ABB RER620 Technical Manual page 127

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

1MAC309294-MB F
Table 139:
67/50P-2 Non group settings
Parameter
Values (Range)
Operation
1=Enable
5=Disable
Reset delay time
0...60000
Minimum trip time
20...60000
Allow Non Dir
0=False
1=True
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Min trip current
0.01...1.00
Min trip voltage
0.01...1.00
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
RER620
Technical Manual
Unit
Step
Default
5=Disable
ms
1
20
ms
1
20
0=False
2=DFT
xIn
0.01
0.01
xVn
0.01
0.01
28.2000
0.1217
2.00
29.10
1.0
1=1 out of 3
Protection functions
Description
Operation Disable / Enable
Reset delay time
Minimum trip time for IDMT curves
Allows prot activation as non-dir when dir info is invalid
Selects used measurement mode
Minimum trip current
Minimum trip voltage
Parameter A for customer programmable curve
Parameter B for customer programmable curve
Parameter C for customer programmable curve
Parameter D for customer programmable curve
Parameter E for customer programmable curve
Number of phases required for trip activation
Section 4