Arc Protection With Several Ref610 Relays; Arc Protection With One Ref610 - ABB REF610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF610:
Table of Contents

Advertisement

1MRS755535
6.2.2.
Feeder Protection Relay
Technical Reference Manual - ANSI Version
52
52
52
Fig. 6.2.1.-1

Arc protection with one REF610

Arc protection with several REF610 relays

When using several REF610 relays (see Fig. 6.2.2.-1), a REF610 protecting an
outgoing feeder will trip the circuit breaker of the outgoing feeder when detecting an
arc at the cable terminations. If the REF610 protecting the outgoing feeder detects
an arc on the busbar (via the other lens sensor), however, it will generate a signal to
the REF610 protecting the incoming feeder. On detection of the signal, the REF610
protecting the incoming feeder will trip the circuit breaker of the incoming feeder
and generate an external trip signal to all REF610 relays protecting outgoing
feeders, which in turn will result in tripping of all circuit breakers of outgoing
feeders.
For maximum safety, the REF610 relays can be configured to trip all circuit
breakers, regardless of where the arc is detected.
PO3
PO1
52
52
REF610
REF610
52
A070053
161