" or "IoSin" modes.
The minimum signal level which allows directional operation can be set by using the Min
trip current and Min trip voltage settings.
When polarizing quantity (residual voltage (-Uo)) is inverted because of switched voltage
measurement cables, the correction can be done by setting the Pol reversal to "True"
which turns polarizing quantity by 180 degrees.
For definitions of different directional earth-fault characteristics, see the
Directional earth-fault characteristics section in this manual.
The directional calculation module calculates several values which are presented in the
monitored data.
Description
The operating sectors for forward and reverse are
defined with the settings
forward angle
angle.
The operating sectors are defined as "forward" when
the mathematical expression has a positive value
and "reverse" when the value is negative
As "IoSin" mode. Only cosine is used for calculating
the operation current.
The sector maximum values are frozen to 80
degrees, respectively. Only Min forward angle and
Min reverse angle
The sector maximum values are frozen to 88
degrees. Otherwise as "Phase angle 80" mode.
) = -90° and in a compensated network φ
1MAC309294-MB F
Min forward angle
Max
,
Min reverse angle
Max reverse
,
and
are settable.
= 0°. In addition,
RCA
Technical Manual
RER620