REF610
REF610
Table 5.1.15.1.-15 Event record
Address
Signal name
671
Latest selection code
672
Sequence number
673
Unread records left
674
Time stamp of the event, date
675
Time stamp of the event, date and time
676
Time stamp of the event, time
677
Time stamp of the event, time
678
Modbus DI point or informative event (SPA channel)
DI event
*
Informative event
*
679
DI value or SPA event code
DI event
*
Informative event
*
a)
Readable and writeable register.
5.1.16.
102
Feeder Protection Relay
Technical Reference Manual - ANSI Version
a)
Structure 4
The relay's real-time clock is stored in this structure. It can be updated by presetting
the whole register structure in one Modbus transaction.
Table 5.1.15.1.-16 Real-time clock structure
Address
721
722
723
724
725
726
727
DNP 3.0 remote communication protocol
The DNP 3.0 protocol was developed by Harris Control based on the early versions
of the IEC 60870-5 standard telecontrol protocol specifications. Today, the DNP
protocol specifications are controlled by the DNP Users Group.
Range
1...3
-1...-99
1...255
0...99
0...999
0/1
0
1
0/1
0...63
Description
Year
Month
Day
Hour
Minute
Second
Hundredth of a second
1MRS755535
Comment
1 = read oldest unread record
2 = read oldest stored record
3 = clear Modbus event buffer
-1...-99 = move to the nth
newest record
2 bytes: YY.MM
2 bytes: DD.HH
2 bytes: MM.SS
0...999 ms
When MSB = 0, bits 14...0
indicate the DI point.
When MSB = 1, bits 14...0
indicate the SPA channel.
In case of a DI event, the
register will contain the DI
value.
In case of an informative event,
the register will contain the
SPA event code.
Range
0...99
1...12
1...31
0...23
0...59
0...59
0...99
Need help?
Do you have a question about the REF610 and is the answer not in the manual?
Questions and answers