magnitude, the FAULT_DIR and DIRECTION outputs are set to 0 = unknown, except
when the Allow non dir setting is "True". In that case, the function is allowed to operate in
the directional mode as non-directional, since the directional information is invalid.
The calculated I
sin(φ) or I
0
through the I_OPER monitored data. The value can be passed directly to a decisive
element, which provides the final pickup and trip signals.
The I_OPER monitored data gives an absolute value of the calculated
current. Otherwise, the value of a current in a reverse area is negative.
The following examples show the characteristics of the different operation criteria:
Example 1.
I
sin(φ) criterion selected, forward-type fault
0
=> FAULT_DIR = 1
Correction
angle
0
= -90 deg
RCA
0
Figure 66:
Operating characteristic I
The operating sector is limited by Angle correction, that is, the operating sector is 180
degrees - 2*(Angle correction).
Example 2.
I
sin(φ) criterion selected, reverse-type fault
0
cos(φ) current used in direction determination can be read
0
0
Min operating
current
sin(φ) in forward fault
0
Section 4
Protection functions
155