GE F60 Instruction Manual
GE F60 Instruction Manual

GE F60 Instruction Manual

Ur series
Hide thumbs Also See for F60:
Table of Contents

Advertisement

Title Page
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet:
http://www.GEmultilin.com
*1601-0093-V1*
F60 Feeder Protection System
UR Series Instruction Manual
F60 Revision: 5.8x
Manual P/N: 1601-0093-V1 (GEK-113551)
Copyright © 2010 GE Multilin
E83849
LISTED
IND.CONT. EQ.
52TL
GE Multilin
832762A2.CDR
I I SO9001:2000
GE Multilin's Quality Management
System is registered to
ISO9001:2000
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE F60

  • Page 1 Title Page GE Multilin F60 Feeder Protection System UR Series Instruction Manual F60 Revision: 5.8x Manual P/N: 1601-0093-V1 (GEK-113551) Copyright © 2010 GE Multilin 832762A2.CDR E83849 I I SO9001:2000 GE Multilin LISTED 215 Anderson Avenue, Markham, Ontario IND.CONT. EQ. 52TL...
  • Page 3 GEK-113551 (revision V1) but are not included in the current F60 operations. The following functions and items are not yet available with the current version of the F60 relay: • Signal sources SRC 3 to SRC 6.
  • Page 5: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 PC REQUIREMENTS ..................1-5 1.3.2 INSTALLATION....................1-5 1.3.3 CONFIGURING THE F60 FOR SOFTWARE ACCESS ........1-7 1.3.4 USING THE QUICK CONNECT FEATURE............1-9 1.3.5 CONNECTING TO THE F60 RELAY ............... 1-15 1.4 UR HARDWARE 1.4.1...
  • Page 6 MANAGED ETHERNET SWITCH MODULE HARDWARE......3-41 3.4.3 MANAGED SWITCH LED INDICATORS ............3-42 3.4.4 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE ....3-42 3.4.5 UPLOADING F60 SWITCH MODULE FIRMWARE .........3-45 3.4.6 ETHERNET SWITCH SELF-TEST ERRORS...........3-47 4. HUMAN INTERFACES 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4.1.1 INTRODUCTION ....................4-1...
  • Page 7 DIRECT INPUTS AND OUTPUTS ..............5-223 5.8.11 TELEPROTECTION INPUTS AND OUTPUTS..........5-226 5.8.12 IEC 61850 GOOSE ANALOGS..............5-228 5.8.13 IEC 61850 GOOSE INTEGERS..............5-229 5.9 TRANSDUCER INPUTS AND OUTPUTS 5.9.1 DCMA INPUTS ....................5-230 GE Multilin F60 Feeder Protection System...
  • Page 8 MODEL INFORMATION ...................6-26 6.5.2 FIRMWARE REVISIONS..................6-26 7. COMMANDS AND 7.1 COMMANDS TARGETS 7.1.1 COMMANDS MENU ...................7-1 7.1.2 VIRTUAL INPUTS ....................7-1 7.1.3 CLEAR RECORDS .....................7-2 7.1.4 SET DATE AND TIME ..................7-2 7.1.5 RELAY MAINTENANCE ..................7-3 viii F60 Feeder Protection System GE Multilin...
  • Page 9 A. FLEXANALOG AND A.1 PARAMETER LISTS FLEXINTEGER A.1.1 FLEXANALOG ITEMS ..................A-1 A.1.2 FLEXINTEGER ITEMS ..................A-13 PARAMETERS B. MODBUS B.1 MODBUS RTU PROTOCOL COMMUNICATIONS B.1.1 INTRODUCTION....................B-1 B.1.2 PHYSICAL LAYER.....................B-1 B.1.3 DATA LINK LAYER....................B-1 B.1.4 CRC-16 ALGORITHM..................B-2 GE Multilin F60 Feeder Protection System...
  • Page 10 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP......C-20 C.6 ACSI CONFORMANCE C.6.1 ACSI BASIC CONFORMANCE STATEMENT ..........C-22 C.6.2 ACSI MODELS CONFORMANCE STATEMENT ..........C-22 C.6.3 ACSI SERVICES CONFORMANCE STATEMENT ......... C-23 C.7 LOGICAL NODES C.7.1 LOGICAL NODES TABLE ................C-26 F60 Feeder Protection System GE Multilin...
  • Page 11 COUNTERS .....................E-10 E.2.4 ANALOG INPUTS ....................E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY ..................F-1 F.1.2 CHANGES TO THE F60 MANUAL ..............F-2 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-8 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY ................F-10 INDEX...
  • Page 12 TABLE OF CONTENTS F60 Feeder Protection System GE Multilin...
  • Page 13: Getting Started

    • GE EnerVista CD (includes the EnerVista UR Setup software and manuals in PDF format). • Mounting screws. For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin website at http://www.GEmultilin.com. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Multilin immediately.
  • Page 14: Ur Overview

    This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. F60 Feeder Protection System...
  • Page 15: Hardware Architecture

    (dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. GE Multilin F60 Feeder Protection System...
  • Page 16: Software Architecture

    Employing OOD/OOP in the software architecture of the F60 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functionality classes.
  • Page 17: Enervista Ur Setup Software

    Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color) • RS232 and/or Ethernet port for communications to the relay The following qualified modems have been tested to be compliant with the F60 and the EnerVista UR Setup software. • US Robotics external 56K FaxModem 5686 •...
  • Page 18 Install Software window as shown below. Select the “Web” option to ensure the most recent software release, or select “CD” if you do not have a web connection, then click the Add Now button to list software items for the F60.
  • Page 19: Configuring The F60 For Software Access

    OVERVIEW The user can connect remotely to the F60 through the rear RS485 port or the rear Ethernet port with a PC running the EnerVista UR Setup software. The F60 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 20 SERIAL PORTS 10. Click the Read Order Code button to connect to the F60 device and upload the order code. If an communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
  • Page 21: Using The Quick Connect Feature

    MODBUS PROTOCOL 11. Click the Read Order Code button to connect to the F60 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.
  • Page 22 F60. This ensures that configuration of the EnerVista UR Setup software matches the F60 model number. b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the F60 from a laptop through Ethernet, first assign an IP address to the relay from the front panel keyboard.
  • Page 23 Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Click on the “Use the following IP address” box. GE Multilin F60 Feeder Protection System 1-11...
  • Page 24 1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED Enter an IP address with the first three numbers the same as the IP address of the F60 relay and the last number dif- ferent (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the F60 (in this example, 255.0.0.0).
  • Page 25 If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the F60 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details.
  • Page 26 Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica- tions to the F60. This ensures that configuration of the EnerVista UR Setup software matches the F60 model number. When direct communications with the F60 via Ethernet is complete, make the following changes: From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con- nections window.
  • Page 27: Connecting To The F60 Relay

    The EnerVista UR Setup software has several new quick action buttons that provide users with instant access to several functions that are often performed when using F60 relays. From the online window, users can select which relay to interro- gate from a pull-down window, then click on the button for the action they wish to perform. The following quick action func- tions are available: •...
  • Page 28: Ur Hardware

    Figure 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the F60 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the F60 rear communications port.
  • Page 29: Using The Relay

    LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed GE Multilin F60 Feeder Protection System 1-17...
  • Page 30: Relay Passwords

    Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level passwords. NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. 1-18 F60 Feeder Protection System GE Multilin...
  • Page 31: Commissioning

    1.5 USING THE RELAY 1.5.7 COMMISSIONING The F60 requires a minimum amount of maintenance when it is commissioned into service. Since the F60 is a microproces- sor-based relay, its characteristics do not change over time. As such, no further functional tests are required.
  • Page 32 1.5 USING THE RELAY 1 GETTING STARTED 1-20 F60 Feeder Protection System GE Multilin...
  • Page 33: Product Description

    Another option provides two 10Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus TCP, and TFTP protocols, and allows access to the relay via any standard web browser (F60 web pages). The IEC 60870- 5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time.
  • Page 34: Ordering

    2.1.2 ORDERING a) OVERVIEW The F60 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod- ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
  • Page 35 2.1 INTRODUCTION b) ORDER CODES WITH TRADITIONAL CTS AND VTS The order codes for the horizontal mount units with traditional CTs and VTs are shown below. Table 2–3: F60 ORDER CODES (HORIZONTAL UNITS) * - F - W/X Full Size Horizontal Mount...
  • Page 36 2 PRODUCT DESCRIPTION The order codes for the reduced size vertical mount units with traditional CTs and VTs are shown below. Table 2–4: F60 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)
  • Page 37 2.1 INTRODUCTION c) ORDER CODES WITH PROCESS BUS MODULES The order codes for the horizontal mount units with the process bus module are shown below. Table 2–5: F60 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X...
  • Page 38: Replacement Modules

    Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or face- plate, please provide the serial number of your existing unit. Not all replacement modules may be applicable to the F60 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 39 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs GE Multilin F60 Feeder Protection System...
  • Page 40 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs F60 Feeder Protection System GE Multilin...
  • Page 41: Specifications

    ±1.5% of reading > 2.0 × CT rating Inverse; IEC (and BS) A/B/C and Short Curve shapes: IEEE Moderately/Very/Extremely Inverse; GE IAC Inverse, Short/Very/ Inverse; IEC (and BS) A/B/C and Short Extremely Inverse; I t; FlexCurves™ Inverse; GE IAC Inverse, Short/Very/ (programmable);...
  • Page 42 40 to 90° in steps of 1, independent for Level accuracy: ±0.5% of reading from 10 to 208 V forward and reverse Curve shapes: GE IAV Inverse, Definite Time Angle accuracy: ±2° Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01 0.00 to 250.00 Ω...
  • Page 43 ¼ cycle after breaker opens Availability: one per CT/VT module (not including 8Z modules) Pickup level: 0.1 to 2.00 pu in steps of 0.01 Reset delay: 0.000 to 65.535 s in steps of 0.001 GE Multilin F60 Feeder Protection System 2-11...
  • Page 44: User-Programmable Elements

    LEDs on, one LED at a time off for 1 s mable condition Number of tests: 3, interruptible at any time Duration of full test: approximately 3 minutes Test sequence 1: all LEDs on 2-12 F60 Feeder Protection System GE Multilin...
  • Page 45: Monitoring

    Storage capacity: (NN is dependent on memory) 1-second rate: 01 channel for NN days 16 channels for NN days ↓ 60-minute rate: 01 channel for NN days 16 channels for NN days GE Multilin F60 Feeder Protection System 2-13...
  • Page 46: Metering

    1 to 275 V Voltage withstand: continuous at 260 V to neutral Current withstand: 20 ms at 250 times rated 1 min./hr at 420 V to neutral 1 sec. at 100 times rated 2-14 F60 Feeder Protection System GE Multilin...
  • Page 47: Power Supply

    100 000 A RMS symmetrical Minimum AC voltage: 88 V at 25 to 100 Hz 10 000 A Maximum AC voltage: 265 V at 25 to 100 Hz Voltage loss hold-up: 200 ms duration at nominal GE Multilin F60 Feeder Protection System 2-15...
  • Page 48: Outputs

    Note: values for 24 V and 48 V are the same due to a 0.001 required 95% voltage drop across the load impedance. Operate time: < 0.6 ms Internal Limiting Resistor: 100 Ω, 2 W 2-16 F60 Feeder Protection System GE Multilin...
  • Page 49: Communications

    MAXIMUM 10 MBPS ETHERNET SEGMENT LENGTHS 100Base-TX (CAT 5 UTP):100 m (328 ft.) Unshielded twisted pair: 100 m (328 ft.) Shielded twisted pair: 150 m (492 ft.) Shielded twisted pair: 150 m (492 ft.) GE Multilin F60 Feeder Protection System 2-17...
  • Page 50: Inter-Relay Communications

    Operating temperature: –40 to 60°C; the LCD contrast may be Pollution degree: impaired at temperatures less than – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6days). 2-18 F60 Feeder Protection System GE Multilin...
  • Page 51: Type Tests

    20 V/m, 80 MHz to 1 GHz Safety UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2.2.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin F60 Feeder Protection System 2-19...
  • Page 52: Approvals

    Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used. Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration of electrolytic capacitors. NOTE 2-20 F60 Feeder Protection System GE Multilin...
  • Page 53 2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS GE Multilin F60 Feeder Protection System 2-21...
  • Page 54 2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2-22 F60 Feeder Protection System GE Multilin...
  • Page 55: Hardware

    HORIZONTAL UNITS The F60 Feeder Protection System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains addi- tional user-programmable pushbuttons and LED indicators.
  • Page 56 VERTICAL UNITS The F60 Feeder Protection System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains addi- tional user-programmable pushbuttons and LED indicators.
  • Page 57 RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. 11.015” 7.482” 1.329” 13.560” 15.000” 14.025” 4.000” 9.780” 843809A1.CDR Figure 3–4: F60 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin F60 Feeder Protection System...
  • Page 58 UR SERIES UR SERIES Figure 3–5: F60 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For details on side mounting F60 devices with the enhanced front panel, refer to the following documents available online from the GE Multilin website. • GEK-113180: UR-series UR-V side-mounting front panel assembly instructions.
  • Page 59 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: F60 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin F60 Feeder Protection System...
  • Page 60: Module Withdrawal And Insertion

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the F60. F60 Feeder Protection System...
  • Page 61 When the clips have locked into position, the module will be fully inserted. All CPU modules except the 9E are equipped with 10/100Base-T or 100Base-F Ethernet connectors. These con- nectors must be individually disconnected from the module before it can be removed from the chassis. NOTE GE Multilin F60 Feeder Protection System...
  • Page 62: Rear Terminal Layout

    3.1 DESCRIPTION 3 HARDWARE The 4.0x release of the F60 relay includes new hardware modules.The new CPU modules are specified with codes 9E and higher. The new CT/VT modules are specified with the codes 8F and higher. NOTE The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old CPUs.
  • Page 63 3 HARDWARE 3.1 DESCRIPTION Figure 3–11: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin F60 Feeder Protection System...
  • Page 64: Wiring

    GROUND BUS MODULE ARRANGEMENT MODULES MUST BE GROUNDED IF Inputs/ Inputs/ Inputs/ Inputs/ TERMINAL IS outputs outputs outputs outputs Inputs/ CT/VT Power PROVIDED outputs Supply (Rear view) * Optional Figure 3–12: TYPICAL WIRING DIAGRAM 3-10 F60 Feeder Protection System GE Multilin...
  • Page 65 Digital Digital MODULES MUST BE inputs/ inputs/ inputs/ inputs/ Power GROUNDED IF outputs outputs outputs outputs CT/VT Supply TERMINAL IS PROVIDED (Rear view) * Optional Figure 3–13: TYPICAL WIRING DIAGRAM WITH HIGH-IMPEDANCE DETECTION GE Multilin F60 Feeder Protection System 3-11...
  • Page 66: Dielectric Strength

    (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize. For high reliability systems, the F60 has a redundant option in which two F60 power supplies are placed in parallel on the bus.
  • Page 67: Ct And Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair cabling on the zero-sequence CT is recommended. GE Multilin F60 Feeder Protection System 3-13...
  • Page 68 8F and 8G modules (4 CTs and 4 VTs) Current inputs 8H and 8J modules (8 CTs) Current inputs Not used 8Z module (used for high-impedance fault detection) 842769A1.CDR Figure 3–16: CT/VT MODULE WIRING 3-14 F60 Feeder Protection System GE Multilin...
  • Page 69: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The F60 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 70: Contact Inputs And Outputs

    The terminal configuration for contact inputs is different for the two applications. The contact inputs are grouped with a common return. The F60 has two versions of grouping: four inputs per common return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
  • Page 71 ~6a, ~6c 2 Inputs Form-A ~7a, ~7c 2 Inputs Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs GE Multilin F60 Feeder Protection System 3-17...
  • Page 72 Not Used ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used 3-18 F60 Feeder Protection System GE Multilin...
  • Page 73 3 HARDWARE 3.2 WIRING 842762A2.CDR Figure 3–19: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) GE Multilin F60 Feeder Protection System 3-19...
  • Page 74 COMMON SURGE 842763A2.CDR Figure 3–20: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) CORRECT POLARITY MUST BE OBSERVED FOR ALL CONTACT INPUT AND SOLID STATE OUTPUT CON- NECTIONS FOR PROPER FUNCTIONALITY. CAUTION 3-20 F60 Feeder Protection System GE Multilin...
  • Page 75 There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. NOTE GE Multilin F60 Feeder Protection System 3-21...
  • Page 76 CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–23: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope. NOTE 3-22 F60 Feeder Protection System GE Multilin...
  • Page 77: Transducer Inputs/Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–24: TRANSDUCER INPUT/OUTPUT MODULE WIRING GE Multilin F60 Feeder Protection System 3-23...
  • Page 78: Rs232 Faceplate Port

