Sgl1...Sgl8 - ABB REF610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF610:
Table of Contents

Advertisement

REF610
REF610
Switch
Function
SGR1...8/13
Alarm signal from element 49
SGR1...8/14
Trip signal from element 49
SGR1...8/15
External trip signal
SGR1...8/16
Open CB command from AR
SGR1...8/17
Close CB command from AR
SGR1...8/18
Definite trip alarm signal from AR
SGR1...8/19
CB reclosing failed signal from AR
SGR1...8/20
Shot due signal from AR
SGR1...8/21
Lockout signal from AR
SGR1...8/22
Trip signal from element ARC
SGR1...8/23
Light signal output
ΣSGR1...8
a)
If the optional I/O module has not been installed, dashes are shown on the LCD and "9999" when the parameter is read via the SPA bus.
66
Feeder Protection Relay
Technical Reference Manual - ANSI Version

SGL1...SGL8

The signals are routed to LED1 with the switches of switchgroup SGL1, to LED2
with those of SGL2, and so forth.
Table 5.1.4.10.-9
SGL1...SGL8
Switch
Function
SGL1...8/1
Trip signal from element 51P
SGL1...8/2
Trip signal from element 50P-1
SGL1...8/3
Trip signal from element 50P-2
SGL1...8/4
Trip signal from element 51N
SGL1...8/5
Trip signal from element 50N
SGL1...8/6
Trip signal from element 46
SGL1...8/7
Alarm signal from element 49
SGL1...8/8
Trip signal from element 49
SGL1...8/9
Trip lockout signal
SGL1...8/10
Definite trip alarm signal from AR
SGL1...8/11
Shot due signal from AR
SGL1...8/12
Lockout signal from AR
SGL1...8/13
CB position open
SGL1...8/14
CB position closed
SGL1...8/15
DI1 signal
SGL1...8/16
DI2 signal
SGL1...8/17
DI3 signal
SGL1...8/18
DI4 signal
SGL1...8/19
DI5 signal
SGL1...8/20
Trip signal from element ARC
SGL1...8/21
Light signal output
SGL1...8/22
Trip signal from CB Fail
Default setting
SGR1...SGR3
SGR4...SGR5
0
1
0
0
0
0
0
0
0
1
0
2108074
1MRS755535
SGR6...SGR8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5461
0
Default setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0