Sgb1...Sgb5 - ABB REF610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF610:
Table of Contents

Advertisement

1MRS755535
Switch
Function
SGF5/7
Selection of the latching feature for programmable LED7
SGF5/8
Selection of the latching feature for programmable LED8
When the switch is in position 0 and the signal routed to the LED is reset, the programmable
*
LED is cleared.
When the switch is in position 1, the programmable LED remains lit although the signal
*
routed to the LED is reset.
A latched programmable LED can be cleared either via the HMI, a digital input or the serial bus.
ΣSGF5
Table 5.1.4.10.-7

SGB1...SGB5

Switch
Function
SGB1...5/1
0 = targets are not cleared by the digital input signal
*
1 = targets are cleared by the digital input signal
*
SGB1...5/2
0 = targets are not cleared and latched output contacts are not unlatched by the digital input
*
signal
1 = targets are cleared and latched output contacts are unlatched by the digital input signal
*
SGB1...5/3
0 = targets and memorized values are not cleared and latched output contacts are not
*
unlatched by the digital input signal
1 = targets and memorized values are cleared and latched output contacts are unlatched by
*
the digital input signal
SGB1...5/4
Switching between setting groups 1 and 2 by using the digital input
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input. When the digital input is energized,
*
setting group 2 is activated, if not, setting group 1 is activated.
SGB1...5/5
Time synchronization by the digital input signal
SGB1...5/6
External tripping by the digital input signal
SGB1...5/7
External triggering of the CBFAIL by the digital input signal
SGB1...5/8
External triggering of the trip lockout by the digital input signal
SGB1...5/9
External arc signalling by the digital input signal
SGB1...5/10
Resetting of the trip lockout by the digital input signal
SGB1...5/11
Blocking of tripping of element 51P by the digital input signal
SGB1...5/12
Blocking of tripping of element 50P-1 by the digital input signal
SGB1...5/13
Blocking of tripping of element 51N by the digital input signal
SGB1...5/14
Blocking of tripping of element 50N by the digital input signal
SGB1...5/15
Blocking of tripping of element 46 by the digital input signal
SGB1...5/16
External AR disable by the digital input signal
SGB1...5/17
External disable of CB reclosing by the digital input signal
SGB1...5/18
CB position open
Feeder Protection Relay
Technical Reference Manual - ANSI Version
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
When SGB1...5/4 is set to 1, it is important that the switch has the same setting
in both setting groups.
REF610
REF610
Default setting
0
0
0
Default setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
63