    3.2.8 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the F60 faceplate for programming with a personal computer. All that is required to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 79 For this reason, surge protection devices are internally provided at both communication ports. An iso- lated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum reliability, all equipment should have similar transient protection devices installed. GE Multilin F60 Feeder Protection System 3-25...
  • Page 80 For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When splicing optical fibers, the diameter and numerical aperture of each fiber must be the same. In order to engage or disengage the ST type connec- tor, only a quarter turn of the coupling is required. 3-26 F60 Feeder Protection System GE Multilin...
  • Page 81: Irig-B

    UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down. Figure 3–29: IRIG-B REPEATER Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping. NOTE GE Multilin F60 Feeder Protection System 3-27...
  • Page 82: Direct Input/Output Communications

    3.3.1 DESCRIPTION The F60 direct inputs and outputs feature makes use of the type 7 series of communications modules. These modules are also used by the L90 Line Differential Relay for inter-relay communications. The direct input and output feature uses the communications channels provided by these modules to exchange digital state information between relays.
  • Page 83 These modules are listed in the following table. All fiber modules use ST type connectors. Not all the direct input and output communications modules may be applicable to the F60 relay. Only the modules specified in the order codes are available as direct input and output communications modules.
  • Page 84: Fiber: Led And Eled Transmitters

    2 Channels Figure 3–34: LASER FIBER MODULES When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maxi- mum optical input power to the receiver. WARNING 3-30 F60 Feeder Protection System GE Multilin...
  • Page 85: Interface

    Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. GE Multilin F60 Feeder Protection System 3-31...
  • Page 86 For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). 3-32 F60 Feeder Protection System GE Multilin...
  • Page 87 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–39: G.703 DUAL LOOPBACK MODE GE Multilin F60 Feeder Protection System 3-33...
  • Page 88: Rs422 Interface

    1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. 3-34 F60 Feeder Protection System GE Multilin...
  • Page 89 Figure 3–42: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION Data module 1 provides timing to the F60 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they may vary depending on the manufacturer.
  • Page 90: Rs422 And Fiber Interface

    When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maxi- mum optical input power to the receiver. WARNING Shield Tx – G.703 Rx – channel 1 Tx + Rx + Surge Fiber channel 2 842778A1.CDR Figure 3–45: G.703 AND FIBER INTERFACE CONNECTION 3-36 F60 Feeder Protection System GE Multilin...
  • Page 91: Ieee C37.94 Interface

    IEEE C37.94 standard, as shown below. The UR-series C37.94 communication module has six (6) switches that are used to set the clock configuration. The func- tions of these control switches is shown below. 842753A1.CDR GE Multilin F60 Feeder Protection System 3-37...
  • Page 92 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. Figure 3–46: IEEE C37.94 TIMING SELECTION SWITCH SETTING 3-38 F60 Feeder Protection System GE Multilin...
  • Page 93: C37.94Sm Interface

    For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured. GE Multilin F60 Feeder Protection System 3-39...
  • Page 94 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. Figure 3–47: C37.94SM TIMING SELECTION SWITCH SETTING 3-40 F60 Feeder Protection System GE Multilin...
  • Page 95: Managed Ethernet Switch Modules

    The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU mod- ules with revisions 5.5x and higher. The modules communicate to the F60 through an internal Ethernet port (referred to as the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST 100Base-FX ports.
  • Page 96: Managed Switch Led Indicators

    Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net- work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified. Do not connect to network while configuring the switch module. CAUTION 3-42 F60 Feeder Protection System GE Multilin...
  • Page 97 SAVING THE ETHERNET SWITCH SETTINGS TO A SETTINGS FILE The F60 allows the settings information for the Ethernet switch module to be saved locally as a settings file. This file con- tains the advanced configuration details for the switch not contained within the standard F60 settings file.
  • Page 98 Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open. The settings file will be transferred to the Ethernet switch and the settings uploaded to the device. 3-44 F60 Feeder Protection System GE Multilin...
  • Page 99: Uploading F60 Switch Module Firmware

    NOTE b) SELECTING THE PROPER SWITCH FIRMWARE VERSION The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to determine the version of firmware currently installed on your switch Log into the switch using the EnerVista web interface.
  • Page 100 Select the firmware file to be loaded on to the Switch, and select the Open option. The following window will pop up, indicating that the firmware file transfer is in progress. If the firmware load was successful, the following window will appear: Note 3-46 F60 Feeder Protection System GE Multilin...
  • Page 101: Ethernet Switch Self-Test Errors

    No setting required; the F60 EQUIPMENT The F60 has not detected the The F60 failed to see the switch module will read the state of a general MISMATCH: Card XXX presence of the Ethernet on power-up, because switch won’t...
  • Page 102 3.4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3-48 F60 Feeder Protection System GE Multilin...
  • Page 103: Human Interfaces

    To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerV- ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the F60 section in Chapter 1 for details.
  • Page 104 Site List window will automatically be sent to the on-line communicating device. g) FIRMWARE UPGRADES The firmware of a F60 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 105: Enervista Ur Setup Main Window

    4.1.5 SETTINGS TEMPLATES Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An exam- ple of this is a substation that has ten similar feeders protected by ten UR-series F60 relays. GE Multilin F60 Feeder Protection System...
  • Page 106 (settings file templates) and online devices (online settings templates). The func- tionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the F60 firmware are at ver- sions 5.40 or higher.
  • Page 107 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin F60 Feeder Protection System...
  • Page 108 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND F60 Feeder Protection System GE Multilin...
  • Page 109 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin F60 Feeder Protection System...
  • Page 110: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. F60 Feeder Protection System GE Multilin...
  • Page 111 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin F60 Feeder Protection System...
  • Page 112: Settings File Traceability

    When a settings file is transfered to a F60 device, the date, time, and serial number of the F60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the F60 actual values at any later date to determine if security has been compromised.
  • Page 113 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE The transfer date of a setting file written to a F60 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 114 ONLINE DEVICE TRACEABILITY INFORMATION The F60 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 115: Faceplate Interface

    LED panel 1 LED panel 2 LED panel 3 Display Front panel RS232 port Small user-programmable User-programmable Keypad (control) pushbuttons 1 to 7 pushbuttons 1 to 12 827801A7.CDR Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin F60 Feeder Protection System 4-13...
  • Page 116: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. 4-14 F60 Feeder Protection System GE Multilin...
  • Page 117 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every F60, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 118 LEDs on these panels. USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LEDS 842782A1.CDR Figure 4–20: LED PANELS 2 AND 3 (INDEX TEMPLATE) DEFAULT LABELS FOR LED PANEL 2: The default labels are intended to represent: 4-16 F60 Feeder Protection System GE Multilin...
  • Page 119: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational. • The F60 settings have been saved to a settings file. • The F60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http:// www.GEindustrial.com/multilin/support/ur and printed.
  • Page 120 Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the F60 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 121 4.2 FACEPLATE INTERFACE Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the F60 enhanced front panel and insert the custom labels. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.
  • Page 122 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the F60 enhanced front panel and insert the custom labels.
  • Page 123 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. GE Multilin F60 Feeder Protection System 4-21...
  • Page 124 The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014). Push in...
  • Page 125: Display

    4.2.5 BREAKER CONTROL a) INTRODUCTION The F60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic™...
  • Page 126: Keypad

    Each press of the MENU key advances through the following main heading pages: • Actual values. • Settings. • Commands. • Targets. • User displays (when enabled). 4-24 F60 Feeder Protection System GE Multilin...
  • Page 127 FLASH MESSAGE Display Properties. TIME: 1.0 s To view the remaining settings associated with the Display Properties subheader, DEFAULT MESSAGE repeatedly press the MESSAGE DOWN key. The last message appears as shown. INTENSITY: 25% GE Multilin F60 Feeder Protection System 4-25...
  • Page 128: Changing Settings

    ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length, but user-defined in character. They may be comprised of upper case letters, lower case letters, numerals, and a selection of special characters. 4-26 F60 Feeder Protection System GE Multilin...
  • Page 129: Installation

    When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the In Service LED will turn on. e) ENTERING INITIAL PASSWORDS The F60 supports password entry from a local or remote connection. GE Multilin F60 Feeder Protection System...
  • Page 130 When an incorrect command or setting password has been entered via the faceplate interface three times within a 3-minute time span, the FlexLogic™ operand will be set to “On” and the F60 will not allow settings or com- LOCAL ACCESS DENIED...
  • Page 131 FlexLogic™ operand will be set to “On” and REMOTE ACCESS DENIED the F60 will not allow Settings or Command access via the any external communications interface for the next ten minutes. FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.
  • Page 132 4.2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4-30 F60 Feeder Protection System GE Multilin...
  • Page 133: Overview

    See page 5-57. PARAMETERS USER-DEFINABLE See page 5-58. DISPLAYS DIRECT I/O See page 5-60. TELEPROTECTION See page 5-68. INSTALLATION See page 5-68. SETTINGS AC INPUTS See page 5-71. SYSTEM SETUP POWER SYSTEM See page 5-72. GE Multilin F60 Feeder Protection System...
  • Page 134: Signal Sources

    See page 5-168. SELECTOR SWITCH See page 5-169. UNDERFREQUENCY See page 5-175. OVERFREQUENCY See page 5-176. FREQUENCY RATE See page 5-177. OF CHANGE SYNCHROCHECK See page 5-179. AUTORECLOSE See page 5-183. DIGITAL ELEMENTS See page 5-189. F60 Feeder Protection System GE Multilin...
  • Page 135 See page 5-226. IEC 61850 See page 5-228. GOOSE ANALOGS IEC 61850 See page 5-229. GOOSE UINTEGERS SETTINGS DCMA INPUTS See page 5-230. TRANSDUCER I/O RTD INPUTS See page 5-231. DCMA OUTPUTS See page 5-233. GE Multilin F60 Feeder Protection System...
  • Page 136: Introduction To Elements

    FUNCTION setting: This setting programs the element to be operational when selected as “Enabled”. The factory default is “Disabled”. Once programmed to “Enabled”, any element associated with the function becomes active and all options become available. • NAME setting: This setting is used to uniquely identify the element. F60 Feeder Protection System GE Multilin...
  • Page 137: Introduction To Ac Sources

    BACKGROUND The F60 may be used on systems with breaker-and-a-half or ring bus configurations. In these applications, each of the two three-phase sets of individual phase currents (one associated with each breaker) can be used as an input to a breaker fail- ure element.
  • Page 138 INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 < bank 1 > < bank 3 > < bank 5 > < bank 2 > < bank 4 > < bank 6 > F60 Feeder Protection System GE Multilin...
  • Page 139 CTs on each of two breakers is required to measure the winding current flow. GE Multilin F60 Feeder Protection System...
  • Page 140: Product Setup

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the F60, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 141 If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both com- mands and settings. NOTE GE Multilin F60 Feeder Protection System...
  • Page 142 Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min The following access supervision settings are available. 5-10 F60 Feeder Protection System GE Multilin...
  • Page 143 INVALID ATTEMPS BEFORE LOCKOUT The F60 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic™ operand is UNAUTHORIZED ACCESS asserted.
  • Page 144: Display Properties

    TIME: 30 min Range: 0.002 to 0.020 pu in steps of 0.001 CURRENT CUT-OFF MESSAGE LEVEL: 0.020 pu Range: 0.1 to 1.0 V secondary in steps of 0.1 VOLTAGE CUT-OFF MESSAGE LEVEL: 1.0 V 5-12 F60 Feeder Protection System GE Multilin...
  • Page 145 Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The F60 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 146: Clear Relay Records

    Selected records can be cleared from user-programmable conditions with FlexLogic™ operands. Assigning user-program- mable pushbuttons to clear specific records are typical applications for these commands. Since the F60 responds to rising edges of the configured FlexLogic™ operands, they must be asserted for at least 50 ms to take effect.
  • Page 147: Communications

    HTTP PROTOCOL TFTP PROTOCOL See page 5–33. MESSAGE IEC 60870-5-104 See page 5–34. MESSAGE PROTOCOL SNTP PROTOCOL See page 5–34. MESSAGE EGD PROTOCOL See page 5–35. MESSAGE ETHERNET SWITCH See page 5–36. MESSAGE GE Multilin F60 Feeder Protection System 5-15...
  • Page 148 0 ms The F60 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or RS485 port.
  • Page 149 MODBUS SLAVE ADDRESS grammed. For the RS485 ports each F60 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur.
  • Page 150 TIMEOUT: 120 s The F60 supports the Distributed Network Protocol (DNP) version 3.0. The F60 can be used as a DNP slave device con- nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the F60 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the F60 at one time.
  • Page 151 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the F60 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 152 (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP master can operate a single point for both trip and close, or raise and lower, operations. The F60 can be configured to sup- port paired control points, with each paired control point operating two virtual inputs.
  • Page 153 IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored. NOTE Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the F60 is restarted. NOTE g) IEC 61850 PROTOCOL...
  • Page 154 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In F60 releases previous to 5.0x, this name string was repre- sented by the setting.
  • Page 155 DESTINATION MAC address; the least significant bit of the first byte must be set. In F60 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the F60) and setting the multicast bit.
  • Page 156 The F60 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 157 Configure the data. This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status value, its associated quality flags, and a floating point analog value. GE Multilin F60 Feeder Protection System 5-25...
  • Page 158 MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The F60 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the...
  • Page 159 IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog™ value in a FlexElement™ or in other settings. The F60 must be rebooted (control power removed and re-applied) before these settings take effect.
  • Page 160 CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta- tus values in the F60. Clients will still be able to connect to the server (F60 relay), but most data values will not be updated.
  • Page 161 (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the F60 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below.
  • Page 162 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the F60 virtual inputs.
  • Page 163 GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point. It is intended that clients use GGIO5 to access generic integer values from the F60. Additional settings are provided to allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the GGIO5 integer inputs.
  • Page 164 Changes to the report configuration will not take effect until the F60 is restarted. Please disconnect any IEC 61850 client connection to the F60 prior to making setting changes to the report config- uration. Disconnecting the rear Ethernet connection from the F60 will disconnect the IEC 61850 client connection.
  • Page 165 NUMBER: The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the F60 over a network. The F60 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the F60 contains a list and description of all available files (event records, oscillography, etc.).
  • Page 166 THRESHOLD: 30000 The F60 supports the IEC 60870-5-104 protocol. The F60 can be used as an IEC 60870-5-104 slave device connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the F60 maintains two sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the F60 at one time.
  • Page 167 F60 clock is closely synchronized with the SNTP/NTP server. It may take up to two minutes for the F60 to signal an SNTP self-test error if the server is offline.
  • Page 168 5.2 PRODUCT SETUP 5 Z SETTINGS Fast exchanges (50 to 1000 ms) are generally used in control schemes. The F60 has one fast exchange (Exchange 1) and two slow exchanges (Exchanges 2 and 3). The settings menu for the slow EGD exchanges is shown below:...
  • Page 169: Modbus User Map

    5.2 PRODUCT SETUP These settings appear only if the F60 is ordered with an Ethernet switch module (type 2S or 2T). The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings are used in advanced network configurations.
  • Page 170: Real Time Clock

    SNTP, the offset is used to determine the local time for the F60 clock, since SNTP provides UTC time. The daylight savings time (DST) settings can be used to allow the F60 clock can follow the DST rules of the local time zone.
  • Page 171: Fault Reports

    MESSAGE Z0 ANGLE: 75° The F60 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as the characteristics of the line or feeder, are entered in this menu. The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in the FaultReport.txt file includes:...
  • Page 172 It should be kept in mind that grounding points in vicinity of the installation impact the system zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, etc.). 5-40 F60 Feeder Protection System GE Multilin...
  • Page 173: Oscillography

    Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. GE Multilin F60 Feeder Protection System 5-41...
  • Page 174 IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. 5-42 F60 Feeder Protection System GE Multilin...
  • Page 175: Data Logger

    The relay automatically partitions the available memory between the channels in use. Exam- ple storage capacities for a system frequency of 60 Hz are shown in the following table. GE Multilin F60 Feeder Protection System 5-43...
  • Page 176 – entering this number via the relay keypad will cause the corresponding parameter to be displayed. • DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not selected to “Off” without over-writing old data. 5-44 F60 Feeder Protection System GE Multilin...
  • Page 177: Demand

    Start Demand Interval logic input pulses. Each new value of demand becomes available at the end of each pulse. Assign a FlexLogic™ operand to the setting to program the input for the new DEMAND TRIGGER demand interval pulses. GE Multilin F60 Feeder Protection System 5-45...
  • Page 178: User-Programmable Leds

    LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting from relay response during testing. The reset pushbutton will not clear any targets when the LED Test is in progress. 5-46 F60 Feeder Protection System GE Multilin...
  • Page 179: User-Programmable Pushbuttons

    Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This is to be performed via user-programmable pushbutton 1. GE Multilin F60 Feeder Protection System 5-47...
  • Page 180 “Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com- munications channel, or from any programmed operand, even if the LED operand state de-asserts. 5-48 F60 Feeder Protection System GE Multilin...
  • Page 181 Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. To enable the Ethernet switch failure function, ensure that the is “Enabled” in this ETHERNET SWITCH FAIL FUNCTION menu. NOTE GE Multilin F60 Feeder Protection System 5-49...
  • Page 182 The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–5: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the F60 is ordered with the twelve user- programmable pushbutton option. STATUS EVENT CAUSE...
  • Page 183 SYSTEM SETUP/ BREAKERS/BREAKER 1/ BREAKER 1 PUSHBUTTON CONTROL Enabled=1 TIMER FLEXLOGIC OPERAND SYSTEM SETUP/ BREAKERS/BREAKER 2/ CONTROL PUSHBTN 1 ON 100 msec BREAKER 2 PUSHBUTTON CONTROL 842010A2.CDR Enabled=1 Figure 5–7: CONTROL PUSHBUTTON LOGIC GE Multilin F60 Feeder Protection System 5-51...
  • Page 184 FlexLogic™ equations, protection elements, and control elements. Typical applications include breaker control, autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of password protection. The user-configurable pushbuttons for the enhanced faceplate are shown below. 5-52 F60 Feeder Protection System GE Multilin...
  • Page 185 The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push- button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari- ous system disturbances that may cause transient assertion of the operating signals. NOTE GE Multilin F60 Feeder Protection System 5-53...
  • Page 186 PUSHBTN 1 SET PUSHBTN 1 RESET • PUSHBTN 1 LOCAL: This setting assigns the FlexLogic™ operand serving to inhibit pushbutton operation from the front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset. 5-54 F60 Feeder Protection System GE Multilin...
  • Page 187 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. GE Multilin F60 Feeder Protection System 5-55...
  • Page 188 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–10: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) 5-56 F60 Feeder Protection System GE Multilin...
  • Page 189: Flex State Parameters

    16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which are of interest to the user are available in a minimum number of Modbus registers. GE Multilin F60 Feeder Protection System 5-57...
  • Page 190 INVOKE AND SCROLL play, not at the first user-defined display. The pulses must last for at least 250 ms to take effect. INVOKE AND SCROLL 5-58 F60 Feeder Protection System GE Multilin...
  • Page 191 4 seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option to remove the display from the user display list. Use the MENU key again to exit the user displays menu. GE Multilin F60 Feeder Protection System 5-59...
  • Page 192 On type 7 cards that sup- port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output 5-60 F60 Feeder Protection System GE Multilin...
  • Page 193 Delivery time for direct input and output messages is approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’. GE Multilin F60 Feeder Protection System 5-61...
  • Page 194 The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged. 5-62 F60 Feeder Protection System GE Multilin...
  • Page 195 UR IED 1 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–13: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. GE Multilin F60 Feeder Protection System 5-63...
  • Page 196 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. 5-64 F60 Feeder Protection System GE Multilin...
  • Page 197 Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below. GE Multilin F60 Feeder Protection System 5-65...
  • Page 198 EVENTS: Disabled The F60 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 199 MESSAGE EVENTS: Disabled The F60 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre- turned messages.
  • Page 200 TERMINAL 1 ID NUMBER 5.2.19 INSTALLATION PATH: SETTINGS PRODUCT SETUP INSTALLATION Range: Not Programmed, Programmed INSTALLATION RELAY SETTINGS: Not Programmed Range: up to 20 alphanumeric characters RELAY NAME: MESSAGE Relay-1 5-68 F60 Feeder Protection System GE Multilin...
  • Page 201 This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the IEC 61850 protocol. GE Multilin F60 Feeder Protection System 5-69...
  • Page 202 Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the F60 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 203 CTs will be adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1 cur- rents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). GE Multilin F60 Feeder Protection System 5-71...
  • Page 204 Range: 25 to 60 Hz in steps of 1 POWER SYSTEM NOMINAL FREQUENCY: 60 Hz Range: ABC, ACB PHASE ROTATION: MESSAGE Range: SRC 1, SRC 2 FREQUENCY AND PHASE MESSAGE REFERENCE: SRC 1 Range: Disabled, Enabled FREQUENCY TRACKING: MESSAGE Enabled 5-72 F60 Feeder Protection System GE Multilin...
  • Page 205 FREQUENCY TRACKING cial variable-frequency applications. NOTE The frequency tracking feature will function only when the F60 is in the “Programmed” mode. If the F60 is “Not Pro- grammed”, then metering values will be available but may exhibit significant errors. NOTE 5.4.3 SIGNAL SOURCES...
  • Page 206 CTs will be summed together. When the F60 is equipped with a type 8Z CT/VT module for high impedance fault detection, the CT bank of this module should not be assigned to a source which will be used by any conventional protection element. The type 8Z module CT bank is used solely by the high impedance fault detection algorithm.
  • Page 207 CT/VT inputs that are used to provide the data. DSP Bank Source 1 Source 2 Amps Amps Source 3 51BF-1 51BF-2 Volts Amps Amps Volts Source 4 UR Relay Figure 5–20: EXAMPLE USE OF SOURCES GE Multilin F60 Feeder Protection System 5-75...
  • Page 208: Breakers

    Range: 0.000 to 1 000 000.000 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic™ operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled 5-76 F60 Feeder Protection System GE Multilin...
  • Page 209 1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the F60. The follow- ing settings are available for each breaker control element.
  • Page 210 Off = 0 827061AS.CDR Figure 5–21: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the F60 is in “Programmed” mode and not in the local control mode. NOTE 5-78 F60 Feeder Protection System...
  • Page 211 FLEXLOGIC OPERANDS BREAKER 1 ANY P OPEN BREAKER 1 1P OPEN BREAKER 1 OOS SETTING BREAKER 1 OUT OF SV = Off 842025A1.CDR Figure 5–22: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) GE Multilin F60 Feeder Protection System 5-79...
  • Page 212: Disconnect Switches

    For greater security in determination of the switch pole position, both the 52/a and 52/b auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches depends on the number of the CT/VT modules ordered with the F60. •...
  • Page 213 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the F60 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin...
  • Page 214 SWITCH Φ BAD ST SWITCH 1 C Φ CLSD SETTING SWITCH 1 C Φ OPEN SWITCH 1 ΦC OPENED SWITCH 1 C Φ INTERM = Off 842026A3.CDR Figure 5–23: DISCONNECT SWITCH SCHEME LOGIC 5-82 F60 Feeder Protection System GE Multilin...
  • Page 215: Flexcurves

    1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin- NOTE ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu. GE Multilin F60 Feeder Protection System 5-83...
  • Page 216 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE 5-84 F60 Feeder Protection System GE Multilin...
  • Page 217 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the F60 are displayed in the following graphs. GE Multilin F60 Feeder Protection System...
  • Page 218 CURRENT (multiple of pickup) 842723A1.CDR Figure 5–27: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–28: RECLOSER CURVES GE113, GE120, GE138 AND GE142 5-86 F60 Feeder Protection System GE Multilin...
  • Page 219 Figure 5–29: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–30: RECLOSER CURVES GE131, GE141, GE152, AND GE200 GE Multilin F60 Feeder Protection System 5-87...
  • Page 220 Figure 5–31: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–32: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 5-88 F60 Feeder Protection System GE Multilin...
  • Page 221 Figure 5–33: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–34: RECLOSER CURVES GE119, GE135, AND GE202 GE Multilin F60 Feeder Protection System 5-89...
  • Page 222: Flexlogic

    Figure 5–35: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the F60 are represented by flags (or FlexLogic™ operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic™...
  • Page 223 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–7: F60 FLEXLOGIC™ OPERAND TYPES OPERAND TYPE STATE...
  • Page 224 5.5 FLEXLOGIC™ 5 Z SETTINGS The operands available for this relay are listed alphabetically by types in the following table. Table 5–8: F60 FLEXLOGIC™ OPERANDS (Sheet 1 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION CONTROL CONTROL PUSHBTN 1 ON...
  • Page 225 5 Z SETTINGS 5.5 FLEXLOGIC™ Table 5–8: F60 FLEXLOGIC™ OPERANDS (Sheet 2 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT BRK RESTRIKE 1 OP Breaker restrike detected in any phase of the breaker control 1 element. Breaker restrike BRK RESTRIKE 1 OP A Breaker restrike detected in phase A of the breaker control 1 element.
  • Page 226 5.5 FLEXLOGIC™ 5 Z SETTINGS Table 5–8: F60 FLEXLOGIC™ OPERANDS (Sheet 3 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: GROUND IOC1 PKP Ground instantaneous overcurrent 1 has picked up Ground GROUND IOC1 OP Ground instantaneous overcurrent 1 has operated...
  • Page 227 5 Z SETTINGS 5.5 FLEXLOGIC™ Table 5–8: F60 FLEXLOGIC™ OPERANDS (Sheet 4 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: NEUTRAL IOC1 PKP Neutral instantaneous overcurrent 1 has picked up Neutral NEUTRAL IOC1 OP Neutral instantaneous overcurrent 1 has operated...
  • Page 228 5.5 FLEXLOGIC™ 5 Z SETTINGS Table 5–8: F60 FLEXLOGIC™ OPERANDS (Sheet 5 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: PHASE UV1 PKP At least one phase of phase undervoltage 1 has picked up Phase undervoltage PHASE UV1 OP...
  • Page 229 5 Z SETTINGS 5.5 FLEXLOGIC™ Table 5–8: F60 FLEXLOGIC™ OPERANDS (Sheet 6 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: SWITCH 1 OFF CMD Disconnect switch 1 open command initiated Disconnect switch SWITCH 1 ON CMD Disconnect switch 1 close command initiated SWITCH 1 ΦA BAD ST...
  • Page 230 5.5 FLEXLOGIC™ 5 Z SETTINGS Table 5–8: F60 FLEXLOGIC™ OPERANDS (Sheet 7 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION INPUTS/OUTPUTS: Cont Ip 1 (will not appear unless ordered) Contact inputs Cont Ip 2 (will not appear unless ordered) ↓...
  • Page 231 5 Z SETTINGS 5.5 FLEXLOGIC™ Table 5–8: F60 FLEXLOGIC™ OPERANDS (Sheet 8 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION REMOTE DEVICES REMOTE DEVICE 1 On Flag is set, logic=1 ↓ ↓ REMOTE DEVICE 16 On Flag is set, logic=1...
  • Page 232: Flexlogic™ Rules

    When making changes to settings, all FlexLogic™ equations are re-compiled whenever any new setting value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic™ during testing, for example, it is suggested to power the unit down and then back up. 5-100 F60 Feeder Protection System GE Multilin...
  • Page 233: Flexlogic™ Example

    DIGITAL ELEMENT 1 on Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–37: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS GE Multilin F60 Feeder Protection System 5-101...
  • Page 234 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." 5-102 F60 Feeder Protection System GE Multilin...
  • Page 235 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". GE Multilin F60 Feeder Protection System 5-103...
  • Page 236 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) 5-104 F60 Feeder Protection System GE Multilin...
  • Page 237: Flexlogic Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". GE Multilin F60 Feeder Protection System 5-105...
  • Page 238 5.5 FLEXLOGIC™ 5 Z SETTINGS • TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0". 5-106 F60 Feeder Protection System GE Multilin...
  • Page 239: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. GE Multilin F60 Feeder Protection System 5-107...
  • Page 240 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS 5-108 F60 Feeder Protection System GE Multilin...
  • Page 241 DIRECTION = Under; FLEXELEMENT INPUT MODE = Signed; FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Absolute; FlexElement 1 OpSig 842706A2.CDR Figure 5–45: FLEXELEMENT™ INPUT MODE SETTING GE Multilin F60 Feeder Protection System 5-109...
  • Page 242 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. 5-110 F60 Feeder Protection System GE Multilin...
  • Page 243: Non-Volatile Latches

    FLEXLOGIC OPERANDS Off=0 LATCH 1 ON Dominant LATCH 1 OFF Previous Previous SETTING State State LATCH 1 SET: Off=0 RESET 842005A1.CDR Figure 5–46: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin F60 Feeder Protection System 5-111...
  • Page 244: Grouped Elements

    Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if no other group is active (see the Control elements section for additional details). 5-112 F60 Feeder Protection System GE Multilin...
  • Page 245 The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of the load encroachment characteristics used to block the quadrilateral distance element. GE Multilin F60 Feeder Protection System 5-113...
  • Page 246 If the voltage is below this threshold a blocking signal will not be asserted by the element. When selecting this setting one must remember that the F60 measures the phase-to-ground sequence voltages regardless of the VT connection.
  • Page 247 (2) phase directional overcurrent elements. b) INVERSE TIME OVERCURRENT CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 248 5.041 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 5-116 F60 Feeder Protection System GE Multilin...
  • Page 249 0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 GE Multilin F60 Feeder Protection System 5-117...
  • Page 250 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–17: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 251 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The F60 uses the FlexCurve™ feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve™ sec- tion in this chapter for additional details. GE Multilin...
  • Page 252 (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see the figure below); the pickup level is calculated as ‘Mvr’ times the setting. If the voltage restraint feature PHASE TOC1 PICKUP is disabled, the pickup level always remains at the setting value. 5-120 F60 Feeder Protection System GE Multilin...
  • Page 253 PHASE TOC1 C DPO Multiplier-Phase C PHASE TOC1 C OP SETTING PHASE TOC1 PKP PHASE TOC1 VOLT RESTRAINT: PHASE TOC1 OP Enabled PHASE TOC1 DPO 827072A4.CDR Figure 5–51: PHASE TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-121...
  • Page 254 The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing curves are shown below for form-A contacts in a 60 Hz system. 5-122 F60 Feeder Protection System GE Multilin...
  • Page 255 Off = 0 PHASE IOC1 PKP SETTING PHASE IOC1 OP PHASE IOC1 BLOCK-B: PHASE IOC1 DPO Off = 0 SETTING 827033A6.VSD PHASE IOC1 BLOCK-C: Off = 0 Figure 5–53: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-123...
  • Page 256 CTs and the line-line voltage from the VTs, based on the 90° or quadrature connection. If there is a requirement to supervise overcurrent elements for flows in opposite directions, such as can happen through a bus-tie breaker, two phase directional elements should be programmed with opposite element characteristic angle (ECA) settings. 5-124 F60 Feeder Protection System GE Multilin...
  • Page 257 Therefore, a coordination time of at least 10 ms must be added to all the instantaneous protec- tion elements under the supervision of the phase directional element. If current reversal is of a concern, a longer delay – in the order of 20 ms – may be needed. GE Multilin F60 Feeder Protection System 5-125...
  • Page 258 MESSAGE DIRECTIONAL OC1 NEUTRAL See page 5–129. MESSAGE DIRECTIONAL OC2 The F60 Feeder Protection System has two (2) Neutral Time Overcurrent, two (2) Neutral Instantaneous Overcurrent, and two (2) Neutral Directional Overcurrent elements. 5-126 F60 Feeder Protection System GE Multilin...
  • Page 259 SETTING NEUTRAL TOC1 PKP RESET: NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–56: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-127...
  • Page 260 NEUTRAL IOC1 PICKUP: RESET DELAY : SETTING NEUTRAL IOC1 DPO NEUTRAL IOC1 OP 3( _0 - K _1 ) PICKUP NEUTRAL IOC1 BLOCK: Off=0 SETTING NEUTRAL IOC1 SOURCE: 827035A4.CDR Figure 5–57: NEUTRAL IOC1 SCHEME LOGIC 5-128 F60 Feeder Protection System GE Multilin...
  • Page 261 × × (EQ 5.17) – The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions. GE Multilin F60 Feeder Protection System 5-129...
  • Page 262 1.5 of a power system cycle. The element is designed to emu- late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi- nation bringing more security to the element operation. 5-130 F60 Feeder Protection System GE Multilin...
  • Page 263 The low-side system impedance should be assumed minimal when checking for this condition. A similar sit- uation arises for a wye/delta/wye transformer, where current in one transformer winding neutral may reverse when faults on both sides of the transformer are considered. GE Multilin F60 Feeder Protection System 5-131...
  • Page 264 NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique for the “Calculated 3I0” mode of operation. 5-132 F60 Feeder Protection System GE Multilin...
  • Page 265 3) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN _1 IS BELOW 0.8pu NEUTRAL DIR OC1 POS- SEQ RESTRAINT: 3( _0 - K _1 ) PICKUP 827077AB.CDR PICKUP Figure 5–59: NEUTRAL DIRECTIONAL OVERCURRENT LOGIC GE Multilin F60 Feeder Protection System 5-133...
  • Page 266 VT connected to the auxiliary channel bank of the relay). When the latter selection is made, the auxiliary channel must be identified by the user as a neutral voltage under the VT bank settings. This element will operate only if the aux- iliary voltage is configured as neutral. 5-134 F60 Feeder Protection System GE Multilin...
  • Page 267 ⎛ ⎞ FlexCurve --------- - (EQ 5.20) ⎝ ⎠ Again, the FlexCurve timer starts after the definite time timer expires. GE Multilin F60 Feeder Protection System 5-135...
  • Page 268 SETTING 1 FUNCTION: WATTMETRIC GND FLT 1 Enabled = 1 OC PKP DEL: WATT GND FLT 1 BLK: FLEXLOGIC OPERAND Off = 0 WATTMETRIC 1 PKP 837033A4.CDR Figure 5–61: WATTMETRIC ZERO-SEQUENCE DIRECTIONAL LOGIC 5-136 F60 Feeder Protection System GE Multilin...
  • Page 269 GROUND TOC 1 SETTING RESET: GROUND TOC1 PKP GROUND TOC1 IG ≥ PICKUP GROUND TOC1 DPO SOURCE: GROUND TOC1 OP SETTING GROUND TOC1 BLOCK: 827036A3.VSD Off = 0 Figure 5–62: GROUND TOC1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-137...
  • Page 270 Enabled = 1 SETTING DELAY: GROUND IOC1 GROUND IOC1 RESET SETTING PICKUP: DELAY: GROUND IOC1 SOURCE: IG ≥ PICKUP SETTING GROUND IOC1 BLOCK: 827037A4.VSD Off = 0 Figure 5–63: GROUND IOC1 SCHEME LOGIC 5-138 F60 Feeder Protection System GE Multilin...
  • Page 271 See page 5–142. MESSAGE The F60 relay provides two (2) negative-sequence time overcurrent elements, two (2) negative-sequence instantaneous overcurrent elements, and two (2) negative-sequence directional overcurrent elements. For additional information on the negative sequence time overcurrent curves, refer to the Inverse Time Overcurrent Curves section earlier.
  • Page 272 SETTING < NEG SEQ PICKUP NEG SEQ TOC1 DPO NEG SEQ TOC1 OP NEG SEQ TOC1 BLOCK: Off=0 SETTING NEG SEQ TOC1 SOURCE: Neg Seq 827057A4.CDR Figure 5–64: NEGATIVE SEQUENCE TOC1 SCHEME LOGIC 5-140 F60 Feeder Protection System GE Multilin...
  • Page 273 RESET DELAY: SETTING NEG SEQ IOC1 DPO NEG SEQ IOC1 OP _2 - K _1 PICKUP NEG SEQ IOC1 BLOCK: Off=0 SETTING NEG SEQ IOC1 SOURCE: 827058A5.CDR Figure 5–65: NEGATIVE SEQUENCE IOC1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-141...
  • Page 274 The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence and zero-sequence currents resulting from: • System unbalances under heavy load conditions. • Transformation errors of current transformers (CTs). • Fault inception and switch-off transients. 5-142 F60 Feeder Protection System GE Multilin...
  • Page 275: Negative-Sequence Current

    CT errors, since the current is low. The operating quantity depends on the way the test currents are injected into the F60. For single phase injection: = ⅓ × (1 – K) × I •...
  • Page 276 The element characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°. • NEG SEQ DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit angle for the forward direction. 5-144 F60 Feeder Protection System GE Multilin...
  • Page 277 ( |I_2| – × |I_1| ) Pickup ≥ Type = Neg Sequence FLEXLOGIC OPERAND = Zero Sequence NEG SEQ DIR OC1 REV ( |3I_0| – × |I_1| ) Pickup ≥ 827091A6.CDR Figure 5–67: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-145...
  • Page 278: Breaker Failure 1

    Range: 0.001 to 30.000 pu in steps of 0.001 BF1 N AMP HISET MESSAGE PICKUP: 1.050 pu Range: 0.001 to 30.000 pu in steps of 0.001 BF1 PH AMP LOSET MESSAGE PICKUP: 1.050 pu 5-146 F60 Feeder Protection System GE Multilin...
  • Page 279 This can also occur in breaker-and-a-half or ring bus configurations where the first breaker closes into a fault; the protection trips and attempts to initiate breaker failure for the second breaker, which is in the process of closing, but does not yet have current flowing through it. GE Multilin F60 Feeder Protection System 5-147...
  • Page 280 BREAKER FAILURE TIMER No. 2 (±1/8 cycle) INITIATE (1/8 cycle) BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle) BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle) FAULT cycles OCCURS 827083A6.CDR Figure 5–68: BREAKER FAILURE MAIN PATH SEQUENCE 5-148 F60 Feeder Protection System GE Multilin...
  • Page 281 In microprocessor relays this time is not significant. In F60 relays, which use a Fourier transform, the calculated current magnitude will ramp-down to zero one power frequency cycle after the current is interrupted, and this lag should be included in the overall margin duration, as it occurs after current interruption.
  • Page 282 Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be given via output operand BKR FAIL 1 TRIP OP 5-150 F60 Feeder Protection System GE Multilin...
  • Page 283 SETTING SETTING Source Pickup Initiated phase C to breaker failure single-pole logic sheet 2 Pickup to breaker failure single-pole logic sheet 3 834013A2.CDR Figure 5–70: SINGLE-POLE BREAKER FAILURE, INITIATE (Sheet 1 of 2) GE Multilin F60 Feeder Protection System 5-151...
  • Page 284 5.6 GROUPED ELEMENTS 5 Z SETTINGS Figure 5–71: SINGLE-POLE BREAKER FAILURE, TIMERS (Sheet 2 of 2) 5-152 F60 Feeder Protection System GE Multilin...
  • Page 285 5 Z SETTINGS 5.6 GROUPED ELEMENTS Figure 5–72: THREE-POLE BREAKER FAILURE, INITIATE (Sheet 1 of 2) GE Multilin F60 Feeder Protection System 5-153...
  • Page 286 5.6 GROUPED ELEMENTS 5 Z SETTINGS Figure 5–73: THREE-POLE BREAKER FAILURE, TIMERS (Sheet 2 of 2) 5-154 F60 Feeder Protection System GE Multilin...
  • Page 287: Voltage Elements

    The time delay is adjustable from 0 to 600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char- acteristic. GE Multilin F60 Feeder Protection System 5-155...
  • Page 288 V = secondary voltage applied to the relay = pickup level pickup % of voltage pickup 842788A1.CDR Figure 5–74: INVERSE TIME UNDERVOLTAGE CURVES At 0% of pickup, the operating time equals the setting. UNDERVOLTAGE DELAY NOTE 5-156 F60 Feeder Protection System GE Multilin...
  • Page 289 Source VT = Wye FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP FLEXLOGIC OPERAND PHASE UV1 DPO 827039AB.CDR Figure 5–75: PHASE UNDERVOLTAGE1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-157...
  • Page 290 FLEXLOGIC OPERAND PHASE OV1 PKP 827066A7.CDR Figure 5–76: PHASE OVERVOLTAGE SCHEME LOGIC > × If the source VT is wye-connected, then the phase overvoltage pickup condition is Pickup for V and V NOTE 5-158 F60 Feeder Protection System GE Multilin...
  • Page 291 “Definite time”. The source assigned to this element must be configured for a phase VT. NEUTRAL OV1 CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–77: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-159...
  • Page 292 NEG SEQ OV1 DPO NEG SEQ OV1 OP SETTING ≥ V_2 or 3 × V_2 PKP NEG SEQ OV1 SIGNAL SOURCE: Wye VT Delta VT 3 × V_2 827839A3.CDR Figure 5–78: NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC 5-160 F60 Feeder Protection System GE Multilin...
  • Page 293 AUX UV1 EVENTS: MESSAGE Disabled The F60 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt- age conditions of the auxiliary voltage. The selects the voltage level at which the time undervoltage ele- AUX UV1 PICKUP ment starts timing.
  • Page 294 AUX OV1 EVENTS: MESSAGE Disabled The F60 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM...
  • Page 295: Sensitive Directional Power

    The operating quantity is displayed in the actual ACTUAL VALUES METERING SENSITIVE DIRECTIONAL POWER 1(2) value. The element has two independent (as to the pickup and delay settings) stages for alarm and trip, respectively. GE Multilin F60 Feeder Protection System 5-163...
  • Page 296 RCA = 0 SMIN < 0 SMIN > 0 OPERATE RESTRAIN RESTRAIN OPERATE RCA = 90 RCA = 270 SMIN > 0 SMIN < 0 842702A1.CDR Figure 5–82: DIRECTIONAL POWER ELEMENT SAMPLE APPLICATIONS 5-164 F60 Feeder Protection System GE Multilin...
  • Page 297 DIR POWER 1 OP Three-phase reactive power (Q) DIR POWER 1 STG2 DPO DIR POWER 1 STG2 OP SETTING DIR POWER 1 STG2 DELAY: 100 ms 842003A3.CDR Figure 5–83: SENSITIVE DIRECTIONAL POWER SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-165...
  • Page 298: Control Elements

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-166 F60 Feeder Protection System GE Multilin...
  • Page 299 TRIP BUS 1 PKP = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–85: TRIP BUS LOGIC GE Multilin F60 Feeder Protection System 5-167...
  • Page 300: Setting Groups

    The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 5-168 F60 Feeder Protection System GE Multilin...
  • Page 301: Selector Switch

    Range: FlexLogic™ operand SELECTOR 1 3BIT ACK: MESSAGE Range: Restore, Synchronize, Sync/Restore SELECTOR 1 POWER-UP MESSAGE MODE: Restore Range: Self-reset, Latched, Disabled SELECTOR 1 TARGETS: MESSAGE Self-reset Range: Disabled, Enabled SELECTOR 1 EVENTS: MESSAGE Disabled GE Multilin F60 Feeder Protection System 5-169...
  • Page 302 • SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest 5-170 F60 Feeder Protection System GE Multilin...
  • Page 303 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. GE Multilin F60 Feeder Protection System 5-171...
  • Page 304 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–87: TIME-OUT MODE 5-172 F60 Feeder Protection System GE Multilin...
  • Page 305 Make the following changes to selector switch element in the SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 GE Multilin F60 Feeder Protection System 5-173...
  • Page 306 3-bit acknowledge SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–89: SELECTOR SWITCH LOGIC 5-174 F60 Feeder Protection System GE Multilin...
  • Page 307: Underfrequency 1

    SETTING ≤ 0 < f PICKUP UNDERFREQ 1 OP UNDERFREQ 1 ACTUAL VALUES MIN VOLT / AMP: UNDERFREQ 1 SOURCE: ≥ Level Minimum VOLT / AMP Frequency 827079A8.CDR Figure 5–90: UNDERFREQUENCY SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-175...
  • Page 308: Overfrequency 1

    OVERFREQ 1 BLOCK: OVERFREQ 1 RESET OVERFREQ 1 PKP DELAY : Off = 0 OVERFREQ 1 DPO OVERFREQ 1 OP SETTING ≥ PICKUP OVERFREQ 1 SOURCE: Frequency 827832A5.CDR Figure 5–91: OVERFREQUENCY SCHEME LOGIC 5-176 F60 Feeder Protection System GE Multilin...
  • Page 309: Frequency Rate Of Change

    FREQ RATE 1 OC SUPV PICKUP: This setting defines minimum current level required for operation of the element. The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set the pickup threshold to zero if no overcurrent supervision is required. GE Multilin F60 Feeder Protection System 5-177...
  • Page 310 SETTINGS FREQ RATE 1 PKP FREQ RATE 1 MIN FREQUENCY: FREQ RATE 1 MAX FREQUENCY: F > MIN & F < MAX Calculate df/dt 832023A2.CDR Figure 5–92: FREQUENCY RATE OF CHANGE SCHEME LOGIC 5-178 F60 Feeder Protection System GE Multilin...
  • Page 311: Synchrocheck

    ΔF. This time can be calculated by: ------------------------------- - (EQ 5.25) 360° ----------------- - × ΔF 2 ΔΦ × where: ΔΦ = phase angle difference in degrees; ΔF = frequency difference in Hz. GE Multilin F60 Feeder Protection System 5-179...
  • Page 312 (SOURCE Z) COMBINATION SOURCE Y SOURCE Z Phase VTs and Phase VTs and Phase Phase Auxiliary VT Auxiliary VT Phase VTs and Phase VT Phase Phase Auxiliary VT Phase VT Phase VT Phase Phase 5-180 F60 Feeder Protection System GE Multilin...
  • Page 313 The relay will use the phase channel of a three-phase set of voltages if pro- grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. GE Multilin F60 Feeder Protection System 5-181...
  • Page 314 ΔF ≤ Maximum Frequency F2 I F1 – F2 I = F Δ = SRC 2 ACTUAL VALUE Synchrocheck 1 V Δ Synchrocheck 1 ΔΦ Synchrocheck 1 F Δ 827076AB.CDR Figure 5–93: SYNCHROCHECK SCHEME LOGIC 5-182 F60 Feeder Protection System GE Multilin...
  • Page 315: Autoreclose

    4.000 s Range: FlexLogic™ operand AR1 ADD DELAY 1: MESSAGE Range: 0.00 to 655.35 s in steps of 0.01 AR1 DELAY 1: MESSAGE 0.000 s Range: FlexLogic™ operand AR1 ADD DELAY 2: MESSAGE GE Multilin F60 Feeder Protection System 5-183...
  • Page 316 Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs: • The maximum shot number was reached. • A ‘Block’ input is in effect (for instance; Breaker Failure, bus differential protection operated, etc.). 5-184 F60 Feeder Protection System GE Multilin...
  • Page 317 ‘reclose-in-progress’ state. If all condi- tions allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. This timer must be set to a delay less than the reset timer. NOTE GE Multilin F60 Feeder Protection System 5-185...
  • Page 318 5.7 CONTROL ELEMENTS 5 Z SETTINGS To sheet 2 Figure 5–94: AUTORECLOSURE SCHEME LOGIC (Sheet 1 of 2) 5-186 F60 Feeder Protection System GE Multilin...
  • Page 319 5 Z SETTINGS 5.7 CONTROL ELEMENTS Figure 5–95: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2) GE Multilin F60 Feeder Protection System 5-187...
  • Page 320 5.7 CONTROL ELEMENTS 5 Z SETTINGS Figure 5–96: SINGLE SHOT AUTORECLOSING SEQUENCE - PERMANENT FAULT 5-188 F60 Feeder Protection System GE Multilin...
  • Page 321: Digital Elements

    Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts. The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A). GE Multilin F60 Feeder Protection System 5-189...
  • Page 322 The settings to use digital element 1 to monitor the breaker trip circuit are indicated below (EnerVista UR Setup example shown): setting should be greater than the operating time of the breaker to avoid nuisance PICKUP DELAY alarms. NOTE 5-190 F60 Feeder Protection System GE Multilin...
  • Page 323 V = voltage monitor 827074A3.CDR Figure 5–99: TRIP CIRCUIT EXAMPLE 2 The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and solid-state contact with voltage monitoring. NOTE GE Multilin F60 Feeder Protection System 5-191...
  • Page 324: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are blocked. 5-192 F60 Feeder Protection System GE Multilin...
  • Page 325 COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–100: DIGITAL COUNTER SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-193...
  • Page 326: Monitoring Elements

