ABB RER620 Technical Manual page 55

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

1MAC309294-MB F
RER620
Technical Manual
Table 31:
Warning indications and codes
Warning indication
Warning
Internal system warning
Warning
Time synch error
Warning
Watchdog reset
Warning
Power down det.
Warning
IEC61850 error
Warning
Modbus error
Warning
DNP3 error
Warning
Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning
Logic error
Warning
SMT logic error
Warning
GOOSE input error
Warning
ACT error
Warning
GOOSE Tx/Rx error
Warning
AFL error
Warning
Unack card comp.
Warning
Protection comm.
Warning
UPD Voltage Low in X115
Warning
UPS Communication error in X115
Warning
UPS Command failure in X115
Warning
Breaker Operation Failure
For further information on warning indications, see the operation manual.
Warning code
Additional information
2
An internal system warning condition has occurred.
5
A time synch error warning condition has occurred.
10
A watchdog reset has occurred.
11
The auxiliary supply voltage has dropped too low.
20
Error when building the IEC 61850 data model.
21
Error in the Modbus communication.
22
Error in the DNP3 communication.
24
Error in the Data set(s).
25
Error in the Report control block(s).
26
Error in the GOOSE control block(s).
27
Error in the SCL configuration file or the file is
missing.
28
Too many connections in the configuration.
29
Error in the SMT connections.
30
Error in the GOOSE connections.
31
ACT error
32
Error in GOOSE message transmitting or receiving.
33
Error in AFL configuration
40
A new composition has not been
acknowledged/accepted.
50
Error in protection communication.
112
UPD Voltage Low in X115
113
UPS Communication error in X115
114
UPS Command failure in X115
115
Breaker Operation Failure, possibly due to incorrect
setting for UPD or UPD profile setting.
Section 3
Basic functions
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents