ABB RER620 Technical Manual page 140

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Values (Range)
Pickup block enable
0=Disabled
1=Enabled
Pickup block value
1.00...40.00
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Time adder
0.00...2.00
Table 153:
51N/G, 50N/G-1 and 50SEF Non group settings
Parameter
Values (Range)
Operation
1=Enable
5=Disable
Minimum trip time
20...60000
Reset delay time
0...60000
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 154:
50N/G-2 Group settings
Parameter
Values (Range)
Pickup value
Pickup value mult
Time multiplier
Trip delay time
Operating curve type
Type of reset curve
Time adder
134
Unit
Step
A
0.01
s
0.01
Unit
ms
ms
Unit
0.10...40.00
xIn
0.8...10.0
0.05...15.00
40...200000
ms
1=ANSI Ext Inv
3=ANSI Norm Inv
5=ANSI DT
9=IEC Norm Inv
10=IEC Very Inv
12=IEC Ext Inv
15=IEC DT
17=Programmable
1=Immediate
2=Def time reset
3=Inverse reset
0.00...2.00
s
Default
Description
0=Disabled
Enables start block function
5
Value over which trip will be blocked
1=Immediate
Selection of reset curve type
0
Time added after curve time before trip
Step
Default
Description
5=Disable
Operation Disable / Enable
1
20
Minimum trip time for IDMT curves
1
20
Reset delay time
2=DFT
Selects used measurement mode
28.2000
Parameter A for customer programmable curve
0.1217
Parameter B for customer programmable curve
2.00
Parameter C for customer programmable curve
29.10
Parameter D for customer programmable curve
1.0
Parameter E for customer programmable curve
Step
Default
0.01
0.50
0.1
1.0
0.05
1.00
10
40
5=ANSI DT
1=Immediate
0.01
0
Description
Pickup value
Multiplier for scaling the pickup value
Time multiplier in IEC/ANSI IDMT curves
Trip delay time
Selection of time delay curve type
Selection of reset curve type
Time added after curve time before trip
1MAC309294-MB F
RER620
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents