Disturbance Recorder Internal Triggering And Storing; Control Parameters; Disturbance Recorder External Triggering And Storing - ABB REF610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF610:
Table of Contents

Advertisement

REF610
REF610
Table 5.1.17.-8

Control parameters

Description
Reading of the event buffer
Re-reading of the event buffer
Reading of relay state data
124
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Table 5.1.17.-6

Disturbance recorder internal triggering and storing

Event
Pickup of element
51P
Trip of element 51P
Pickup of element
50P
Trip of element 50P
Pickup of element
50P-2
Trip of element 50P-2
Pickup of element
51N
Trip of element 51N
Pickup of element
50N
Trip of element 50N
Pickup of element 46
Trip of element 46
Alarm of element 49
Trip of element 49
Σ
a)
0 = rising edge; 1 = falling edge.
Table 5.1.17.-7

Disturbance recorder external triggering and storing

Event
Weighting factor Default value of
DI1
DI2
DI3
DI4
DI5
Σ
a)
0 = rising edge; 1 = falling edge.
Parameter
L
B
C
Weighting
Default value of
factor
triggering
mask, V236
1
0
2
1
4
0
8
1
16
0
32
1
64
0
128
1
256
0
512
1
1024
0
2048
0
4096
0
8192
0
682
triggering mask,
V241
1
0
2
0
4
0
8
0
16
0
0
R, W, P
Value
R
Time, channel number and event code
R
Time, channel number and event code
R
0 = Normal state
1 = The relay has been subject to an
automatic reset
2 = Overflow of the event buffer
3 = Both 1 and 2
1MRS755535
Default value
Default value of
of triggering
storing mask,
a)
edge, V237
V238
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
751
Default value of
Default value of
triggering edge,
storing mask,
a)
V242
V243
0
0
0
0
0
0
1
1
1
1
0
1
1
1
0
1
0
0
0
0
0
0
0
0
0
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents