ABB RER620 Technical Manual page 40

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

Section 3
Basic functions
Table 11:
Binary input: Non group settings
Parameter
Values (Range)
Threshold voltage
18...176
Input osc. level
2...50
Input osc. hyst
2...50
Table 12:
Ethernet front port: Non group settings
Parameter
Values (Range)
IP address
Mac address
Table 13:
Ethernet rear port: Non group settings
Parameter
Values (Range)
IP address
Subnet mask
Default gateway
Mac address
Table 14:
General system: Non group settings
Parameter
Values (Range)
Rated frequency
1=50Hz
2=60Hz
Phase rotation
1=ABC
2=ACB
Blocking mode
1=Freeze timer
2=Block all
3=Block trip
Bay name
SG follow input
0=False
1=True
Phase Order Mode
1=ABC
2=BCA
3=CAB
4=ACB
5=CBA
6=BAC
34
Unit
Step
Default
Vdc
2
48
events/s
1
30
events/s
1
10
Unit
Step
Default
192.168.0.254
XX-XX-XX-XX-XX-XX
Unit
Step
Default
192.168.2.10
255.255.255.0
192.168.2.1
XX-XX-XX-XX-XX-XX
Unit
Step
Default
2=60Hz
1=ABC
1=Freeze timer
RER620
0=False
1=ABC
When the Phase Order Mode setting is changed, the relay must be rebooted
to activate the new setting.
Description
Digital input threshold voltage
Digital input oscillation suppression threshold
Digital input oscillation suppression hysteresis
Description
IP address for front port (fixed)
Mac address for front port
Description
IP address for rear port(s)
Subnet mask for rear port(s)
Default gateway for rear port(s)
Mac address for rear port(s)
Description
Rated frequency of the network
Phase rotation order
Behavior for function BLOCK inputs
Bay name in system
Enable setting group change to follow the input state
Selection for phase correction order
1MAC309294-MB F
RER620
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents