Section 5
Control functions
Parameter
Values (Range)
Synchronization set
0...127
Auto wait time
0.00...60.00
Auto lockout reset
0=False
1=True
Protection crd limit
1...5
Protection crd mode
1=No condition
2=AR
inoperative
3=CB close
manual
4=AR inop, CB
man
5=Always
Auto initiation cnd
1=Not allowed
2=When sync
fails
3=CB
doesn't
close
4=Both
Tripping line
0...63
Control line
0...63
Allow shot jump
0=False
1=True
CB closed Pos status
0=False
1=True
Fourth delay in SOTF
0=False
1=True
Init signals CBB1
0...63
Init signals CBB2
0...63
Init signals CBB3
0...63
Init signals CBB4
0...63
Init signals CBB5
0...63
Init signals CBB6
0...63
Init signals CBB7
0...63
Blk signals CBB1
0...63
Blk signals CBB2
0...63
Blk signals CBB3
0...63
Blk signals CBB4
0...63
Blk signals CBB5
0...63
Blk signals CBB6
0...63
Blk signals CBB7
0...63
Shot number CBB1
0...5
Shot number CBB2
0...5
Shot number CBB3
0...5
Shot number CBB4
0...5
Shot number CBB5
0...5
Shot number CBB6
0...5
318
Unit
Step
Default
0
s
0.01
2.00
1=True
3
1=No condition
2=When sync
fails
63
63
1=True
1=False
0=False
3
3
3
3
0
0
0
60
60
60
60
0
0
0
0
0
0
0
0
0
Description
Configures synchrony check for CBB
Maximum wait time for reclosing condition fulfilling
Automatic lockout reset
Protection coordination shot limit
Protection coordination mode
Auto initiation condition
Defines INIT inputs which cause CMD_OPEN activation
Defines INIT inputs which are protection signals
Allows shot jumping
Status (TRUE or FALSE) meaning closed CB in input
CB_POS
Sets fourth delay into use for all DEL_INIT signals during
SOTF
Sets INIT inputs which initiate CBB1
Sets INIT inputs which initiate CBB2
Sets INIT inputs which initiate CBB3
Sets INIT inputs which initiate CBB4
Sets INIT inputs which initiate CBB5
Sets INIT inputs which initiate CBB6
Sets INIT inputs which initiate CBB7
Sets INIT inputs which block CBB1
Sets INIT inputs which block CBB2
Sets INIT inputs which block CBB3
Sets INIT inputs which block CBB4
Sets INIT inputs which block CBB5
Sets INIT inputs which block CBB6
Sets INIT inputs which block CBB7
Sets CBB1 shot number
Sets CBB2 shot number
Sets CBB3 shot number
Sets CBB4 shot number
Sets CBB5 shot number
Sets CBB6 shot number