ABB RER620 Technical Manual page 53

Advanced recloser protection and control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

1MAC309294-MB F
RER620
Technical Manual
Table 30:
Internal fault indications and codes
Fault indication
Internal Fault
System error
Internal Fault
File system error
Internal Fault
Test
Internal Fault
SW watchdog error
Internal fault
Supply voltage break
Internal fault
Settings error
Internal Fault
SO-relay(s),X105
Internal Fault
SO-relay(s),X115
Internal Fault
SO-relay(s),X100
Internal Fault
SO-relay(s),X110
Internal Fault
SO-relay(s),X120
Internal Fault
SO-relay(s),X130
Internal Fault
PO-relay(s),X105
Internal Fault
PO-relay(s),X115
Internal Fault
PO-relay(s),X100
Internal Fault
PO-relay(s),X110
Internal Fault
PO-relay(s),X120
Internal Fault
PO-relay(s),X130
Internal Fault
Light sensor error
Internal Fault
Conf. error,X105
Internal Fault
Conf. error,X115
Internal Fault
Conf. error,X000
Internal Fault
Conf. error,X100
Internal Fault
Conf. error,X110
Internal Fault
Conf. error,X120
Fault code
Additional information
2
An internal system error has occurred.
7
A file system error has occurred.
8
Internal fault test activated manually by the user.
10
Watchdog reset has occurred too many times within an hour.
11
The auxiliary supply voltage has dropped to the failure level.
32
Settings error has occurred.
40
Faulty Signal Output relay(s) in card located in slot X105.
41
Faulty Signal Output relay(s) in card located in slot X115.
43
Faulty Signal Output relay(s) in card located in slot X100.
44
Faulty Signal Output relay(s) in card located in slot X110.
45
Faulty Signal Output relay(s) in card located in slot X120.
46
Faulty Signal Output relay(s) in card located in slot X130.
50
Faulty Power Output relay(s) in card located in slot X105.
51
Faulty Power Output relay(s) in card located in slot X115.
53
Faulty Power Output relay(s) in card located in slot X100.
54
Faulty Power Output relay(s) in card located in slot X110.
55
Faulty Power Output relay(s) in card located in slot X120.
56
Faulty Power Output relay(s) in card located in slot X130.
57
Faulty ARC light sensor input(s).
60
Card in slot X105 is wrong type.
61
Card in slot X115 is wrong type.
62
Card in slot X000 is wrong type.
63
Card in slot X100 is wrong type or does not belong to the
original composition.
64
Card in slot X110 is wrong type, is missing or does not belong
to the original composition.
65
Card in slot X120 is wrong type, is missing or does not belong
to the original composition.
Section 3
Basic functions
47

Hide quick links:

Advertisement

Table of Contents
loading