Application Examples
17 Application Examples
This section lists the various application examples, and
gives the parameter settings and special notes, as needed,
for each example.
NOTICE
PELV COMPLIANCE
If short circuits occur between the motor windings and
the sensor when the motor temperature is monitored via
a thermistor or KTY sensor, PELV compliance is not
achieved. Ensure PELV compliance by using reinforced or
double insulation.
17.1 Automatic Motor Adaptation (AMA)
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 17.1 AMA with T27 Connected
17
17
152
®
VLT
Parallel Drive Modules
Parameters
Function
Setting
Parameter 1-29 A
utomatic Motor
[1] Enable
Adaptation
complete
(AMA)
AMA
Parameter 5-12 T
[2]* Coast
erminal 27
inverse
Digital Input
*=Default value
Notes/comments: Set
Parameter group 1-2* Motor
Data according to motor
nameplate.
Danfoss A/S © 6/2016 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
32
D IN
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 17.2 AMA without T27 Connected
17.2 Analog Speed Reference
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
-10 - +10V
COM
39
U - I
A53
Table 17.3 Analog Speed Reference (Voltage)
Parameters
Function
Setting
Parameter 1-29 A
utomatic Motor
[1] Enable
Adaptation
complete
(AMA)
AMA
Parameter 5-12 T
[0] No
erminal 27
operation
Digital Input
*=Default value
Notes/comments: Set
Parameter group 1-2* Motor
Data according to motor
nameplate.
Parameters
Function
Setting
Parameter 6-10 T
erminal 53 Low
Voltage
0.07 V*
Parameter 6-11 T
10 V*
erminal 53 High
Voltage
Parameter 6-14 T
0 RPM
erminal 53 Low
Ref./Feedb. Value
Parameter 6-15 T
1500 RPM
erminal 53 High
Ref./Feedb. Value
*=Default value
Notes/comments:
MG37N102