    Range: 10 to 200 s in steps of 1 HI-Z OC PROTECTION MESSAGE COORD TIMEOUT: 15 s Range: 0.01 to 10.00 pu in steps of 0.01 HI-Z PHASE OC MIN MESSAGE PICKUP: 1.50 pu 5-194 F60 Feeder Protection System GE Multilin...
  • Page 327 High-Z Data Capture: Hi-Z Data Captures are triggered and maintained in an identical manner as RMS Data Cap- tures. The relay maintains four captures of 300 records each. The capture frequency is 1 Hz and the data collected is defined in the following two tables. GE Multilin F60 Feeder Protection System 5-195...
  • Page 328 “enough times” means. If these criteria are met, the algorithm temporarily moves to either the “Arcing” state or the “Downed Conductor” state, the difference being determined by whether or not there was a 5-196 F60 Feeder Protection System GE Multilin...
  • Page 329 The Hi-Z detection algorithms will ignore all data as long as an overcurrent condition exists on the system, because it is assumed that conventional feeder overcurrent protection GE Multilin F60 Feeder Protection System 5-197...
  • Page 330 For the first three to five days after installation (or after being out-of-service for a sig- NOTE nificant period), the F60 may identify some of this noise as arcing. This should be taken into account when responding to alarms during these type of operating periods.
  • Page 331 C EVEN % > PKP > 0 VOLTAGE SUPERVISION ALG. SETTING HI-Z VOLTAGE SUPV SETTING THRESHOLD: HI-Z VOLTAGE SUPV DELAY: VA % > PKP VB % > PKP VC % > PKP 827838A8.CDR Figure 5–101: HI-Z SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-199...
  • Page 332 • BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. 5-200 F60 Feeder Protection System GE Multilin...
  • Page 333 YES=1 BKR 1 ARCING AMP C 827071A3.CDR BKR 1 OPERATING TIME A BKR 1 OPERATING TIME B BKR 1 OPERATING TIME C BKR 1 OPERATING TIME Figure 5–103: BREAKER ARCING CURRENT SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-201...
  • Page 334 Voltage drop measured from either side of the breaker during the flashover period, Voltage difference drop, and Measured flashover current through the breaker. Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across the breaker. 5-202 F60 Feeder Protection System GE Multilin...
  • Page 335 This application do not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than the setting. However, monitoring the breaker contact will ensure scheme stability. BRK 1 FLSHOVR DIFF V PKP GE Multilin F60 Feeder Protection System 5-203...
  • Page 336 BRK 1 FLSHOVR SPV A to BRK 1 FLSHOVR SPV C: These settings specifiy FlexLogic™ operands (per breaker pole) that supervise the operation of the element per phase. Supervision can be provided by operation of other protec- 5-204 F60 Feeder Protection System GE Multilin...
  • Page 337 BRK 1 FLSHOVR DIFF V SRC: PKP: SRC 1 SRC 2 SRC 6 , … , , none VA > PKP VA = VA - Va 842018A2.CDR Figure 5–104: BREAKER FLASHOVER SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-205...
  • Page 338 MESSAGE EVENTS: Disabled One breaker restrike element is provided in the F60. According to IEEE standard C37.100: IEEE Standard Definitions for Power Switchgear, restrike is defined as “a resumption of current between the contacts of a switching device during an opening operation after an interval of zero current of ¼...
  • Page 339 “1” when breaker is opened, either manually or from protection logic. • BRK RSTR 1 CLS CMD: This setting assigns a FlexLogic™ operand indicating a breaker close command. It must be logic “1” when breaker is closed. GE Multilin F60 Feeder Protection System 5-207...
  • Page 340 Due to shortness of such spikes, they are not usually detected by the instantaneous protection of the feeder, which operates on the RMS or fundamental component of the phase current with a relatively high pickup. 5-208 F60 Feeder Protection System GE Multilin...
  • Page 341 INCIPIENT FLT 1 TRIP COUNTS NUMBER: This setting selects the number of faults required to initiate a trip. • INCIPNT FLT 1 DETECT WINDOW: This setting specifies a time window for “Counts per window” mode of operation. GE Multilin F60 Feeder Protection System 5-209...
  • Page 342 An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive sequence voltage and current are both below threshold levels. The function setting enables and disables the fuse failure feature for each source. 5-210 F60 Feeder Protection System GE Multilin...
  • Page 343: Cold Load Pickup 1

    During the cold load condition, the current level can be above the pickup setting of some protection elements, so this feature can be used to prevent the tripping that would otherwise be caused by the normal settings. GE Multilin F60 Feeder Protection System 5-211...
  • Page 344 The reset delay interval is intended to be set to a period until the ON-LOAD TIME BEFORE RESET feeder load has decayed to normal levels, after which other features may be used to switch setting groups. Figure 5–112: COLD LOAD PICKUP SCHEME LOGIC 5-212 F60 Feeder Protection System GE Multilin...
  • Page 345: Inputs/Outputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the F60 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 346 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5-214 F60 Feeder Protection System GE Multilin...
  • Page 347: Virtual Inputs

    SETTING “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–114: VIRTUAL INPUTS SCHEME LOGIC GE Multilin F60 Feeder Protection System 5-215...
  • Page 348: Contact Outputs

    The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the F60 using the FlexLogic™ operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
  • Page 349 5.8 INPUTS/OUTPUTS The F60 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
  • Page 350: Virtual Outputs

    FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: 5-218 F60 Feeder Protection System GE Multilin...
  • Page 351: Remote Devices

    The remote input/output facility provides for 32 remote inputs and 64 remote outputs. b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES In a F60 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the...
  • Page 352: Remote Inputs

    This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre- sponding settings on the sending device. setting provides for the choice of the F60 fixed (DNA/UserSt) dataset (that is, containing REMOTE DEVICE 1 DATASET DNA and UserSt bit pairs), or one of the configurable datasets.
  • Page 353: Remote Double-Point Status Inputs

    PATH: SETTINGS INPUTS/OUTPUTS REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUPUTS DNA- 1(32) BIT PAIR Range: FlexLogic™ operand REMOTE OUTPUTS DNA- 1 OPERAND: DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled GE Multilin F60 Feeder Protection System 5-221...
  • Page 354: Resetting

    RESET OP to identify the source of the command. The setting RESET OP (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) shown above selects the operand that will create the operand. RESET OP (OPERAND) 5-222 F60 Feeder Protection System GE Multilin...
  • Page 355: Direct Inputs And Outputs

    FlexLogic™ operand that determines the state of this direct output. c) APPLICATION EXAMPLES The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. GE Multilin F60 Feeder Protection System 5-223...
  • Page 356 5.8 INPUTS/OUTPUTS 5 Z SETTINGS EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A F60 RELAY Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements.
  • Page 357 "3" (effectively, this is a message from IED 1) DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: GE Multilin F60 Feeder Protection System 5-225...
  • Page 358: Teleprotection Inputs And Outputs

    Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-1 MESSAGE DEFAULT: Off Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-2 MESSAGE DEFAULT: Off ↓ Range: Off, On, Latest/Off, Latest/On TELEPROT INPUT 2-16 MESSAGE DEFAULT: Off 5-226 F60 Feeder Protection System GE Multilin...
  • Page 359 (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. GE Multilin F60 Feeder Protection System 5-227...
  • Page 360: Iec 61850 Goose Analogs

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log™ values in other F60 features, such as FlexElements™. The base factor is applied to the GOOSE analog input FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 361: Iec 61850 Goose Integers

    = maximum primary RMS value of all the sources related to the +IN and –IN inputs BASE (Max Delta Volts) The GOOSE analog input FlexAnalog™ values are available for use in other F60 functions that use FlexAnalog™ values. 5.8.13 IEC 61850 GOOSE INTEGERS PATH: SETTINGS...
  • Page 362: Transducer Inputs And Outputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT H1 MIN VALUE DCMA INPUT H1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE 5-230 F60 Feeder Protection System GE Multilin...
  • Page 363: Rtd Inputs

    1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. GE Multilin F60 Feeder Protection System 5-231...
  • Page 364 15.61 168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 5-232 F60 Feeder Protection System GE Multilin...
  • Page 365: Dcma Outputs

    – MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. DRIVING SIGNAL MIN VAL MAX VAL 842739A1.CDR Figure 5–121: DCMA OUTPUT CHARACTERISTIC GE Multilin F60 Feeder Protection System 5-233...
  • Page 366 The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow- ing for 50% overload. The phase current with the 50% overload margin is: 5-234 F60 Feeder Protection System GE Multilin...
  • Page 367 254.03 kV 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. GE Multilin F60 Feeder Protection System 5-235...
  • Page 368: Testing

    TEST MODE FORCING: MESSAGE The F60 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 369: Force Contact Inputs

    Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a F60 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 370: Force Contact Outputs

    USER PUSHBUTTON 1 PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu: SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: 5-238 F60 Feeder Protection System GE Multilin...
  • Page 371: Actual Values

    DIRECT INPUTS See page 6-7. DIRECT DEVICES See page 6-8. STATUS IEC 61850 See page 6-8. GOOSE UINTEGERS EGD PROTOCOL See page 6-8. STATUS TELEPROT CH TESTS See page 6-9. INCIPIENT FAULT See page 6-9. GE Multilin F60 Feeder Protection System...
  • Page 372 See page 6-23. OSCILLOGRAPHY See page 6-24. DATA LOGGER See page 6-24. MAINTENANCE See page 6-25. HIZ RECORDS See page 6-25. ACTUAL VALUES MODEL INFORMATION See page 6-26. PRODUCT INFO FIRMWARE REVISIONS See page 6-26. F60 Feeder Protection System GE Multilin...
  • Page 373: Contact Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin F60 Feeder Protection System...
  • Page 374: Remote Double-Point Status Inputs

    The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of the display indicates the logic state of the contact output. F60 Feeder Protection System GE Multilin...
  • Page 375: Virtual Outputs

    The present state of up to 16 programmed remote devices is shown here. The message indi- ALL REMOTE DEVICES ONLINE cates whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required remote device is not online. GE Multilin F60 Feeder Protection System...
  • Page 376: Digital Counters

    6.2.12 FLEX STATES PATH: ACTUAL VALUES STATUS FLEX STATES Range: Off, On FLEX STATES PARAM 1: Off Range: Off, On PARAM 2: Off MESSAGE ↓ Range: Off, On PARAM 256: Off MESSAGE F60 Feeder Protection System GE Multilin...
  • Page 377: Ethernet

    AVERAGE MSG RETURN TIME ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last ten messages. There are two return times for dual-channel communications modules. GE Multilin F60 Feeder Protection System...
  • Page 378: Direct Devices Status

    UINT INPUT 16 MESSAGE The F60 Feeder Protection System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
  • Page 379: Teleprotection Channel Tests

    The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values can be reset to zero with the command. COMMANDS CLEAR RECORDS CLEAR INCIPENT FAULT COUNTERS GE Multilin F60 Feeder Protection System...
  • Page 380: Ethernet Switch

    SWITCH MAC ADDRESS: MESSAGE 00A0F40138FA These actual values appear only if the F60 is ordered with an Ethernet switch module (type 2S or 2T). The status informa- tion for the Ethernet switch is shown in this menu. • SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on the Ethernet switch.
  • Page 381: Metering Conventions

    PF = Lag WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS GE Multilin F60 Feeder Protection System 6-11...
  • Page 382 ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. 6-12 F60 Feeder Protection System GE Multilin...
  • Page 383 The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a relative matter. It is important to remember that the F60 displays are always referenced as specified under SETTINGS...
  • Page 384: Sources

    0.000 SRC 1 RMS Ib: MESSAGE 0.000 SRC 1 RMS Ic: MESSAGE 0.000 SRC 1 RMS In: MESSAGE 0.000 SRC 1 PHASOR Ia: MESSAGE 0.000 0.0° SRC 1 PHASOR Ib: MESSAGE 0.000 0.0° 6-14 F60 Feeder Protection System GE Multilin...
  • Page 385 0.0° SRC 1 PHASOR Vbg: MESSAGE 0.000 0.0° SRC 1 PHASOR Vcg: MESSAGE 0.000 0.0° SRC 1 RMS Vab: MESSAGE 0.00 SRC 1 RMS Vbc: MESSAGE 0.00 SRC 1 RMS Vca: MESSAGE 0.00 GE Multilin F60 Feeder Protection System 6-15...
  • Page 386 REACTIVE PWR MESSAGE 3φ: 0.000 SRC 1 REACTIVE PWR MESSAGE φa: 0.000 SRC 1 REACTIVE PWR MESSAGE φb: 0.000 SRC 1 REACTIVE PWR MESSAGE φc: 0.000 SRC 1 APPARENT PWR MESSAGE 3φ: 0.000 6-16 F60 Feeder Protection System GE Multilin...
  • Page 387 DMD IA: SRC 1 0.000 SRC 1 DMD IA MAX: MESSAGE 0.000 SRC 1 DMD IA DATE: MESSAGE 2001/07/31 16:30:07 SRC 1 DMD IB: MESSAGE 0.000 SRC 1 DMD IB MAX: MESSAGE 0.000 GE Multilin F60 Feeder Protection System 6-17...
  • Page 388 The signal used for frequency estimation is low-pass filtered. The SYSTEM SETUP POWER SYSTEM final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and transients. 6-18 F60 Feeder Protection System GE Multilin...
  • Page 389 The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental ampli- tude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the fundamental: … (EQ 6.2) GE Multilin F60 Feeder Protection System 6-19...
  • Page 390: Sensitive Directional Power

    6.3 METERING 6 ACTUAL VALUES Voltage harmonics are not available on F60 relays configured with the high-impedance fault detection (Hi-Z) fea- ture. NOTE Voltage harmonics are calculated only for Wye connected phase VTs. Ensure the SYSTEM SETUP AC INPUTS setting is “Wye” to enable voltage harmonics metering.
  • Page 391: Frequency Rate Of Change

    = maximum nominal primary RMS value of the +IN and –IN inputs BASE SYNCHROCHECK = maximum primary RMS value of all the sources related to the +IN and –IN inputs BASE (Max Delta Volts) GE Multilin F60 Feeder Protection System 6-21...
  • Page 392: Iec 61580 Goose Analog Values

    MESSAGE 0.000 The F60 Feeder Protection System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
  • Page 393: Records

    If all 1024 event records have been filled, the oldest record will be removed as a new record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the event trigger. Refer to the menu for clearing event records. COMMANDS CLEAR RECORDS GE Multilin F60 Feeder Protection System 6-23...
  • Page 394: Oscillography

    It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the menu for clearing data logger records. COMMANDS CLEAR RECORDS 6-24 F60 Feeder Protection System GE Multilin...
  • Page 395: Breaker Maintenance

    If the element is triggered by high impedance fault detection arcing algorithm, then the records are dis- RMS 4 played in the actual values. Refer to High impedance fault detection section in chapter 5 for more information. HIZ 1 HIZ 4 GE Multilin F60 Feeder Protection System 6-25...
  • Page 396: Product Information

    6 ACTUAL VALUES 6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE multilin order code format; MODEL INFORMATION ORDER CODE LINE 1: example order code shown F60-E00-HCH-F8F-H6A Range: standard GE multilin order code format...
  • Page 397: Commands And

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin F60 Feeder Protection System...
  • Page 398 24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com- mand. The new time will take effect at the moment the ENTER key is clicked. F60 Feeder Protection System GE Multilin...
  • Page 399: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the F60 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the F60 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
  • Page 400: Targets Menu

    The critical fail relay on the power supply module is de-energized. • All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. • event is recorded. RELAY OUT OF SERVICE F60 Feeder Protection System GE Multilin...
  • Page 401 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the F60 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 402 How often the test is performed: Monitored every five seconds. An error is issued after five consecutive failures • What to do: Check the F60 device and switch IP configuration settings. Check for incorrect UR port (port 7) settings on the Ethernet switch. Check the power to the switch.
  • Page 403 What to do: Check direct input and output configuration and wiring. REMOTE DEVICE FAIL: COMM Path Incomplete • Latched target message: No. • Description of problem: One or more GOOSE devices are not responding. GE Multilin F60 Feeder Protection System...
  • Page 404 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the F60 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 405: Security

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the F60, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 406: Password Security Menu

    If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both com- mands and settings. NOTE F60 Feeder Protection System GE Multilin...
  • Page 407: Remote Passwords

    ACCESS ACCESS LEVEL SUPERVISION TIMEOUTS Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min GE Multilin F60 Feeder Protection System...
  • Page 408: Dual Permission Security Access

