Trip Lockout Function - ABB REF610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF610:
Table of Contents

Advertisement

1MRS755535
5.1.6.
Feeder Protection Relay
Technical Reference Manual - ANSI Version
PO1
TCS
SO2
HW
SW
SGF1/8
TRIP-CIRCUIT
SUPERVISION
TCS STATE WARNING
Fig. 5.1.5.-1
Connecting the trip-circuit supervision using two external contacts and
the external resistor in the trip circuit

Trip lockout function

The trip lockout function is used to prevent accidental closing of the circuit breaker
after a trip. The trip lockout function must be locally reset with a separate reset
command before the circuit breaker can be closed again. This function is useful
when the trip output contact of the relay is latched or the open circuit of the circuit
breaker remains activated.
The trip lockout function is selected in SGF1. When selected, PO3 is dedicated to
this function. As long as no trip occurs, PO3 is closed.
Every signal which has been routed to PO3 via the output signal matrix activates the
trip lockout function and opens the contacts of PO3. When the contacts have
opened, they are locked into the open state.
The trip lockout function can also be activated externally, via a digital input. The
trip lockout function can be reset via a digital input, the HMI or SPA parameter
V103, but not before the signal which activated the function has been reset.
In case of loss of auxiliary power when the trip lockout function is in use, the
contacts of PO3 return to the same state as before the loss, provided that the battery
has been inserted and is charged. If no battery has been inserted, the trip lockout
function is activated and the contacts of PO3 remain open when the auxiliary power
is switched on again.
X4.1
18
+
R ext
19
16
17
-
8
7
6
HMI
REF610
REF610
R s
A040329_2