Section 5
Control functions
322
Table 302:
79 monitored data
Name
Type
FRQ_OPR_CNT
INT32
FRQOP_CNT_AL
Binary
STATUS
Enum
ACTIVE
Binary
INPRO_1
Binary
INPRO_2
Binary
INPRO_3
Binary
INPRO_4
Binary
INPRO_5
Binary
DISCR_IN_PRO
Binary
CUTOUT_INPRO
Binary
SUC_RECL
Binary
UNSUC_CB
Binary
CNT_SHOT1
INT32
CNT_SHOT2
INT32
CNT_SHOT3
INT32
CNT_SHOT4
INT32
CNT_SHOT5
INT32
COUNTER
INT32
SHOT_PTR
INT32
MAN_CB_CL
Binary
SOTF
Binary
REC_T_STD
Binary
REC_T_ELA
Binary
DISA_COUNT
Values (Range)
Unit
Description
0...2147483647
Frequent operation counter
0=False
Frequent operation counter alarm
1=True
-2=Unsuccessful
Auto reclosing status
-1=Not defined
1=Ready
2=In progress
3=Successful
0=False
Reclosing sequence active
1=True
0=False
First reclosing in progress
1=True
0=False
Second reclosing in progress
1=True
0=False
Third reclosing in progress
1=True
0=False
Fourth reclosing in progress
1=True
0=False
Fifth reclosing in progress
1=True
0=False
Discrimination time in progress
1=True
0=False
Cut-out time in progress
1=True
0=False
Reclosing sequence successful
1=True
0=False
Circuit breaker closing unsuccessful
1=True
0...2147483647
Resetable operation counter, shot 1
0...2147483647
Resetable operation counter, shot 2
0...2147483647
Resetable operation counter, shot 3
0...2147483647
Resetable operation counter, shot 4
0...2147483647
Resetable operation counter, shot 5
0...2147483647
Resetable operation counter, all shots
0...6
Shot pointer value
0=False
Circuit breaker closed manually
1=True
0=False
Switch-onto-fault
1=True
0=False
Reclaim time started
1=True
0=False
Reclaim time elapsed
1=True
Disable signal for counters
1MAC309294-MB F