4.2.2 Output frequency range (Pr. 1, Pr. 2)

Pr. 1 "maximum frequency"
Pr. 2 "minimum frequency"
Used to clamp the upper and lower limits of the output frequency.
Can be used to set the upper and lower limits of motor speed.
Parameter
Factory
Number
Setting
1
60Hz
2
0Hz
<Setting>
• Use Pr. 1 to set the upper limit of the output frequency. If the frequency of the frequency command entered is
higher than the setting, the output frequency is clamped at the maximum frequency.
• Use Pr. 2 to set the lower limit of the output frequency.
Note: When the frequency setting analog signal is used to run the motor beyond 60Hz, change the Pr. 903
and Pr. 905 values. If Pr. 1 is only changed, the motor cannot run beyond 60Hz.
When the Pr. 2 setting is higher than the Pr. 13 value, note that the motor will run at the
set frequency by merely switching the start signal on, without entering the command
frequency.
Setting Range
Output frequency
0 to 120Hz
(Hz)
0 to 120Hz
Pr.1
CAUTION
62
PARAMETERS
Related parameters
Pr. 13 "starting frequency"
Pr. 903 "frequency setting voltage gain"
Pr. 905 "frequency setting current gain"
Frequency setting
Pr.2
0
5,10V
20mA, etc.
4