Technical data on protection functions

Table 5.1.4.11.-1

Elements 51P, 50P-1 and 50P-2

Feature
Set pickup value, 51P,
50P-1 and 50P-2
at definite-time
*
characteristic
at IDMT characteristic
*
Pickup time, typical
Time/current characteristic
definite-time
*
operate time, 51P TDLY,
50P-1 TDLY and 50P-2
TDLY
IDMT (mode) according
*
to IEC 60255-3
time dial, 51P TD IEC
Special type of IDMT
*
(mode) characteristic
time dial, 51P TD IEC
IDMT (mode) according
*
to IEEE C37.112
time dial, 51P TD ANSI
Resetting time, maximum 50 ms
Retardation time, typical
Set resetting time, 51P
RSET
Drop-off/pick-up ratio,
typical
Operate time accuracy
1 = recorded data and information on the
*
number of pickups of the protection
elements are retained
1 = the real-time clock is running also
*
during loss of auxiliary voltage
Element 51P
Element 50P-1
0.30...5.00 x I
(CT) 0.50...35.0 x I
n
a)
0.30...2.50 x I
(CT)
n
55 ms
30 ms
0.05...300 s
0.04...300 s
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
0.05...1.00
RI-type inverse
RD-type inverse
(RXIDG)
0.05...1.00
Extremely inverse
Very inverse
Inverse
1...15
b)
50 ms
30 ms
30 ms
0.05...2.50 s
0.96
0.96
REF610
REF610
Default setting
1
1
a)
31
Element 50P-2
(CT) 0.50...35.0 x I
(CT)
n
n
30 ms
0.04...300 s
50 ms
30 ms
0.96
69