    INVALID ATTEMPS BEFORE LOCKOUT The F60 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic™ operand is UNAUTHORIZED ACCESS asserted.
  • Page 409 If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin F60 Feeder Protection System...
  • Page 410: Settings Security

    (settings file templates) and online devices (online settings templates). The func- tionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the F60 firmware are at ver- sions 5.40 or higher.
  • Page 411 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin F60 Feeder Protection System...
  • Page 412 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND F60 Feeder Protection System GE Multilin...
  • Page 413 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin F60 Feeder Protection System...
  • Page 414: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. 8-10 F60 Feeder Protection System GE Multilin...
  • Page 415 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin F60 Feeder Protection System 8-11...
  • Page 416: Settings File Traceability

    When a settings file is transfered to a F60 device, the date, time, and serial number of the F60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the F60 actual values at any later date to determine if security has been compromised.
  • Page 417 8.2 SETTINGS SECURITY The transfer date of a setting file written to a F60 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 418 ONLINE DEVICE TRACEABILITY INFORMATION The F60 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 419: Enervista Security Management System

    Select the Security > User Management menu item to open the user management configuration window. Enter a username in the User field. The username must be between 4 and 20 characters in length. GE Multilin F60 Feeder Protection System 8-15...
  • Page 420: Modifying User Privileges

    The EnerVista security management system must be enabled. The following procedure describes how to modify user privileges. Select the Security > User Management menu item to open the user management configuration window. Locate the username in the User field. 8-16 F60 Feeder Protection System GE Multilin...
  • Page 421 When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights. Click OK to save the changes to user to the security management system. GE Multilin F60 Feeder Protection System 8-17...
  • Page 422 8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8-18 F60 Feeder Protection System GE Multilin...
  • Page 423: Theory Of Operation

    50 Hz system, it consists of a sum of the 25, 75, 125,..., 625 Hz components. If the Energy Algorithm detects a sudden, sustained increase in one of these component energies, it reports this to the Expert Arc Detector algorithm, resets itself, and continues to monitor for another sudden increase. GE Multilin F60 Feeder Protection System...
  • Page 424: Randomness Algorithm

    F60 Feeder Protection System GE Multilin...
  • Page 425: Load Analysis Algorithm

    The duration over which the algorithm inhibits the setting of the overcurrent flag(s) is from the time the even-harmonic level (as a percentage of RMS) increases above the threshold until one second after it falls back below the threshold. GE Multilin F60 Feeder Protection System...
  • Page 426: Hi-Z Voltage Supervision Algorithm

    If one phase voltage shows a dip, the block is applied for all phases. Also the High Impedance Oscillography will record that a voltage dip was experienced. The Oscillography record is phase specific. F60 Feeder Protection System GE Multilin...
  • Page 427: Fault Locator

    Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before applying the two equations above (the superscripts denote phases, the subscripts denote stations). For AG faults: ⋅ (EQ 9.7) GE Multilin F60 Feeder Protection System...
  • Page 428 SYS0 -- - V (EQ 9.14) – – SYS0 -- - V – – SYS0 where Z is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu. SYS0 F60 Feeder Protection System GE Multilin...
  • Page 429 FAULT TYPE FAULT FAULT LOCATION 3I_0 LOCATOR 1 FAULT# RECLOSE SHOT VA or VAB VB or VBC VC or VCA Vn or V_0 SHOT # FROM 827094A5.CDR AUTO RECLOSURE Figure 9–2: FAULT LOCATOR SCHEME GE Multilin F60 Feeder Protection System...
  • Page 430 9.2 FAULT LOCATOR 9 THEORY OF OPERATION F60 Feeder Protection System GE Multilin...
  • Page 431: Commissioning

    Injection to a particular F60 frequency element must be to its configured source and to the channels the source uses for fre- quency measurement.
  • Page 432 1 second from test set time reading of ramp start to relay operation. Note that the F60 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time taken by the frequency responding component to pickup.
  • Page 433: Parameter Lists

    Source 2 ground current RMS 6230 SRC 2 Ig Mag Degrees Source 2 ground current magnitude 6232 SRC 2 Ig Angle Amps Source 2 ground current angle 6233 SRC 2 I_0 Mag Degrees Source 2 zero-sequence current magnitude GE Multilin F60 Feeder Protection System...
  • Page 434 SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS 6739 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS 6741 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude F60 Feeder Protection System GE Multilin...
  • Page 435 Source 2 phase A power factor 7226 SRC 2 Phase B PF Source 2 phase B power factor 7227 SRC 2 Phase C PF Source 2 phase C power factor 7552 SRC 1 Frequency Source 1 frequency GE Multilin F60 Feeder Protection System...
  • Page 436 Volts Source 1 phase B voltage seventh harmonic 8096 SRC 1 Vb Harm[6] Volts Source 1 phase B voltage eighth harmonic 8097 SRC 1 Vb Harm[7] Volts Source 1 phase B voltage ninth harmonic F60 Feeder Protection System GE Multilin...
  • Page 437 Volts Source 2 phase A voltage fourth harmonic 8143 SRC 2 Va Harm[3] Volts Source 2 phase A voltage fifth harmonic 8144 SRC 2 Va Harm[4] Volts Source 2 phase A voltage sixth harmonic GE Multilin F60 Feeder Protection System...
  • Page 438 Source 2 phase C voltage total harmonic distortion (THD) 8190 SRC 2 Vc Harm[0] Volts Source 2 phase C voltage second harmonic 8191 SRC 2 Vc Harm[1] Volts Source 2 phase C voltage third harmonic F60 Feeder Protection System GE Multilin...
  • Page 439 Degrees Fault 1 post-fault phase C current angle 9051 Postfault Va Mag [0] Volts Fault 1 post-fault phase A voltage magnitude 9053 Postfault Va Ang [0] Degrees Fault 1 post-fault phase A voltage angle GE Multilin F60 Feeder Protection System...
  • Page 440 Amps Source 1 phase B current eighth harmonic 10281 SRC 1 Ib Harm[7] Amps Source 1 phase B current ninth harmonic 10282 SRC 1 Ib Harm[8] Amps Source 1 phase B current tenth harmonic F60 Feeder Protection System GE Multilin...
  • Page 441 Amps Source 2 phase A current fifth harmonic 10344 SRC 2 Ia Harm[4] Amps Source 2 phase A current sixth harmonic 10345 SRC 2 Ia Harm[5] Amps Source 2 phase A current seventh harmonic GE Multilin F60 Feeder Protection System...
  • Page 442 Source 2 phase C current second harmonic 10407 SRC 2 Ic Harm[1] Amps Source 2 phase C current third harmonic 10408 SRC 2 Ic Harm[2] Amps Source 2 phase C current fourth harmonic A-10 F60 Feeder Protection System GE Multilin...
  • Page 443 23 actual value 13550 DCMA Inputs 24 Value dcmA input 24 actual value 13552 RTD Inputs 1 Value RTD input 1 actual value 13553 RTD Inputs 2 Value RTD input 2 actual value GE Multilin F60 Feeder Protection System A-11...
  • Page 444 RTD Inputs 46 Value RTD input 46 actual value 13598 RTD Inputs 47 Value RTD input 47 actual value 13599 RTD Inputs 48 Value RTD input 48 actual value 24459 Active Setting Group Current setting group A-12 F60 Feeder Protection System GE Multilin...
  • Page 445: Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 GE Multilin F60 Feeder Protection System A-13...
  • Page 446 A.1 PARAMETER LISTS APPENDIX A A-14 F60 Feeder Protection System GE Multilin...
  • Page 447: Modbus Rtu Protocol

    Broadcast mode is only recognized when associated with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored. GE Multilin F60 Feeder Protection System...
  • Page 448: Algorithm

    No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC F60 Feeder Protection System GE Multilin...
  • Page 449: Modbus Function Codes

    125. See the Modbus memory map table for exact details on the data registers. Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The F60 interpretation allows either function code to be used for reading one or more consecutive data registers.
  • Page 450: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high F60 Feeder Protection System GE Multilin...
  • Page 451: Store Multiple Settings (Function Code 10H

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte GE Multilin F60 Feeder Protection System...
  • Page 452: File Transfers

    Cleared Date to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT F60 Feeder Protection System GE Multilin...
  • Page 453 READING FAULT REPORT FILES Fault report data has been available via the F60 file retrieval mechanism since UR firmware version 2.00. The file name is faultReport#####.htm. The ##### refers to the fault report record number. The fault report number is a counter that indicates how many fault reports have ever occurred.
  • Page 454: Modbus Password Operation

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the F60, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 455: Memory Mapping

