ABB REF610 Technical Reference Manual page 170

Feeder protection relay
Hide thumbs Also See for REF610:
Table of Contents

Advertisement

REF610
REF610
170
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Variable
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Checksum, SGR 5
Checksum, SGR 6
Checksum, SGR 7
Checksum, SGR 8
Checksum, SGL 1
Checksum, SGL 2
Checksum, SGL 3
Checksum, SGL 4
Checksum, SGL 5
Checksum, SGL 6
Checksum, SGL 7
Checksum, SGL 8
Table 8.-3
Control parameters
Description
Rated frequency
Time setting range for
demand values in
minutes
Non-volatile memory
settings
Time setting for disabling
new trip targets on the
LCD
Trip-circuit supervision
Remote control of settings V150
Unit address of the relay V200
Data transfer rate (SPA),
kbps
Rear communication
protocol
Group/
Setting range
Channel 2
(R, W, P)
2S81
0...8388607
2S82
0...8388607
2S83
0...8388607
2S84
0...8388607
2S85
0...8388607
2S86
0...8388607
2S87
0...8388607
2S88
0...8388607
2S91
0...8388607
2S92
0...8388607
2S93
0...8388607
2S94
0...8388607
2S95
0...8388607
2S96
0...8388607
2S97
0...8388607
2S98
0...8388607
Parameter
Setting range Default setting Customer's
(channel 0)
V104
50 or 60 Hz
V105
0...999 min
V106
0...31
V108
0...999 min
V113
0 = not in use
1 = in use
0 = setting
group 1
1 = setting
group 2
1...254
V201
9.6/4.8
V203
0 = SPA
1 = IEC_103
2 = Modbus
RTU
3 = Modbus
ASCII
1MRS755535
Default
Custo-
setting
mer's
setting
10922
10922
10922
5461
5461
0
0
0
0
0
0
0
0
0
0
0
setting
60 Hz
10 min
31
60 min
0
0
1
9.6
0

Hide quick links: