ABB RER620 Technical Manual page 159

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

1MAC309294-MB F
RER620
Technical Manual
I
0
Min forward angle
Non-operating area
Max reverse angle
Min operate
current
Figure 65:
Configurable operating sectors in phase angle characteristic
Table 169:
Momentary operating direction
Fault direction
Angle between the polarizing and operating quantity
is not in any of the defined sectors.
Angle between the polarizing and operating quantity
is in the forward sector.
Angle between the polarizing and operating quantity
is in the reverse sector.
Angle between the polarizing and operating quantity
is in both the forward and the reverse sectors, that
is, the sectors are overlapping.
Directional operation is not allowed (the setting Allow non dir is "False") when the
measured polarizing or operating quantities are not valid, that is, their magnitude is below
the set minimum values. The minimum values can be defined with the settings Min trip
current and Min trip voltage. In case of low magnitudes, the FAULT_DIR and
DIRECTION outputs are set to 0 = unknown, except when the Allow non dir setting is
"True". In that case, the function is allowed to operate in the directional mode as
non-directional, since the directional information is invalid.
-V
0
= 0 deg
RCA
Forward
area
Max forward angle
Min reverse angle
Backward
area
The value for DIRECTION
0 = unknown
1= forward
2 = backward
3 = both
Section 4
Protection functions
153