Setting the real-time clock

How to reset the trip lockout function

The trip lockout function is used to prevent accidental closing of the circuit breaker
after a trip. The trip lockout function must be locally reset with a separate reset
before the circuit breaker can be closed again.
Reset the trip lockout as follows:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select OPERATION\TRIPLOCKOUT\LOCKOUT
RESET.
3. Press (E) to enter the setting mode. The second line will start to flash.
4. Press (E) to reset trip lockout.
5. Press to return the display to the idle mode.