1MRS755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Description
Connection type
Line-idle state
Optional communication
module
Table 8.-4
Parameters for the disturbance recorder
Description
Sampling rate
Station identification/unit
number
Name of the feeder
Analog channel
conversion factor and unit
for I
, I
and I
a
b
c
Analog channel
conversion factor and unit
for the ground-fault
current
Internal trigger signals'
checksum
Internal trigger signal's
edge
Checksum of internal
signal storing mask
Post-triggering recording
length
External trigger signal's
checksum
External trigger signal's
edge
Checksum of external
signal storing mask
Table 8.-5
Auto-reclose parameters
Description
CB Closing time
Pickup delay of element
51P
Pickup delay of element
51N
Reclaim time
Parameter
Setting range Default setting Customer's
(channel 0)
V204
0 = loop
1 = star
V205
0 = light off
1 = light on
V206
0 = not in use
1 = in use
Parameter
Setting range Default setting Customer's
(channel 0)
M15
800/960 Hz
400/480 Hz
50/60 Hz
M18
0...9999
M20
Max 16
characters
M80, M81, M82 Factor
0...65535, unit
(A, kA), e.g. 10,
kA
M83
Factor
0...65535, unit
(A, kA), e.g. 10,
kA
V236
0...16383
V237
0...16383
V238
0...16383
V240
0...100%
V241
0...31
V242
0...31
V243
0...31
Parameter
Value
(channel 0)
V121
0.1...10 s
V122
0...300 s
V123
0...300 s
V124
3...300 s
REF610
REF610
setting
0
0
0
setting
800 Hz
0
- ABB -
00001, CT
00001, CT
682
0
751
50 %
0
0
0
Default setting Customer's
setting
0.2 s
300 s
300 s
10 s
171