    0 (Off) 0419 Virtual Input 26 State 0 to 1 F108 0 (Off) 041A Virtual Input 27 State 0 to 1 F108 0 (Off) 041B Virtual Input 28 State 0 to 1 F108 0 (Off) GE Multilin F60 Feeder Protection System...
  • Page 456 ...Repeated for Digital Counter 7 0838 ...Repeated for Digital Counter 8 FlexStates (Read Only) 0900 FlexState Bits (16 items) 0 to 65535 F001 Element States (Read Only) 1000 Element Operate States (64 items) 0 to 65535 F502 B-10 F60 Feeder Protection System GE Multilin...
  • Page 457 Frequency Rate of Change 1 -327.67 to 327.67 Hz/s 0.01 F002 16E1 Reserved (3 items) 0 to 65535 F001 16E4 ...Repeated for Frequency Rate of Change 2 16E8 ...Repeated for Frequency Rate of Change 3 GE Multilin F60 Feeder Protection System B-11...
  • Page 458 Source 1 Auxiliary Voltage Magnitude 0 to 999999.999 0.001 F060 1A22 Source 1 Auxiliary Voltage Angle -359.9 to 0 degrees F002 1A23 Source 1 Zero Sequence Voltage Magnitude 0 to 999999.999 0.001 F060 B-12 F60 Feeder Protection System GE Multilin...
  • Page 459 0.001 F060 1D08 Reserved (8 items) F001 1D10 ...Repeated for Source 2 1D20 ...Repeated for Source 3 1D30 ...Repeated for Source 4 1D40 ...Repeated for Source 5 1D50 ...Repeated for Source 6 GE Multilin F60 Feeder Protection System B-13...
  • Page 460 Breaker flashover 1 side 1 source 0 to 5 F167 0 (SRC 1) 21A8 Breaker flashover 1 side 2 source 0 to 6 F211 0 (None) 21A9 Breaker flashover 1 status closed A 0 to 65535 F300 B-14 F60 Feeder Protection System GE Multilin...
  • Page 461 ...Repeated for Hi-Z RMS Capture 4 Fault Location (Read Only) (5 modules) 2340 Fault 1 Prefault Phase A Current Magnitude 0 to 999999.999 0.001 F060 2342 Fault 1 Prefault Phase A Current Angle -359.9 to 0 degrees F002 GE Multilin F60 Feeder Protection System B-15...
  • Page 462 IEC 61850 GGIO5 configuration (read/write setting registers) 26B0 IEC 61850 GGIO5 uinteger input 1 operand F612 26B1 IEC 61850 GGIO5 uinteger input 2 operand F612 26B2 IEC 61850 GGIO5 uinteger input 3 operand F612 B-16 F60 Feeder Protection System GE Multilin...
  • Page 463 Oscillography Number of Triggers 0 to 65535 F001 3001 Oscillography Available Records 0 to 65535 F001 3002 Oscillography Last Cleared Date 0 to 400000000 F050 3004 Oscillography Number Of Cycles Per Record 0 to 65535 F001 GE Multilin F60 Feeder Protection System B-17...
  • Page 464 DCMA Inputs 17 Value -9999999 to 9999999 F004 34E2 DCMA Inputs 18 Value -9999999 to 9999999 F004 34E4 DCMA Inputs 19 Value -9999999 to 9999999 F004 34E6 DCMA Inputs 20 Value -9999999 to 9999999 F004 B-18 F60 Feeder Protection System GE Multilin...
  • Page 465 -32768 to 32767 °C F002 351D RTD Input 46 Value -32768 to 32767 °C F002 351E RTD Input 47 Value -32768 to 32767 °C F002 351F RTD Input 48 Value -32768 to 32767 °C F002 GE Multilin F60 Feeder Protection System B-19...
  • Page 466 DNP Address 0 to 65519 F001 409D Reserved 0 to 1 F001 409E DNP Client Addresses (2 items) 0 to 4294967295 F003 40A3 TCP Port Number for the Modbus protocol 1 to 65535 F001 B-20 F60 Feeder Protection System GE Multilin...
  • Page 467 4148 Ethernet switch IP address 0 to 4294967295 F003 3232235778 414A Ethernet switch Modbus IP port number 1 to 65535 F001 414B Ethernet switch Port 1 Events 0 to 1 F102 0 (Disabled) GE Multilin F60 Feeder Protection System B-21...
  • Page 468 Oscillography Analog Channel n (16 items) 0 to 65535 F600 4200 Oscillography Digital Channel n (63 items) 0 to 65535 F300 Trip and Alarm LEDs (Read/Write Setting) 4260 Trip LED Input FlexLogic Operand 0 to 65535 F300 B-22 F60 Feeder Protection System GE Multilin...
  • Page 469 ...Repeated for User-Programmable LED 33 42C2 ...Repeated for User-Programmable LED 34 42C4 ...Repeated for User-Programmable LED 35 42C6 ...Repeated for User-Programmable LED 36 42C8 ...Repeated for User-Programmable LED 37 42CA ...Repeated for User-Programmable LED 38 GE Multilin F60 Feeder Protection System B-23...
  • Page 470 Source 1 Auxiliary VT 0 to 63 F400 4587 ...Repeated for Source 2 458E ...Repeated for Source 3 4595 ...Repeated for Source 4 459C ...Repeated for Source 5 45A3 ...Repeated for Source 6 B-24 F60 Feeder Protection System GE Multilin...
  • Page 471 F001 47AB Synchrocheck 1 Live V2 Minimum Voltage 0 to 1.25 0.01 F001 47AC Synchrocheck 1 Target 0 to 2 F109 0 (Self-reset) 47AD Synchrocheck 1 Events 0 to 1 F102 0 (Disabled) GE Multilin F60 Feeder Protection System B-25...
  • Page 472 0 to 65535 F300 4E29 User Programmable Pushbutton 1 Set 0 to 65535 F300 4E2A ...Repeated for User Programmable Pushbutton 2 4E54 ...Repeated for User Programmable Pushbutton 3 4E7E ...Repeated for User Programmable Pushbutton 4 B-26 F60 Feeder Protection System GE Multilin...
  • Page 473 ...Repeated for RTD Input 36 56AC ...Repeated for RTD Input 37 56BF ...Repeated for RTD Input 38 56D2 ...Repeated for RTD Input 39 56E5 ...Repeated for RTD Input 40 56F8 ...Repeated for RTD Input 41 GE Multilin F60 Feeder Protection System B-27...
  • Page 474 Phase Time Overcurrent 1 Voltage Restraint 0 to 1 F102 0 (Disabled) 5908 Phase TOC 1 Block For Each Phase (3 items) 0 to 65535 F300 590B Phase Time Overcurrent 1 Target 0 to 2 F109 0 (Self-reset) B-28 F60 Feeder Protection System GE Multilin...
  • Page 475 5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 0.01 F001 5C04 Neutral Instantaneous Overcurrent 1 Reset Delay 0 to 600 0.01 F001 5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 65535 F300 GE Multilin F60 Feeder Protection System B-29...
  • Page 476 ...Repeated for Ground Instantaneous Overcurrent 11 5EB0 ...Repeated for Ground Instantaneous Overcurrent 12 Incipient cable fault detector actual values (read only) 5EC0 Incipient cable fault detector 1 phase A counter 0 to 65535 F001 B-30 F60 Feeder Protection System GE Multilin...
  • Page 477 Autoreclose 1 Block Time Upon Manual Close 0 to 655.35 0.01 F001 1000 624B Autoreclose 1 Dead Time Shot 1 0 to 655.35 0.01 F001 624C Autoreclose 1 Dead Time Shot 2 0 to 655.35 0.01 F001 GE Multilin F60 Feeder Protection System B-31...
  • Page 478 Negative Sequence Overvoltage Events 0 to 1 F102 0 (Disabled) Overfrequency (Read/Write Setting) (4 modules) 64D0 Overfrequency 1 Function 0 to 1 F102 0 (Disabled) 64D1 Overfrequency 1 Block 0 to 65535 F300 B-32 F60 Feeder Protection System GE Multilin...
  • Page 479 7041 Phase Overvoltage 1 Source 0 to 5 F167 0 (SRC 1) 7042 Phase Overvoltage 1 Pickup 0 to 3 0.001 F001 1000 7043 Phase Overvoltage 1 Delay 0 to 600 0.01 F001 GE Multilin F60 Feeder Protection System B-33...
  • Page 480 Breaker 1 Arcing Current Function 0 to 1 F102 0 (Disabled) 72C1 Breaker 1 Arcing Current Source 0 to 5 F167 0 (SRC 1) 72C2 Breaker 1 Arcing Current Initiate A 0 to 65535 F300 B-34 F60 Feeder Protection System GE Multilin...
  • Page 481 754C Disconnect switch 1 phase B opened 0 to 65535 F300 754D Disconnect switch 1 phase C closed 0 to 65535 F300 754E Disconnect switch 1 phase C opened 0 to 65535 F300 GE Multilin F60 Feeder Protection System B-35...
  • Page 482 ...Repeated for User Programmable Pushbutton 3 7BE1 ...Repeated for User Programmable Pushbutton 4 7C0C ...Repeated for User Programmable Pushbutton 5 7C37 ...Repeated for User Programmable Pushbutton 6 7C62 ...Repeated for User Programmable Pushbutton 7 B-36 F60 Feeder Protection System GE Multilin...
  • Page 483 Auxiliary Undervoltage 1 Function 0 to 1 F102 0 (Disabled) 7F61 Auxiliary Undervoltage 1 Signal Source 0 to 5 F167 0 (SRC 1) 7F62 Auxiliary Undervoltage 1 Pickup 0 to 3 0.001 F001 GE Multilin F60 Feeder Protection System B-37...
  • Page 484 Breaker Failure 1 Breaker Test On 0 to 65535 F300 8612 Breaker Failure 1 Phase Amp Hiset Pickup 0.001 to 30 0.001 F001 1050 8613 Breaker Failure 1 Neutral Amp Hiset Pickup 0.001 to 30 0.001 F001 1050 B-38 F60 Feeder Protection System GE Multilin...
  • Page 485 ...Repeated for Digital Element 19 8B7C ...Repeated for Digital Element 20 8B90 ...Repeated for Digital Element 21 8BA4 ...Repeated for Digital Element 22 8BB8 ...Repeated for Digital Element 23 8BCC ...Repeated for Digital Element 24 GE Multilin F60 Feeder Protection System B-39...
  • Page 486 0 to 1 F102 0 (Disabled) 8E18 Reserved (8 items) F001 8E20 ...Repeated for Trip Bus 2 8E40 ...Repeated for Trip Bus 3 8E60 ...Repeated for Trip Bus 4 8E80 ...Repeated for Trip Bus 5 B-40 F60 Feeder Protection System GE Multilin...
  • Page 487 Output 1 Range 0 to 2 F522 0 (–1 to 1 mA) 9302 dcmA Output 1 Minimum –90 to 90 0.001 F004 9304 dcmA Output 1 Maximum –90 to 90 0.001 F004 1000 GE Multilin F60 Feeder Protection System B-41...
  • Page 488 ...Repeated for Direct Input/Output 24 9520 ...Repeated for Direct Input/Output 25 952C ...Repeated for Direct Input/Output 26 9538 ...Repeated for Direct Input/Output 27 9544 ...Repeated for Direct Input/Output 28 9550 ...Repeated for Direct Input/Output 29 B-42 F60 Feeder Protection System GE Multilin...
  • Page 489 F500 9BB0 Teleprotection Input 1 States, 1 per register (16 items) 0 to 1 F108 0 (Off) 9BC0 Teleprotection Input 2 States, 1 per register (16 items) 0 to 1 F108 0 (Off) GE Multilin F60 Feeder Protection System B-43...
  • Page 490 0 to 1 F102 0 (Disabled) A706 Reserved (4 items) F001 A70A ...Repeated for Non-Volatile Latch 2 A714 ...Repeated for Non-Volatile Latch 3 A71E ...Repeated for Non-Volatile Latch 4 A728 ...Repeated for Non-Volatile Latch 5 B-44 F60 Feeder Protection System GE Multilin...
  • Page 491 IEC 61850 received analog settings (read/write) AA00 IEC 61850 GOOSE analog 1 default value –1000000 to 1000000 0.001 F060 1000 AA02 IEC 61850 GOOSE analog input 1 mode 0 to 1 F491 0 (Default Value) GE Multilin F60 Feeder Protection System B-45...
  • Page 492 Operand for IEC 61850 XSWI1.ST.Loc status 0 to 65535 F300 AED0 Command to clear XSWI1 OpCnt (operation counter) 0 to 1 F126 0 (No) AED1 Repeated for IEC 61850 XSWI2 AED3 Repeated for IEC 61850 XSWI3 B-46 F60 Feeder Protection System GE Multilin...
  • Page 493 ...Repeated for IEC 61850 GGIO4 analog input 23 AFB1 ...Repeated for IEC 61850 GGIO4 analog input 24 AFB8 ...Repeated for IEC 61850 GGIO4 analog input 25 AFBF ...Repeated for IEC 61850 GGIO4 analog input 26 GE Multilin F60 Feeder Protection System B-47...
  • Page 494 IEC 61850 MMXU PPV.phsCA Deadband 1 0.001 to 100 0.001 F003 10000 B0D0 IEC 61850 MMXU PhV.phsADeadband 1 0.001 to 100 0.001 F003 10000 B0D2 IEC 61850 MMXU PhV.phsB Deadband 1 0.001 to 100 0.001 F003 10000 B-48 F60 Feeder Protection System GE Multilin...
  • Page 495 F001 B5C6 IEC 61850 Configurable GOOSE VLAN ID 0 to 4095 F001 B5C7 IEC 61850 Configurable GOOSE ETYPE APPID 0 to 16383 F001 B5C8 IEC 61850 Configurable GOOSE ConfRev 1 to 4294967295 F003 GE Multilin F60 Feeder Protection System B-49...
  • Page 496 ...Repeated for Contact Input 27 BBD8 ...Repeated for Contact Input 28 BBE0 ...Repeated for Contact Input 29 BBE8 ...Repeated for Contact Input 30 BBF0 ...Repeated for Contact Input 31 BBF8 ...Repeated for Contact Input 32 B-50 F60 Feeder Protection System GE Multilin...
  • Page 497 ...Repeated for Contact Input 81 BD88 ...Repeated for Contact Input 82 BD90 ...Repeated for Contact Input 83 BD98 ...Repeated for Contact Input 84 BDA0 ...Repeated for Contact Input 85 BDA8 ...Repeated for Contact Input 86 GE Multilin F60 Feeder Protection System B-51...
  • Page 498 ...Repeated for Virtual Input 32 BFB0 ...Repeated for Virtual Input 33 BFBC ...Repeated for Virtual Input 34 BFC8 ...Repeated for Virtual Input 35 BFD4 ...Repeated for Virtual Input 36 BFE0 ...Repeated for Virtual Input 37 B-52 F60 Feeder Protection System GE Multilin...
  • Page 499 ...Repeated for Virtual Output 19 C1C8 ...Repeated for Virtual Output 20 C1D0 ...Repeated for Virtual Output 21 C1D8 ...Repeated for Virtual Output 22 C1E0 ...Repeated for Virtual Output 23 C1E8 ...Repeated for Virtual Output 24 GE Multilin F60 Feeder Protection System B-53...
  • Page 500 ...Repeated for Virtual Output 73 C378 ...Repeated for Virtual Output 74 C380 ...Repeated for Virtual Output 75 C388 ...Repeated for Virtual Output 76 C390 ...Repeated for Virtual Output 77 C398 ...Repeated for Virtual Output 78 B-54 F60 Feeder Protection System GE Multilin...
  • Page 501 ...Repeated for Contact Output 18 C518 ...Repeated for Contact Output 19 C524 ...Repeated for Contact Output 20 C530 ...Repeated for Contact Output 21 C53C ...Repeated for Contact Output 22 C548 ...Repeated for Contact Output 23 GE Multilin F60 Feeder Protection System B-55...
  • Page 502 ...Repeated for Control Pushbutton 4 C768 ...Repeated for Control Pushbutton 5 C76A ...Repeated for Control Pushbutton 6 C76C ...Repeated for Control Pushbutton 7 Clear Records (Read/Write Setting) C770 Clear Fault Reports operand 0 to 65535 F300 B-56 F60 Feeder Protection System GE Multilin...
  • Page 503 ...Repeated for Direct Input 23 C8EC ...Repeated for Direct Input 24 C8F0 ...Repeated for Direct Input 25 C8F4 ...Repeated for Direct Input 26 C8F8 ...Repeated for Direct Input 27 C8FC ...Repeated for Direct Input 28 GE Multilin F60 Feeder Protection System B-57...
  • Page 504 Direct I/O Ch 1 Unreturned Messages Alarm Threshold 1 to 1000 F001 CAE3 Direct I/O Ch 1 Unreturned Messages Alarm Events 0 to 1 F102 0 (Disabled) CAE4 Reserved (4 items) 1 to 1000 F001 B-58 F60 Feeder Protection System GE Multilin...
  • Page 505 ...Repeated for Remote Input 19 D05E ...Repeated for Remote Input 20 D068 ...Repeated for Remote Input 21 D072 ...Repeated for Remote Input 22 D07C ...Repeated for Remote Input 23 D086 ...Repeated for Remote Input 24 GE Multilin F60 Feeder Protection System B-59...
  • Page 506 ...Repeated for Remote Output 3 D2AC ...Repeated for Remote Output 4 D2B0 ...Repeated for Remote Output 5 D2B4 ...Repeated for Remote Output 6 D2B8 ...Repeated for Remote Output 7 D2BC ...Repeated for Remote Output 8 B-60 F60 Feeder Protection System GE Multilin...
  • Page 507 IEC 61850 GGIO2.CF.SPCSO26.ctlModel Value 0 to 2 F001 D33A IEC 61850 GGIO2.CF.SPCSO27.ctlModel Value 0 to 2 F001 D33B IEC 61850 GGIO2.CF.SPCSO28.ctlModel Value 0 to 2 F001 D33C IEC 61850 GGIO2.CF.SPCSO29.ctlModel Value 0 to 2 F001 GE Multilin F60 Feeder Protection System B-61...
  • Page 508 ...Repeated for Remote Device 13 D3B4 ...Repeated for Remote Device 14 D3B8 ...Repeated for Remote Device 15 D3BC ...Repeated for Remote Device 16 D3C0 ...Repeated for Remote Device 17 D3C4 ...Repeated for Remote Device 18 B-62 F60 Feeder Protection System GE Multilin...
  • Page 509 Setting file template values (read only) ED00 FlexLogic™ displays active 0 to 1 F102 1 (Enabled) ED01 Reserved (6 items) ED07 Last settings change date 0 to 4294967295 F050 ED09 Template bitmask (750 items) 0 to 65535 F001 GE Multilin F60 Feeder Protection System B-63...
  • Page 510: Data Formats

    0 = 1 & 3 Pole, 1 = 1 Pole, 2 = 3 Pole-A, 3 = 3 Pole-B Positive values indicate lagging power factor; negative values indicate leading. F083 ENUMERATION: SELECTOR MODES 0 = Time-Out, 1 = Acknowledge B-64 F60 Feeder Protection System GE Multilin...
  • Page 511 ENUMERATION: NEUTRAL OVERVOLTAGE CURVES ENUMERATION: LOGIC INPUT 0 = Definite Time, 1 = FlexCurve™ A, 2 = FlexCurve™ B, 0 = Disabled, 1 = Input 1, 2 = Input 2 3 = FlexCurve™ C GE Multilin F60 Feeder Protection System B-65...
  • Page 512 Ground Instantaneous Overcurrent 2 Ground Instantaneous Overcurrent 3 Ground Instantaneous Overcurrent 4 F123 ENUMERATION: CT SECONDARY Ground Instantaneous Overcurrent 5 Ground Instantaneous Overcurrent 6 0 = 1 A, 1 = 5 A Ground Instantaneous Overcurrent 7 B-66 F60 Feeder Protection System GE Multilin...
  • Page 513 Autoreclose (three-pole) 1 Non-volatile Latch 14 Autoreclose (three-pole) 2 Non-volatile Latch 15 Autoreclose (three-pole) 3 Non-volatile Latch 16 Autoreclose (three-pole) 4 Frequency Rate of Change 1 Autoreclose (three-pole) 5 Frequency Rate of Change 2 GE Multilin F60 Feeder Protection System B-67...
  • Page 514 RTD Input 37 Digital Element 39 RTD Input 38 Digital Element 40 RTD Input 39 Digital Element 41 RTD Input 40 Digital Element 42 RTD Input 41 Digital Element 43 RTD Input 42 B-68 F60 Feeder Protection System GE Multilin...
  • Page 515 0 = Disabled, 1 = Self-Reset, 2 = Latched F127 F138 ENUMERATION: LATCHED OR SELF-RESETTING ENUMERATION: OSCILLOGRAPHY FILE TYPE 0 = Latched, 1 = Self-Reset 0 = Data File, 1 = Configuration File, 2 = Header File GE Multilin F60 Feeder Protection System B-69...
  • Page 516 Process Bus Trouble null Brick Trouble Field RTD Trouble Field TDR Trouble Remote Device Offline Direct Device Offline Direct Input/Output Ring Break Any Minor Error Any Major Error B-70 F60 Feeder Protection System GE Multilin...
  • Page 517 System Integrity Recovery System Integrity Recovery 06 System Integrity Recovery 07 F155 ENUMERATION: REMOTE DEVICE STATE 0 = Offline, 1 = Online F147 ENUMERATION: LINE LENGTH UNITS 0 = km, 1 = miles GE Multilin F60 Feeder Protection System B-71...
  • Page 518 0 = A, 1 = B, 2 = C ENUMERATION: AUXILIARY VT CONNECTION TYPE 0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca B-72 F60 Feeder Protection System GE Multilin...
  • Page 519 ARCING LOSS OF LOAD DOWNED CONDUCTOR ARCING SUSPECTED ARCING F188 OVERCURRENT ENUMERATION: HI-Z CAPTURE TRIGGER TYPES DOWNED CONDUCTOR EXTERNAL bitmask trigger type None Loss Of Load Arc Suspected Arcing Overcurrent Down Conductor GE Multilin F60 Feeder Protection System B-73...
  • Page 520 5 = SRC 5, 6 = SRC 6 ENUMERATION: DNP SCALE 0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000, 6 = 10000, 7 = 100000, 8 = 0.001 B-74 F60 Feeder Protection System GE Multilin...
  • Page 521 ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS FOR TRANSMISSION MMXU2.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.PPV.phsAB.cVal.ang.f value GOOSE dataset item MMXU2.MX.PPV.phsBC.cVal.mag.f None MMXU2.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind1.q MMXU2.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind1.stVal MMXU2.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind2.q MMXU2.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind2.stVal MMXU2.MX.PhV.phsA.cVal.ang.f ↓ ↓ MMXU2.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind128.q MMXU2.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind128.stVal MMXU2.MX.PhV.phsC.cVal.mag.f MMXU1.MX.TotW.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f GE Multilin F60 Feeder Protection System B-75...
  • Page 522 MMXU4.MX.VA.phsB.cVal.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU3.MX.A.neut.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU3.MX.W.phsB.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f B-76 F60 Feeder Protection System GE Multilin...
  • Page 523 GGIO4.MX.AnIn28.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f GGIO4.MX.AnIn29.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f GGIO4.MX.AnIn30.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GGIO4.MX.AnIn31.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f GGIO4.MX.AnIn32.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f GGIO5.ST.UIntIn1.q MMXU6.MX.A.phsA.cVal.mag.f GGIO5.ST.UIntIn1.stVal MMXU6.MX.A.phsA.cVal.ang.f GGIO5.ST.UIntIn2.q MMXU6.MX.A.phsB.cVal.mag.f GGIO5.ST.UIntIn2.stVal MMXU6.MX.A.phsB.cVal.ang.f GGIO5.ST.UIntIn3.q MMXU6.MX.A.phsC.cVal.mag.f GGIO5.ST.UIntIn3.stVal MMXU6.MX.A.phsC.cVal.ang.f GGIO5.ST.UIntIn4.q MMXU6.MX.A.neut.cVal.mag.f GGIO5.ST.UIntIn4.stVal MMXU6.MX.A.neut.cVal.ang.f GGIO5.ST.UIntIn5.q MMXU6.MX.W.phsA.cVal.mag.f GGIO5.ST.UIntIn5.stVal MMXU6.MX.W.phsB.cVal.mag.f GGIO5.ST.UIntIn6.q MMXU6.MX.W.phsC.cVal.mag.f GGIO5.ST.UIntIn6.stVal GE Multilin F60 Feeder Protection System B-77...
  • Page 524 GGIO3.MX.AnIn2.mag.f GGIO3.ST.UIntIn9.q GGIO3.MX.AnIn3.mag.f GGIO3.ST.UIntIn9.stVal GGIO3.MX.AnIn4.mag.f GGIO3.ST.UIntIn10.q GGIO3.MX.AnIn5.mag.f GGIO3.ST.UIntIn10.stVal GGIO3.MX.AnIn6.mag.f GGIO3.ST.UIntIn11.q GGIO3.MX.AnIn7.mag.f GGIO3.ST.UIntIn11.stVal GGIO3.MX.AnIn8.mag.f GGIO3.ST.UIntIn12.q GGIO3.MX.AnIn9.mag.f GGIO3.ST.UIntIn12.stVal GGIO3.MX.AnIn10.mag.f GGIO3.ST.UIntIn13.q GGIO3.MX.AnIn11.mag.f GGIO3.ST.UIntIn13.stVal GGIO3.MX.AnIn12.mag.f GGIO3.ST.UIntIn14.q GGIO3.MX.AnIn13.mag.f GGIO3.ST.UIntIn14.stVal GGIO3.MX.AnIn14.mag.f GGIO3.ST.UIntIn15.q GGIO3.MX.AnIn15.mag.f GGIO3.ST.UIntIn15.stVal GGIO3.MX.AnIn16.mag.f GGIO3.ST.UIntIn16.q GGIO3.MX.AnIn17.mag.f GGIO3.ST.UIntIn16.stVal GGIO3.MX.AnIn18.mag.f B-78 F60 Feeder Protection System GE Multilin...
  • Page 525 First [32] END Second [34] NOT (1 INPUT) Third [36] 2 INPUT XOR (0) [38] LATCH SET/RESET (2 inputs) Fourth [40] OR (2 to 16 inputs) Last [42] AND (2 to 16 inputs) GE Multilin F60 Feeder Protection System B-79...
  • Page 526 IDs. The operate bit for element ID 13TH 25TH X is bit [X mod 16] in register [X/16]. F515 ENUMERATION ELEMENT INPUT MODE 0 = Signed, 1 = Absolute B-80 F60 Feeder Protection System GE Multilin...
  • Page 527 ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION Enumeration Remote double-point status input bitmask default variation None Remote input 1 Remote input 2 Remote input 3 ↓ ↓ Remote input 64 GE Multilin F60 Feeder Protection System B-81...
  • Page 528 UR_UINT16: FLEXINTEGER PARAMETER This 16-bit value corresponds to the Modbus address of the Enumeration Configurable GOOSE retransmission scheme selected FlexInteger paramter. Only certain values may be used Heartbeat as FlexIntegers. Aggressive Medium Relaxed B-82 F60 Feeder Protection System GE Multilin...
  • Page 529: Iec 61850

    The F60 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks. The TP4/CLNP profile requires the F60 to have a network address or Network Service Access Point (NSAP) to establish a communication link. The TCP/IP profile requires the F60 to have an IP address to establish communications. These addresses are located in the menu.
  • Page 530: Server Data Organization

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the F60 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 531: Mmxu: Analog Measured Values

    A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a F60 current and voltage source. There is one MMXU available for each con- figurable source (programmed in the menu).
  • Page 532 The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the F60 protection elements, these flags take their values from the pickup and operate FlexLogic™ operands for the corresponding element.
  • Page 533: Server Features And Configuration

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the F60. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
  • Page 534: Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the F60 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the F60. This frees up the con- nection to be used by other clients.
  • Page 535: Generic Substation Event Services: Gsse And Goose

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the F60 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 536 The F60 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 537: Ethernet Mac Address For Gsse/Goose

    REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic™ equations or other settings. The F60 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 538: Gsse Id And Goose Id Settings

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the F60 is configured to use an automated multicast MAC scheme. If the F60 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 539: Iec 61850 Implementation Via Enervista Ur Setup

    An ICD file is generated for the F60 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 540: Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the F60 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 541: About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 542 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. C-14 F60 Feeder Protection System GE Multilin...
  • Page 543 RptEnabled Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure 0–4: ICD FILE STRUCTURE, IED NODE GE Multilin F60 Feeder Protection System C-15...
  • Page 544 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure 0–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE C-16 F60 Feeder Protection System GE Multilin...
  • Page 545: Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline F60 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 546 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE C-18 F60 Feeder Protection System GE Multilin...
  • Page 547 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. GE Multilin F60 Feeder Protection System C-19...
  • Page 548: Importing An Scd File With Enervista Ur Setup

    Figure 0–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the F60 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 549 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 550: Acsi Conformance

    Setting group control REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion C-22 F60 Feeder Protection System GE Multilin...
  • Page 551: Acsi Services Conformance Statement

    SERVER/ UR FAMILY PUBLISHER SERVER (CLAUSE 6) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 7) Associate Abort Release LOGICAL DEVICE (CLAUSE 8) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 9) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 10) GetDataValues SetDataValues GetDataDirectory GetDataDefinition GE Multilin F60 Feeder Protection System C-23...
  • Page 552 (qchg) S27-3 data-update (dupd) GetURCBValues SetURCBValues LOGGING (CLAUSE 14) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4) GOOSE-CONTROL-BLOCK SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK SendGSSEMessage GetReference C-24 F60 Feeder Protection System GE Multilin...
  • Page 553 (QueryLogByTime or QueryLogAfter) c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) GE Multilin F60 Feeder Protection System C-25...
  • Page 554: Logical Nodes

    RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing C-26 F60 Feeder Protection System GE Multilin...
  • Page 555 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer GE Multilin F60 Feeder Protection System C-27...
  • Page 556 ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-28 F60 Feeder Protection System GE Multilin...
  • Page 557: Iec 60870-5-104

    Address Field of the Link: Balanced Transmision Not Present (Balanced Transmission Only) Unbalanced Transmission One Octet Two Octets Structured Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin F60 Feeder Protection System...
  • Page 558 <18> := Packed start events of protection equipment with time tag M_EP_TB_1 <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1 <20> := Packed single-point information with status change detection M_SP_NA_1 F60 Feeder Protection System GE Multilin...
  • Page 559 <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1 <104> := Test command C_TS_NA_1 <105> := Reset process command C_RP_NA_1 <106> := Delay acquisition command C_CD_NA_1 <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin F60 Feeder Protection System...
  • Page 560 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 F60 Feeder Protection System GE Multilin...
  • Page 561 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin F60 Feeder Protection System...
  • Page 562 P_ME_NC_1 <113> P_AC_NA_1 <120> F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization: Remote initialization Cyclic Data Transmission: Cyclic data transmission Read Procedure: Read procedure F60 Feeder Protection System GE Multilin...
  • Page 563 Mode A: Local freeze with spontaneous transmission Mode B: Local freeze with counter interrogation Mode C: Freeze and transmit by counter-interrogation commands Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously Counter read Counter freeze without reset GE Multilin F60 Feeder Protection System...
  • Page 564 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs F60 Feeder Protection System GE Multilin...
  • Page 565: Iec 60870-5-104 Point List

    D.1.2 IEC 60870-5-104 POINT LIST The IEC 60870-5-104 data points are configured through the SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin F60 Feeder Protection System...
  • Page 566 D.1 IEC 60870-5-104 APPENDIX D D-10 F60 Feeder Protection System GE Multilin...
  • Page 567: Device Profile Document

    Transmitted: 292 Transmitted: configurable up to 2048 Received: Received: 2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries: None None Fixed at 3 Configurable Configurable Requires Data Link Layer Confirmation: Never Always Sometimes Configurable GE Multilin F60 Feeder Protection System...
  • Page 568 FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. F60 Feeder Protection System GE Multilin...
  • Page 569 Configurable (attach explanation) Configurable (attach explanation) Default Object: 16 Bits (Counter 8) Default Variation: 1 32 Bits (Counters 0 to 7, 9) Point-by-point list attached Other Value: _____ Point-by-point list attached Sends Multi-Fragment Responses: GE Multilin F60 Feeder Protection System...
  • Page 570: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F60 is not restarted, but the DNP process is restarted. F60 Feeder Protection System GE Multilin...
  • Page 571 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F60 is not restarted, but the DNP process is restarted. GE Multilin F60 Feeder Protection System...
  • Page 572 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F60 is not restarted, but the DNP process is restarted. F60 Feeder Protection System GE Multilin...
  • Page 573 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the F60 is not restarted, but the DNP process is restarted. GE Multilin F60 Feeder Protection System...
  • Page 574: Dnp Point Lists

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 F60 Feeder Protection System GE Multilin...
  • Page 575: Binary And Control Relay Output

    Virtual Input 27 Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin F60 Feeder Protection System...
  • Page 576: Counters

    Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. F60 Digital Counter values are represented as 32-bit inte- gers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.
  • Page 577: Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin F60 Feeder Protection System E-11...
  • Page 578 E.2 DNP POINT LISTS APPENDIX E E-12 F60 Feeder Protection System GE Multilin...
  • Page 579: Change Notes

    31 August 2007 URX-246 1601-0093-R3 5.4x 17 October 2007 URX-251 1601-0093-S1 5.5x 7 December 2007 URX-253 1601-0093-S2 5.5x 22 February 2008 URX-258 1601-0093-S3 5.5x 12 March 2008 URX-260 1601-0093-T1 5.6x 27 June 2008 08-0390 GE Multilin F60 Feeder Protection System...
  • Page 580: Changes To The F60 Manual

    09-0938 1601-0109-U2 5.7x 30 September 2009 09-1165 1601-0109-V1 5.8x 29 May 2010 09-1457 F.1.2 CHANGES TO THE F60 MANUAL Table F–1: MAJOR UPDATES FOR F60 MANUAL REVISION V1 PAGE PAGE CHANGE DESCRIPTION (U2) (V1) Title Title Update Manual part number to 1601-0093-V1...
  • Page 581 Added SECURITY chapter A-13 Added FLEXINTEGER ITEMS section Update Updated MODBUS MEMORY MAP section B-61 B-64 Update Updated DATA FORMATS section Table F–4: MAJOR UPDATES FOR F60 MANUAL REVISION T1 (Sheet 1 of 2) PAGE PAGE CHANGE DESCRIPTION (S3) (T1) Title Title...
  • Page 582 F.1 CHANGE NOTES APPENDIX F Table F–4: MAJOR UPDATES FOR F60 MANUAL REVISION T1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (S3) (T1) 5-11 Added DUAL PERMISSION SECURITY ACCESS section 5-20 5-21 Update Updated IEC 61850 PROTOCOL section 5-67...
  • Page 583 APPENDIX F F.1 CHANGE NOTES Table F–7: MAJOR UPDATES FOR F60 MANUAL REVISION S1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (R3) (S1) 5-45 5-47 Update Updated USER-PROGRAMMABLE PUSHBUTTONS section 5-65 5-69 Update Updated BREAKERS section 5-73 Added DISCONNECT SWITCHES section...
  • Page 584 F.1 CHANGE NOTES APPENDIX F Table F–10: MAJOR UPDATES FOR F60 MANUAL REVISION R1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (P2) (R1) Update Updated RELAY SELF-TESTS section Added FAULT TYPE DETERMINATION section Update Updated MODBUS PASSWORD OPERATION section...
  • Page 585 APPENDIX F F.1 CHANGE NOTES Table F–12: MAJOR UPDATES FOR F60 MANUAL REVISION P1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (N2) (P1) 5-109 5-110 Update Updated WATTMETRIC ZERO-SEQUENCE DIRECTIONAL section 5-131 5-132 Update Updated PHASE OVERVOLTAGE sub-section Update...
  • Page 586: Abbreviations

    MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A ... MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set MVA_B ... MegaVolt-Ampere (phase B) FLA....Full Load Current MVA_C... MegaVolt-Ampere (phase C) FO ....Fiber Optic F60 Feeder Protection System GE Multilin...
  • Page 587 ....With Option RST ....Reset WRT....With Respect To RSTR ..... Restrained RTD....Resistance Temperature Detector X .....Reactance RTU....Remote Terminal Unit XDUCER..Transducer RX (Rx) ..Receive, Receiver XFMR....Transformer s ..... second Z......Impedance, Zone S..... Sensitive GE Multilin F60 Feeder Protection System...
  • Page 588: Warranty

    24 months from date of shipment from factory. In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay providing the warrantor determined that it is defective and it is returned with all transportation charges prepaid to an authorized service centre or the factory.
  • Page 589: Index

    AUXILIARY OVERVOLTAGE C37.94SM COMMUNICATIONS ........3-39 FlexLogic™ operands ............ 5-92 CE APPROVALS .............. 2-20 logic ................5-162 CHANGES TO F60 MANUAL..........F-2 Modbus registers ............B-37 settings ............... 5-162 CHANGES TO MANUAL ....... F-4, F-5, F-6, F-7 CHANNEL COMMUNICATION .......... 3-30 specifications ..............
  • Page 590 DIRECT DEVICES CT INPUTS ............3-14, 5-6, 5-71 actual values ..............6-8 CURRENT BANK ............. 5-71 Modbus registers ............B-20 CURRENT DEMAND ............5-45 settings ................ 5-223 CURRENT HARMONICS ......... 2-14, 6-19 DIRECT I/O F60 Feeder Protection System GE Multilin...
  • Page 591 FAX NUMBERS ..............1-1 ENERVISTA UR SETUP FEATURES ................ 2-1 creating a site list ............4-1 FIRMWARE REVISION ............. 6-26 event recorder ..............4-2 FIRMWARE UPGRADES ............ 4-2 firmware upgrades ............4-2 FLASH MESSAGES ............5-12 GE Multilin F60 Feeder Protection System...
  • Page 592 Modbus registers ..........B-17, B-39 settings ................. 5-57 specifications..............2-12 FLEXCURVES™ G.703 ............ 3-31, 3-32, 3-33, 3-36 equation ..............5-119 GE TYPE IAC CURVES ..........5-118 Modbus registers ..........B-26, B-44 GROUND CURRENT METERING ........6-15 settings ................. 5-83 GROUND IOC specifications..............2-12 FlexLogic™...
  • Page 593 MODEL INFORMATION ............ 6-26 MODIFICATION FILE NUMBER ........6-26 MODULE FAILURE ERROR ..........7-5 MODULES LAMPTEST ................ 7-3 communications ............. 3-25 LANGUAGE ..............5-12 CT/VT ..............3-13, 5-6 LASER MODULE ............. 3-30 direct inputs/outputs ............3-30 GE Multilin F60 Feeder Protection System...
  • Page 594 ..............2-10, 5-158 NEUTRAL TIME OVERCURRENT see entry for NEUTRAL TOC NEUTRAL TOC FlexLogic™ operands ............ 5-95 logic ................5-127 PANEL CUTOUT ............3-1, 3-2 Modbus registers ............B-29 PARITY ................5-16 settings ............... 5-127 F60 Feeder Protection System GE Multilin...
  • Page 595 POWER SYSTEM with fiber interface ............3-36 Modbus registers ............B-25 RS485 PREFERENCES communications ............. 3-24 Modbus registers ............B-20 configuration ..............1-7 PROCESS BUS description ..............3-26 overview ............... 3-15 specifications ..............2-17 GE Multilin F60 Feeder Protection System...
  • Page 596 EnerVista UR Setup data ............ 4-11, 4-12, 8-13, 8-14 SOURCE FREQUENCY ............ 6-18 overview ............... 4-10, 8-12 SOURCE TRANSFER SCHEMES ........5-155 rules ..............4-12, 8-14 SOURCES TRACKING FREQUENCY ........6-20, B-38 viii F60 Feeder Protection System GE Multilin...
  • Page 597 WEBSITE ................1-1 FlexLogic™ operands ............ 5-99 Modbus registers ..........B-26, B-36 settings ................. 5-52 specifications ..............2-13 USER-PROGRAMMABLE SELF TESTS ZERO SEQUENCE CORE BALANCE ........ 3-14 Modbus registers ............B-24 settings ................. 5-49 GE Multilin F60 Feeder Protection System...
  • Page 598 INDEX F60 Feeder Protection System GE Multilin...

Table of Contents