Recorded data

Parameter V1 shows the element and phase which caused the trip. Parameter V2
shows the trip target code.
Parameters V3...V8 show the number of pickups of the protection elements,
parameters V9...V12 the number of trips of the protection elements , and parameters
V13...V24 the number of initiated auto-reclose shots.
Table 5.1.17.-3
Recorded data: Channel 0
Recorded data
Parameter (R)
Element/phase
which caused the
trip
Trip target code
Value
V1
1=I
(51P)
c
2=l
(51P)
b
4=l
(51P)
a
8=51N
16=l
(50P-1)
c
32=l
(50P-1)
b
64=l
(50P-1)
a
128=50N
256=l
(50P-2)
c
512==l
(50P-2)
b
1024=l
(50P-2)
a
2048=46
4096=49
8192=external trip
16384=AR
32768=trip of element ARC (local)
65536=trip of element ARC (remote)
0 = —
V2
1=pickup of element 51P
2=trip of element 51P
3=pickup of element 50P-1
4=trip of element 50P-1
5=pickup of element 50P-2
6=trip of element 50P-2
7=pickup of element 51N
8=trip of element 51N
9=pickup of element 50P-1
10=trip of element 50P-1
11=pickup of element 46
12=trip of element 46
13=alarm of element 49
14=trip of element 49
15=external trip
16=definite trip alarm
17=CB reclosing failed
REF610